Obs-
301 Industrial Boulevard
Tullahoma, TN 37388
Phone: 931.454.9940 ~ Fax: 931.454.2338
Dollar Tree MEP Site Observation Report
|Mall Name: Gulf Harbor Plz |Date: 23DEC14 |
|Address: 4758 – 4770 US Hwy 19 |Deal #: 8739 |
|City, State: New Port Richey, FL |ORA File: 617114 |
General Summary:
Space is LLB with new HVAC by DTS per SLM. Space has adequate HVAC capacity with the 8 units existing but has old equipment for the most part. Several units are horizontal discharge above the roof and with changing should be changed to conventional downflow units. Space needs about 32 tons with the west storefront, space has insulation on top of grid. Space shows signs of roof leaks also. Ductwork is ductboard and food service comprised the larger space and needs replacing, probably better to replace it all. Space has power, water, sewer, and sprinkler. Space has no basement, no mezzanine, no wood construction was noted. Grease waste will need to be avoided for sewer service.
The (2) 200A 208Y120V services in spaces 4760 and 4762 could possibly be used for the DTS fit-out if there is no freezer/cooler package, If there is a f/c package, then a 600A service may be required. The distribution wireway is directly behind the DTS space.
LOI Summary:
Not Available VB LLB AS-IS Expansion
HVAC By: DTS LL
Utility Separation DTS LL LL Stub-In Only
General Info:
Storefront Direction: North South East West
Power Still On: Yes No
Insul. Top of Grid: Yes No
Roof Height 13’-1 Fixed Ladder Required: Yes No
Sprinkler Main Height 10’-3
Permanent Fixed Ladder Location N/A
Roof Insulation Thickness UTD
Does the building have a Basement Yes No Partial
Does the building have a Mezzanine Yes No
Is there Wood Construction Yes No Partial
Mechanical:
HVAC Equipment Information:
Unit |Mfgr |Model |Serial # |Size |Age |SASD |RASD |Comments | |1 |ICP |PA5560 |L99323841 |5 |15 | | | | |2 |ICP |PA5560 |G050511130 |5 |9 | | | | |3 |UTD |UTD |UTD |5? | | | | | |1a |Trane |TSC060 |632102745L |5 |8 | | | | |2a |Trane |TSC060 |636103164L |5 |8 | | | | |3a |Trane |TSC060 |638100930L |5 |8 | | | | |4a |Carrier |TFF008 |1904G30303 |7.5 |10 | | | | |8 |Trane |SA00B856 |C85F067L8 |7 |24 | | | | |Total area: 10500 sqft @ 45? tons EXISTING= 233 sqft/ton Existing
Estimated Requirement: @ 325 sf/ton – 32.3 tons Estimated As Referenced by LOI
How much of the ductwork can be reused? Majority Half None
If Ductwork Re-used, existing Diffusers Need Replacing Clean/Paint/Reuse Likely
The ductwork is constructed of: Sheet Metal Fiber Ductboard.
Insulation: Lined Wrapped
Ductwork Clearance Issues: Yes None Noted Inches Clear above 12’ Ceiling/Below Struct.
Water & Sewer:
Utility Company No Info On Meter
Phone #:
Meter #
Water Meter /service location: Rear: Left Center Right Outside DTS Space: FT Left Right
Front: Left Center Right
Side: Left Right Front Center Rear
Water Into Space Yes No Location: Rear: Left Center Right
Size:
Sewer Location: Rear: Left Center Right Outside DTS Space: FT Left Right
Front: Left Center Right
Side: Left Right Front Center Rear
Manhole Location: Rear: Left Center Right FT
Front: Left Center Right FT
Side: Left Right Front Center Rear
Toilet room location: Rear: Left Center Right Outside DTS Space: FT Left Right
Front: Left Center Right
Side: Left Right Front Center Rear
Gas:
Utility Company LP Tanks
Phone #:
Meter #
Gas meter/service location: Rear: Left Center Right Outside DTS Space: FT Left Right
Front: Left Center Right
Side: Left Right Front Center Rear
Gas Piping Routed: Above Ceiling On Roof
Fire Sprinkler:
Sprinkler riser location: Rear: Left Center Right Outside DTS Space: FT Left Right
Front: Left Center Right
Side: Left Right Front Center Rear
Sprinkler Co. Tag Missing – No Info
Phone #:
Gauge Pressure 90 PSI
Electrical:
Utility Company Progress Energy Florida
Phone #:
Meter # 470-119-184-533 / 4768-139-82-613 / 4764-119-184-532 / 4760-119-184-534 /
4758-119-185-047 / (House) 4776-119-185-049
Electrical Service: Single Service Multiple Services / 6 Services
Overhead Underground
Can Multiple Meters be Used Yes No Unknown
Served by Multiple Transformers Yes No Unknown
Electrical Service Voltage: 277/480V/3ph 120/208V/3ph 120/208/1ph Other?
208/120 XFMR / kVA Inside DTS Space
Riser Diagram Attached
The (2) 200A 208Y120V services in spaces 4760 and 4762 could possibly be used for the DTS fit-out if there is no freezer/cooler package, If there is a f/c package, then a 600A service may be required. The distribution wireway is directly behind the DTS space.
Service amperage size: (2) * 200A + (4) * 100A Amps Clarify if Multiple
Estimated Required Service: 400 Amps WITHOUT C/F Package
Estimated Required Service: 600 Amps WITH C/F Package
New Service Needed/Estimated
Electrical meter location: Rear: Left Center Right Outside DTS Space: FT Left Right
Front: Left Center Right
Side: Left Right Front Center Rear
Inside LL Meter Room LL Meter Room Part of DTS Space
Service Disc.t location: Rear: Left Center Right Outside DTS Space: FT Left Right
Front: Left Center Right
Side: Left Right Front Center Rear
Inside LL Meter Room LL Meter Room Part of DTS Space
Panel location: Rear: Left Center Right Outside DTS Space: FT Left Right
Front: Left Center Right
Side: Left Right Front Center Rear
Inside LL Meter Room LL Meter Room Part of DTS Space
Panel Type: MLO Main Circuit Breaker Both
Panelboards: Re-usable Need Replacing (Mostly)
Wiring: Pipe & Wire MC Cable
Romex Other:
Lighting: T-8 T-12
Ballast Verification: N/A
Sales - Lamps per Fixture
Incandescent Other:
Fire Alarm:
Control Panel: Rear: Left Center Right Outside DTS Space: FT Left Right
Front: Left Center Right
Side: Left Right Front Center Rear
The fire alarm was only in spaces 4760 and 4762.
................
................