PowerFlex 753 and PowerFlex 755 Pre ... - Rockwell Automation

Technical Data

PowerFlex 753 and PowerFlex 755 Pre-engineered FasTrac Packaged Drives

Catalog Numbers 24F, 24G

Topic

Page

Summary of Changes

1

Product Overview

2

Catalog Number Explanation

3

Specifications

7

Options

9

Drawings

14

Maintenance

14

Enclosure Information

14

Mechanical Installation

32

Electrical Installation

34

Output Power Wiring

38

Additional Resources

41

Summary of Changes

This publication contains new and updated information as indicated in the following table.

Topic

Page

Added Fahrenheit to NEMA / UL Type 12 ambient temperature design

6

PowerFlex 753 and PowerFlex 755 Pre-engineered FasTrac Packaged Drives

Product Overview

Rockwell Automation? PowerFlexTM 753 and 755 drives are now available in a Pre-engineered FasTrac Packaged Drive program. The Pre-engineered FasTrac Packaged Drives program provides PowerFlex 750-Series drives packaged with a much larger offering of factory-mounted options than what is normally available with a standard drive product. With the Pre-engineered FasTrac program, you receive packaged PowerFlex 753 and 755 drives in as little as 20 business days.

The Pre-engineered FasTrac program is a separate, centrally managed program. It combines the capabilities of Rockwell Automation low voltage drives with the Local Solution Centers. As orders are received, they are immediately released to a manufacturing location based on capacity.

Benefits: ? A proven and tested design ? Quality drives and quick turnaround ? Pre-engineered packages to deliver sizing, wiring, and calculations ? Some ratings meet CSA requirements (contact Rockwell Automation for clarification). Available only in Canada. ? Available in an assortment of environmental protection enclosures: NEMA 1, 12, 3R, or 4X (indoor and outdoor)

This document contains information that is related to the Rockwell Automation PowerFlex 750-Series Pre-engineered FasTrac Packaged Drives program. The document is intended to provide drive catalog numbers, specifications, options and accessories, enclosures, and dimension information.

IMPORTANT

This information can be useful when specifying an application of a Pre-engineered FasTrac Packaged PowerFlex 750-Series AC drive. Be advised that this information is for reference only and subject to change at any time.

2

Rockwell Automation Publication 750-TD002E-EN-P - March 2018

PowerFlex 753 and PowerFlex 755 Pre-engineered FasTrac Packaged Drives

Catalog Number Explanation

The following catalog information is for PowerFlex 750-Series Drives Pre-engineered FasTrac packaged drives. Contact your Rockwell Automation representative for product option rules.

Position

1...3 4

5

6

7 8...10 11

12

13

14

15

16

17

24G 1 1 R D 096 A A 0 N N N N - ND - P3...

a

b

c

d

e

f

g

h

i

a

Drive

Code

Type

24F

PowerFlex 753

24G

PowerFlex 755

b

Input Type

Code

Type

1

AC & DC Input with Precharge

A

AC Input w/ precharge, no DC terminals

Code I A J

H S R X (indoor)

C (outdoor)

c

Enclosure Type and Conformal Coating

Enclosure Rating

Frame

Enclosure Style

Conformal Coating

NEMA 1 / IP20

1 Single drive Yes

NEMA 1 / IP20

2...7 Single drive Yes

NEMA 12 / IP54 (fan and filter)

1 Single drive Yes

NEMA 12 / IP54 (fan and filter)

2...7 Single drive Yes

NEMA 3R / IP24

1 Single drive Yes

NEMA 3R / IP24

2...7 Single drive Yes

NEMA 4X / IP66 (non-vented)

2...5 Single drive Yes

NEMA 4X / IP66 (fan and filter)

2...5 Single drive Yes

d

Version and Voltage Rating

Code

Input Voltage Source Type

D

480V AC

3 PH

E

600V AC(1)

3 PH

(1) Only available in Canada.

e

DC Precharge No No

Output amps, Hp ratings @ 480V AC Input

Code

Amps

ND Hp

HD Hp Frame Size

2P1

2.1

1

0.75

1 or 2

3P4

3.4

2

1.5

1 or 2

5P0

5

3

3

1 or 2

8P0

8

5

5

1 or 2

011

11

7.5

5

1 or 2

014

14

10

7.5

1 or 2

022

22

15

10

2

027

27

20

15

3

034

34

25

20

3

040

40

30

25

3

052

52

40

30

4

065

65

50

40

4

077

77

60

50

5

096

96

75

60

5

125

125

100

75

6

156

156

125

100

6

186

186

150

125

6

248

248

200

150

6

302

302

250

200

7

361

361

300

250

7

415

415

350

300

7

477

477

400

7(1)

(1) PowerFlex 755 only.

