BACnet Multi-Network Router

BACnet? Multi-Network Router

User Manual

Firmware 3.0 and Later

UM-BASRTB03-AA9

Trademarks

BASautomation, Contemporary Controls and CTRLink are registered trademarks of Contemporary Control Systems, Inc. BACnet is a registered trademark of the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Powered by Sedona Framework is a trademark of Tridium, Inc. Other product names may be trademarks or registered trademarks of their respective companies.

Copyright

? Copyright 2020, by Contemporary Control Systems, Inc. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language or computer language, in any form or by any means, electronic, mechanical, magnetic, optical, chemical, manual, or otherwise, without the prior written permission of:

Contemporary Control Systems, Inc. 2431 Curtiss Street Downers Grove, Illinois 60515 USA

Contemporary Controls Ltd 14 Bow Court Fletchworth Gate Coventry CV5 6SP UK

Tel: Fax: E-mail:

Tel: Fax: E-mail:

+1-630-963-7070 +1-630-963-0109 info@

+44 (0)24 7641 3786 +44 (0)24 7641 3923 info@ccontrols.co.uk

Contemporary Controls (Suzhou) Co. Ltd 19F, Metropolitan Towers, No.199 Shishan Road, Suzhou New District, 215009 China

Tel: Fax: E-mail:

+44 (0)24 7641 3786 +44 (0)24 7641 3923 info@.cn

Contemporary Controls GmbH Fuggerstra?e 1 B D-04158 Leipzig Germany

Tel: Fax: E-mail:

+49 (0)341 520359 0 +49 (0)341 520359 16 info@ccontrols.de

Disclaimer

Contemporary Control Systems, Inc. reserves the right to make changes in the specifications of the product described within this manual at any time without notice and without obligation of Contemporary Control Systems, Inc. to notify any person of such revision or change.

WARNING -- This is a Class A product as defined in EN55022. In a domestic environment this product may cause radio interference in which

case the user may be required to take adequate measures.

UM-BASRTB03-AA9 2

Contents

1 Introduction .............................................................................................................. 5 2 Specifications ........................................................................................................... 7

2.1 Electrical............................................................................................................. 7 2.2 Environmental .................................................................................................... 7 2.3 Mounting ............................................................................................................ 7 2.4 Functional........................................................................................................... 7 2.5 Regulatory Compliance ...................................................................................... 7 2.6 Electromagnetic Compatibility ............................................................................ 7 2.7 Connectors......................................................................................................... 8 2.8 Mechanical ......................................................................................................... 8 3 Power ....................................................................................................................... 9 3.1 POWER SUPPLY PRECAUTIONS.................................................................... 9 3.2 Limited Power Sources .................................................................................... 11 4 LEDs ...................................................................................................................... 12 5 Operation ............................................................................................................... 13 5.1 MS/TP Port....................................................................................................... 13

EIA-485 Bias and Termination Jumpers .................................................... 14 5.2 Ethernet Port .................................................................................................... 14 5.3 Reset IP Switch ................................................................................................ 14 6 Webpage Configuration ......................................................................................... 15 Web page navigation ................................................................................................. 19 6.1 Device Parameters........................................................................................... 20

Device Name (Default Value = BASRT-Bxxxxxx) ..................................... 20 Device Instance (Default Value = 0) ......................................................... 20 Device Location (Default Value = location) ............................................... 20 6.2 BACnet Ethernet (0 disables BACnet Ethernet) .............................................. 20 Ethernet Network (Default Value = 0) ...................................................... 20 6.3 BACnet/IP Parameters ..................................................................................... 21 BACnet/IP UDP Port (Default Value = 0xBAC0)........................................ 21

UM-BASRTB03-AA9 3

BACnet/IP Network (Default Value = 1) ..................................................... 21 IP Assigned By (Default Value = FIXED) ................................................... 21 IP Address (Default Value = 192.168.92.68) ............................................. 21 IP Subnet (Default Value = 24) .................................................................. 21 IP Gateway (Default Value = 192.168.92.1) .............................................. 22 6.4 MS/TP Parameters........................................................................................... 22 MS/TP MAC (Default Value = 00).............................................................. 22 MS/TP Network (Default Value = 2001)................................................... 22 Max Masters (Default Value = 127) ......................................................... 22 Max Info Frames (Default Value = 100) ................................................... 22 MS/TP Baud Rate (Default Value = 38400) ............................................. 23 MS/TP Tolerance (Default Selection = Strict) .......................................... 23 7. Firmware Updates ..................................................................................................... 24 8. Advanced Features and Diagnostics...................................................................... 25 8.1 Advanced Configuration Page.......................................................................... 25 8.2 Status Screen................................................................................................... 28 8.3 Routing Table ................................................................................................... 32 8.4 Security Screen ................................................................................................ 33 9 Warranty ................................................................................................................ 34 10 Returning Products for Repair ............................................................................. 35 11 Declaration of Conformity .................................................................................... 36

UM-BASRTB03-AA9 4

1 Introduction

The BASRT-B is housed in a metal enclosure which is DIN-rail mountable. The router is powered from a 24 VAC/VDC source and it is fully web page configurable using a standard web browser. It is equipped with one optically isolated MS/TP port and one 10/100 Mbps Ethernet Auto-MDIX port. It is a rugged and compact BACnet multi-network router which provides versatile stand-alone routing between BACnet/IP, BACnet Ethernet (ISO 8802-3), and BACnet MS/TP networks. By being BTL-certified, full BACnet compliance is guaranteed by completed independent interoperability testing by BTL (BACnet Test Labs) and listings obtained for both BRTR and B-BBMD device profiles.

