General

Load voltage and bypass line voltage shall be 480VAC, three-phase, three-wire plus ground. Input voltage shall be 480VAC, three-phase, three-wire plus ground. Battery [ choose (1): VRLA, PURE LEAD, LITHIUM] shall support the UPS at 100% rated kW load for at least _______ minutes at startup (initial run time) OR _____ minutes at end of life (EOL ... ................
................