AR-716-E16

ACCESS & INDUSTRIAL CONTROL

AR-716-E16

V220912

Contents

1 Product

2 Panel Mounting Base (AR-716-E16-X)

3 Metal Box (AR-716-E16-M)

Option

Option

AR-701B-X Fit 35mm DIN Rail or Mount directly

Specification

CPU

32bit / ARM32 72MHz / Flash 512KB Temperature

20 70

Memory

2048KB (2MB)

Digital Input

2 Door Open Button/ 2 Door Sensor/ 1 Fire-alarm

Power Supply 9 ~ 24VDC

Relpy Output 2 Door Relay / 1 Alarm Relay

Power Consumption < 3W

Door Relay Time Toggle, 0.1~600 Sec.

Interface /

RS-485 : 9600 bps (N, 8, 1) Alarm Relay Time Toggle, 0.1~600 Sec.

Baud Rate

Ethernet : 10/100M Base T

User Capacity 16,000 (Default value) / 32,000 / 65,000

External Readers 2 RS-485 + 2 WG

Event log

32,000

Aux. WG Port Anti-pass-back Lift Control Door Group Time Zone Real-time Clock DIP_SW

WG 26 / WG 34 16 Doors Yes 255 63 (stand-alone /networking) YES 8 (Node ID: 1~254)

Connector Table

POWER BUSY (REV)

LED

ON 1 2 3 45 6 7 8

CN15 CN13/CN14/CN12 CN10/CN11/CN9

21 7 65 4 3 2 1 7 65 4 3 2 1

GND Fire WG PORT0 Dip-switch ALM

WG PORT1

Reset (Hold till BUSY LED is blinking)

LED

Host

21

Host TX Host RX CH1 TX CH1 RX CH2 TX CH2 RX

LED

CH1

21

LED

CH2

21

TCP/IP Module

Relay LED

K1 K2 K3 Door Door ALM

N.O.

N.O.

N.O.

Door/Alarm Relay Ouput Power 65 43 21 43 21

CN1 CN2 CN3 CN18 CN4/CN5/CN6 CN7/CN8

Connector CN1 Host RS-485

Code

Pin Description

LA+

1 Host RS-485(A+)

LB-

2 Host RS-485(B-)

Connector: CN2 CH1 Slave RS-485

Code

Pin Description

LA+

1 RS-485(A+)

LB-

2 RS-485(B-)

Connector CN4/CN5/CN6 WG Door / Alarm Relay

Code

Pin Description

Alarm Relay

1 K3-N.O./N.C.

Output

2 COM

Door 1 Relay

3 K2-N.O./N.C.

Output (WG1)

4 COM

Door 0 Relay

5 K1-N.O./N.C.

Output (WG0)

6 COM

Connector CN3 CH2 Slave RS-485

Code

Pin Description

LA+

1 RS-485(A+)

LB-

2 RS-485(B-)

Connector CN15 Fire-alarm Input

Code

Pin Description

Fire-ALM

1 Fire-alarm Input

GND

2 DC Power 0V Output

Connector CN7/CN8 Power Supply

Code

Pin Description

GND

1 0V Input

VIN (716-E16) 2 12VDC Input

GND

3 0V Output

VOUT(Slave units) 4 12VDC Output

Connector CN9/CN10/CN11 WG Port 1

Code

Pin Description

WG0

1 Wiegand DAT: 0 Input

WG1

2 Wiegand DAT: 1 Input

BZ

3 Beeper Output

LEDG

4 LED Green Output

LEDR

5 LED Red Output

SEN (N.C.)

6 Door Status Input

EGR: PB (N.O.) 7 Exit Button Input

Connector CN12/CN13/CN14 WG Port 0

Code

Pin

WG0

1

WG1

2

BZ

3

LEDG

4

LEDR

5

SEN (N.C.)