Rockwell Automation Publication 750-TD002E-EN-P - March 2018

3

PowerFlex 753 and PowerFlex 755 Pre-engineered FasTrac Packaged Drives

e (cont'd)

Output amps, Hp ratings @ 600V AC Input(1)

Code

Amps

ND Hp

HD Hp

1P7

1.7

1

2P7

2.7

2

1

3P9

3.9

3

2

6P1

6.1

5

3

009

9

7.5

5

011

11

10

7.5

017

17

15

10

022

22

20

15

027

27

25

20

032

32

30

25

041

41

40

30

052

52

50

40

063

63

60

50

077

77

75

60

099

99

100

75

125

125

125

100

144

144

150

125

192

192

200

150

242

242

250

200

289

289

300

250

(1) 600V AC rating is only available in Canada.

Frame Size 3 3 3 3 3 3 3 3 4 4 5 5 6 6 6 6 6 7 7 7

f

Filtering and Common Mode Capacitor Configuration

Code

Filtering

Default CM Cap Connection

A

Yes

Jumper removed

J

Filtered, CN jumper installed

g

Dynamic Braking

Code

Internal Resistor

Internal Transistor

A

No

Yes

N

No

No

h

HIM

Code

Version

0

No HIM - Blank plastic inserted (drive mounted)

3

Full numeric LCD HIM (drive mounted)

5

Programmer only LCD HIM (drive mounted)

6

Door mounted full numeric LCD HIM

7

Door mounted Programmer only LCD HIM

i

Code

Options

-ND

Normal duty

-HD

Heavy duty

Input Devices

-P3

Circuit breaker

-P4

Drive/Bypass mode circuit breaker

-P6

Fused disconnect

-P7

Drive/Bypass mode fused disconnect

P13

Circuit breaker (65 kA)

P14

Drive/Bypass mode circuit breaker (65 kA)

Reactors

-L1

Input reactor, 3%

-L2

Output reactor, 3%

-L3

Input reactor, 5%

-L4

Output reactor, 5%

Enclosure Options

-H1

Lexan HIM cover (with a viewing window)

-H2

Metallic HIM cover (solid door, no window)

-E5

Enclosure space heater

LK12

12 in. enclosure leg kit Available on frames 1...5 only.

LK18

18 in. enclosure leg kit Available on Frames 1...4 only.

LK24

24 in. enclosure leg kit Available on Frames 1...4 only.

PH4

4 in. Plinth for frame 6 & 7, Frame 7 with bypass and NEMA 1, 12, and 3R only

PH4A

4 in. Plinth for frame 7only without bypass and NEMA 1, 12, and 3R only

4

Rockwell Automation Publication 750-TD002E-EN-P - March 2018

Code

-B0 -B1

-C1

-F5 HF

-S51 -S59W -S59G -S59R -S60R -S60A -S68 -S53 -S54 -S55 -S57 -S66 -S85 ETM1 ETM2

i (cont'd)

Options

Option

Bypass No bypass

Manual bypass Control Power

Drive only control power, 60 Hz only Power Filtering

Transient voltage surge suppressor Externally mounted harmonic filter Operator Devices

Hand/Off/Auto selector switch (start/stop/speed reference)

Run pilot light (white) Run pilot light (green) Run pilot light (red) Drive fault pilot light (red) Drive fault pilot light (amber) Speed potentiometer (1 Turn) Control power on pilot light (white) Drive and bypass mode pilot lights (amber) Local start/stop push buttons Drive reset push button Drive/Bypass (B1, if present) disable mushroom

push button Local stop start push buttons

Elapse time meter Elapse time meter

PowerFlex 753 and PowerFlex 755 Pre-engineered FasTrac Packaged Drives

i (cont'd)

Control Interface

PS1

24V DC power supply

S56

Local / remote SEL SW

STO

PowerFlex 750 Safe Torque Off card

S67

Motor high temp circuit

S87

Motor high temp circuit

J4

Run relay with Aux that is wired to terms (8 A contacts)

J42

Run relay with Aux that is wired to terms (8 A contacts)

J2

FLT relay with Aux that is wired to terms (8 A contacts)

J22

FLT relay with Aux that is wired to terms (8 A contacts)

RS

Emergency stop circuit W/Safe Torque Off

SIB

SCADA interface I/O option

SIA

SCADA interface I/O option

AP

Approval Drawings

Feedback

-F0

None

-F1

Standard encoder

I/O

N

None

-IA

Standard

-IB

Standard

Communication

-MN

None

-MD

DeviceNet

-MC

ControlNet (coax)

-MF

ControlNet (fiber)

-MS

RS-485 DF1

-MH

RS-485 HVAC

-MP

PROFIBUS DPV1

-MI

INTERBUS

-ME

EtherNet/IP

-MB

BACnet/IP

-MT

Dual-port EtherNet/IP

Rockwell Automation Publication 750-TD002E-EN-P - March 2018

5

................
................

In order to avoid copyright disputes, this page is only a partial summary.

Google Online Preview   Download