Enhanced Diagnostics are built in and accessible from router web page: BACnet MS/TP "Status" webpage with present MS/TP device status and network statistics, in addition to a BACnet/IP "Routing" webpage with a discoverable routing table become useful when setting up or troubleshooting BACnet networks.

The MS/TP port offers a 3-pin terminal block with a removable plug for the EIA-485 connection. Up to 254 master and slave devices can be addressed through this port -- however, the attached segment can accommodate up to 31 full-load devices. MS/TP baud rates: 9600, 19200, 38400, and 76800 are supported.

The Ethernet port offers a shielded RJ-45 connector. Through auto-negotiation and AutoMDIX, it automatically matches its duplex setting, data rate and communication pair usage to whatever is needed by the attached equipment. Thus, only a straight-through CAT5 cable is needed for connection.

DHCP IP Addressing when enabled from the web page, allows the BASrouter to obtain an IP address from a DHCP server on the network automatically. FIXED IP address is the default setting. DHCP setting should be used with caution when BBMD and FDR are enabled because of the dynamic IP addressing nature of the DHCP protocol. If you are unsure use FIXED IP setting.

Reset IP switch is the user-accessible momentary switch used to reset the IP address, subnet mask and gateway address to the factory defaults. Use a paper clip to press it for a few seconds while the router is powered and then power-cycle the router to restore IP address, subnet mask, gateway address and credentials to default values of:

IP Address

192.168.92.68

Subnet Mask

255.255.255.0 (/24)

Gateway Address

192.168.92.1

Username

admin

Password

admin

Three LEDs indicate operation:

Power LED glows green when 24V is provided to BASrouter.

Ethernet LED glows green for 100 Mbps link, yellow for 10 Mbps link, and the LED will flash to indicate

network activity.

MS/TP LED flashes green when MS/TP traffic is received. When flashing continuously and without long

interruptions, the MS/TP receive LED is a good indicator that the MS/TP network is operational.

UM-BASRTB03-AA9 5

BBMD: A BACnet Broadcast Management Device (BBMD) within the router can be enabled to allow BACnet communication across routed IP networks, that is a network comprised of multiple IP subnets. If all IP devices use the same subnet, this functionality can be left disabled. The router also supports Foreign Device Registration. Attention: Be cautious when using BBMD and FDR in conjunction with DHCP IP addressing. Depending on your DHCP server settings, obtained IP address may change. If you are unsure and need to use BBMD, use FIXED IP addressing in the BASrouter. Each unit complies with Class A radiated and conducted emissions as defined by EN55022 and CFR 47, Part 15, and is intended for use in non-residential areas.

UM-BASRTB03-AA9 6

2 Specifications

2.1 Electrical

(Class 2 Circuits Only)

INPUT

Voltage (?10%): Power: Frequency:

DC

24 V 2 W N/A

AC

24 V 4 VA 47?63 Hz

2.2 Environmental

Operating temperature: Storage temperature: Relative humidity:

?40?C to +75?C ?40?C to +85?C 10?95%, non-condensing

2.3 Mounting

TS-35 DIN-rail

2.4 Functional

Physical Layer:

Cable length limit: MS/TP Baud rate (bps): MS/TP node limit:

MS/TP LED: Ethernet LED:

Ethernet 10BASE-T 100BASE-TX

MS/TP EIA-485

100 m

1200 m (for AWG 18)

9600, 19200, 38400, 76800

254 devices total, 31 full-load devices per segment

flashing green = receive MS/TP activity

green = 100 Mbps yellow = 10 Mbps flashing = activity

2.5 Regulatory Compliance

CE Mark; RoHS; CFR47, Part 15 Class A UL508 and C22.2 No. 142-M1987: Industrial Control Equipment

2.6 Electromagnetic Compatibility

Each unit complies with Class A radiated and conducted emissions as defined by EN55022 and CFR 47, Part 15. This equipment is intended for use in non-residential areas.

WARNING -- This is a Class A product as defined in EN55022. In a domestic environment this product may cause radio interference in which

case the user may be required to take adequate measures.

UM-BASRTB03-AA9 7

2.7 Connectors

3-pin (MS/TP) Pin Assignments (Also displayed on product label)

RJ-45 (MDI Ethernet) Pin Assignments

1 TD +

3 RD +

2 TD ?

6 RD ?

(All other pins are unused.)

USB Mini B Connector (Aux) This connector is only used for firmware upgrades.

EIA-485 Bias and Termination Jumpers U Install jumper to apply pull-up bias. T Install jumper to terminate bus. D Install jumper to apply pull-down bias.

(All jumpers are installed by default.)

2.8 Mechanical

Figure 1 -- 3-pin Connector Figure 2 -- RJ-45 Connector Figure 3 -- USB Figure 4 -- Internal

Figure 5 -- Product Dimensions

UM-BASRTB03-AA9 8

................
................