6

EGR: PB (N.O.) 7

Description Wiegand DAT:0 Input Wiegand DAT:1 Input Beeper Output LED Green Output LED Red Output Door Status Input Exit Button Input

Connector CN18 Host TCP/IP

Code

Pin Description

TCP/IP Socket 1 CAT5

Installation

231 mm 117 mm

110 mm 80 mm

Metal Box

Plastic Mounting Base

175 mm 90 mm

180 mm 93 mm

- 1 -

16 Doors IP Control Panel

Hardware Architecture

WG Port 0

WG Port 1

V220912

Fire

Door Sensor Push Button

Wiegand Reader

Door Sensor Push Button

Wiegand Reader

CN15

CN12~14

CN9~11

SOYAL

or

or

Converter Converter AR-727-CM AR-321-CM

CN1 CN2 CN3

CN18 CN4 CN5 CN6 CN7 CN8

Door Lock for WG Port 0

Door Lock for WG Port 1

CH1 support two wiring method:

1 CH1 supports WG1 & WG2 & 6 doors (WG1 & WG2 & Subnode 3~8)

2 CH1 supports 8 doors (Subnode 1~8)

CH1

CH2

or

or

Magnetic Lock or Electric Bolt

Magnetic Lock or Electric Bolt

CH2 supports 8 doors (Subnode 9~16)

WG

Node ID 003 Node ID 004 Node ID 005

Reader

WG

Node ID 008

Reader

Node ID 009 Node ID 010 Node ID 011 Node ID 012 Node ID 013 Node ID 014 Node ID 015 Node ID 016

AR-0600M-270 Magnetic Lock

AR-0600M-270 Magnetic Lock

AR-0600M-270 Magnetic Lock

AR-101PBI-L Push Button

AR-101PBI-L Push Button

AR-101PBI-L Push Button

Controller

Each reader under CH/CH2 is able to connect input and output devices according to the requirements (such as: exit button/door sensor /electric magnetic lock/electric bolt lock/electric strike )

AR-1207 Electric Bolt

AR-1207

AR-1207

WG Reader

WG

WG

Controller

Controller

Controller

- 2 -

ACCESS & INDUSTRIAL CONTROL

AR-716-E16

Wiring Diagram

Fire

COM N.O.

WG Port 0

SOYAL SOYAL Door Sensor

SOYAL PSusOhYABLutton DNo.oOr. Sensor

WG Port 1

1 23 456 789

*0#

Wiegand Reader Push Button

1 23 456 789

*0#

Wiegand Reader

N.C.

N.O.

ON

1 2 3 45 6 7 8

Node ID is set by DIP_Switch, Node ID: 001~254

~

Value DIP SW Node 01 Node 02 Node 03

1 2 4 8 16 32 64 128 12345678 ON Off Off Off Off Off Off Off Off ON Off Off Off Off Off Off ON ON Off Off Off Off Off Off

Node 253 ON Off ON ON ON ON ON ON Node 254 Off ON ON ON ON ON ON ON

LEDG BZ

EGR: PB (N.O.) CN10 SEN (N.C.)

LEDR

WG1 WG0

LEDG BZ

EGR: PB (N.O.) CN13 SEN (N.C.)

LEDR

GND CN15 Fire-ALM

CN11

CN12

CN14

To PC

Port 0

Port 1

BZ RLED GGLLEEDD WG 1 WG 0

0V 12V BZ RLED GGLLEEDD WG 1 WG 0 0V 12V

+ ?

ON 1 2 3 45 6 7 8

+ ?

CN9

WG1 WG0

V220912

POWER

12~24V

If the wire length of Controller and Reader is more than 100 meters, it is recommended NOT to use the "Wiegand Power." Check connection mode within the dashed box: Controller and Reader must use the "common-COM-point."

