Model: Frequency: 50 Fuel Type: Diesel - Cummins

? Generator set data sheet

Model: C700 D5 Frequency: 50 Fuel Type: Diesel

Our energy working for you.TM

Spec sheet: Noise data sheet (Open/enclosed): Airflow data sheet: Derate data sheet (Open/enclosed): Transient data sheet:

Fuel consumption

Ratings Load gph L/hr

Engine

Engine manufacturer Engine model Configuration Aspiration Gross engine power output, kWm BMEP at set rated load, kPa Bore, mm Stroke, mm Rated speed, rpm Piston speed, m/s Compression ratio Lube oil capacity, L Overspeed limit, rpm Regenerative power, kW Governor type Starting voltage

Fuel flow

Maximum fuel flow, L/hr Maximum fuel inlet restriction, mm Hg Maximum fuel inlet temperature (?C)

Air

Combustion air, m3/min Maximum air cleaner restriction, kPa

Standby

kVA (kW)

706 (565)

1/4

1/2

10.8

17.6

49.00

80.00

SS12-CPGK ND50-OSHHP / ND50-CS550 AF50-HHP DD50-OSHHP / DD50-CSHHP TD50-HHP

3/4 25.1 114.00

Full 33.8 154.00

Prime

kVA (kW)

640 (512)

1/4

1/2

9.5

16.0

43.00 73.00

3/4 22.9 104.00

Standby rating

Prime rating

Cummins

VTA28-G5

Cast Iron, 40? V12 Cylinder

Turbo Charged and After-Cooled

612

560

1751

1599

140

152

1500

7.6

13.1:1

83

1850 ?50

75

Electronic

24 Volts DC

Full 30.8 140.00

337 203 70

52.60 6.2

49.50

?2010 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand and "Our energy working for you." are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.

Exhaust

Exhaust gas flow at set rated load, m3/min Exhaust gas temperature, ?C Maximum exhaust back pressure, kPa

Standard set-mounted radiator cooling

Ambient design, ?C Fan load, KWm Coolant capacity (with radiator), L

Cooling system air flow, m3/sec @ 12.7mmH2O

Total heat rejection, BTU/min

Maximum cooling air flow static restriction mmH2O

Standby rating 122.8 507.2 10.2

40 19.6 125 12.45 21610 19.1

Prime rating 119.1 493.3

19310

Open set derating factors kVA (kW)

Note: Standard open genset options running at 400V, 150m above sea level. For enclosed product derates, please refer to datasheet - DD50CSHHP.

For 380V product derates, please consult the factory for details.

27?C

40?C

Standby

701 (561)

703 (562)

45?C 689 (551)

50?C 668 (534)

55?C 646 (517)

Prime

640 (512)

640 (512)

636 (509)

630 (504)

610 (488)

Weights*

Unit dry weight kgs

Unit wet weight kgs

Open 5491 5760

Enclosed RTF RTF

* Weights represent a set with standard features. See outline drawing for weights of other configurations

Dimensions

Standard open set dimensions Enclosed set standard dimensions

Length 4047 RTF

Width 1608 RTF

Height 1942 RTF

Genset outline

Open set

Enclosed set

Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.

?2010 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand and "Our energy working for you." are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.

Alternator data

Feature code

Connection1

B729

Wye, 3 Phase

B680

Wye, 3 Phase

Temp rise degrees C Duty2

150/125C

S/P

150/125C

S/P

Alternator HC6G HC5F

Voltage 380-440V 380-415V

Ratings definitions

Emergency Standby Power (ESP)

Limited-Time running Power (LTP):

Prime Power (PRP)

Base Load (Continuous) Power (COP)

Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. Emergency Standby Power (ESP) is in accordance with ISO 8528. Fuel Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514.

Applicable for supplying power to a Applicable for supplying power to Applicable for supplying power

constant electrical load for limited varying electrical load for unlimited continuously to a constant electrical

hours. Limited Time Running

hours. Prime Power (PRP) is in load for unlimited hours.

Power (LTP) is in accordance with accordance with ISO 8528. Ten Continuous Power (COP) in

ISO 8528.

percent overload capability is

accordance with ISO 8528, ISO

available in accordance with ISO 3046, AS 2789, DIN 6271 and BS

3046, AS 2789, DIN 6271 and BS 5514.

5514.

Formulas for calculating full load currents:

Three phase output

kWx1000 Voltagex1. 73x0.8

Single phase output

kWxSingleP haseFactor x1000 Voltage

See your distributor for more information.

Cummins Power Generation Manston Park, Columbus Avenue Manston, Ramsgate Kent CT12 5BF, UK Telephone: +44 (0) 1843 255000 Fax: +44 (0) 1843 255902 E-Mail: cpg.uk@ Web:

?2010 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand and "Our energy working for you." are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.

................
................

In order to avoid copyright disputes, this page is only a partial summary.