POWER 12~24V

(REV) BUSY Reset POWER

K3 Alarm

K1: WG PORT0 N.O. Door

K2: WG PORT1 N.O. Door

TCP/IP Module (Optional)

HUB

USB

CH1 CN2 CH1 TX CH1 RX

CH2 CN3 CH2 TX CH2 RX

Host TX Host RX

TCP/IP RJ45

CN18

Host CN1

or

or

Converter AR-727-CM

Converter AR-321-CM

+

+

+

Ethernet

N.O.(Jumper)

COM CN4 Door 0

COM Door 1

CN5

COM Alarm

CN6

VOUT(Slave units)

GND CN7

N.O.

VIN (716-E16) GND CN8

Door Lock for WG Port 1

Electric Bolt Door Lock for WG Port 0 or

Magnetic Lock

Electric Bolt

or +

+

Magnetic Lock

+

......

1 23 456 789

*0#

Node ID 008 Controller

Node ID 002 Node ID 001 Controller Controller

RS-485 CH1/CH2 Port Connect to Electric Lock

?

POWER 12~24V

+

1 23 456 789

*0#

......

Node ID 009 Node ID 010 Node ID 011 Node ID 012 Controller Controller Controller Controller

Node ID 016 Controller

Lock Power 12~24V

?

+

N.O. N.C. COM SEN PB ALM 12V 0V

1 23 456 789

*0#

Controller

N.C.

SOYAL SOYAL

Door Sensor

N.O.

+

+

Push Button Electric Strike Electric Bolt or Magnetic Lock

- 3 -

16 Doors IP Control Panel

IP Setting

Open your Web Browser and input factory default IP

address:

If the IP address of AR-716-E16 has been changed, we must enter the new IP address.

Page menu

Current Status

Monitor the on-line computer

Network Setting

IP Setting

User Password

Change the Log-in information

Current State Online Status is able to be monitored showing which computer is linking on Ethernet Module

Current IP address of the AR-716-E16

Log-in User Password

When you choose the "Networking Setting" or "User Password," Log-in window will pop out and please input user name and password. At the Factory Default Status -

User name: SuperAdm Password: 721568

Networking Setting

You will see initial IP Address 192.168.1.127 and make sure MAC Address is identical to the sticker on Ethernet Module device. Please alter the IP address as you want, and then click "Update" button. After updating the IP, please re-connect the Web Browser with the new IP address.

User Password Change the log-in password to lock the IP setting of Ethernet Module. The password can be made up of 10 characters at most, and it can be either A~Z or 0~9.

- 4 -

V220912

ACCESS & INDUSTRIAL CONTROL

AR-716-E16

V220912

Initial Setup:

Software: Connection

1. Open the "701 Server" Software There are two ways to open the Communication Port setting window:

and Communication Port Setting

a

c e

a. According to the computer Detection results to select the port (Use the RS-485)

b b. Select [TCP/IP Oonly] (Use the Ethernet) c. Select the option: Polling Message From Controller

d d. Polling Interval: 200ms - meaning the PC polls the controller every 200ms once it accesses the message from the controller

e. Click YES

2. After COM Port setting, there are two ways to open the Node Number for Polling window:

and

Node Number for Polling

f. Select node ID (for example:001) and access controller

" 327E/3xxE/7xxE/8xxE/716Ev5"

g. If use the Ethernet mode, please check the "IP"; if use the RS-485

mode, there's no need to check

f

g

h

h. If use the Ethernet mode, input IP in "IP Address" column

(Default value: 192.168.1.127)

i i. Input 1621 in "Port" column(Default value: 1621; the Port number

is predetermined by SOYAL for connection to the network)

j. Select LAN BASE

k. Click YES

3. Open Controller On/Off Line window to check the device connection status:

Well: controller successfully connected to PC. Not connected well: the following checks are required.

Software: Parameters Settting: Door Number and Users Edit

1. After the 701Server Software connection, go click 82xEv5 Parameters Setting

to set up 716-E16's door number

a. Roll and select the Targe Node ID of 716-E16 (The same as the dip-switch) b. Click "Read" to read back the parameter of 716-E16 c. Click "716-E16" button to set up Door Number d. Input the new Door Number of Slave Reader, which door number must be unique and non-repetitive

- 5 -

................
................