Building Condition Assessment Survey 2021 - 2022

Architectural Inspection

Q226

Asset:

I.S. 226 - QUEENS, 121-10 ROCKAWAY BLVD, New York, 11420

Inspection Id Inspection Type

Time In

Last Edited

SA : Q226 AA : Q226

Asset Data

Architectural - Senior Architectural - Associate

2021-12-09 12:11 PM 2021-12-09 11:10 AM

2021-12-16 4:29 PM 2021-12-18 10:01 AM

Question

Answer

Was the building fully accessible for inspection Inspection Access Comment

Principal(s) Information

No

Awnings/Canopy, Areaways 1, 4, Window Lintels, Exterior Guards (Staging, Scaffolding and Netting); Boys and Girls Shower Rooms (sealed)

Principal Name Organization Did you meet with this Principal? Did this Principal provide feedback? Summary of Principal's Feedback

Dr. Maureen Hussey

I.S. 297 - Hawtree Creek Middle School - Queens

No

Yes

Principal Secretary Nicole Napolitano on behalf of the Principal provided comments as follows: 1. All corridor drinking water fountains should be with a filtration system. 2. Students and Staff Toilet Rooms need to be upgraded on the 2nd Floor.

Principal Name Organization Did you meet with this Principal? Did this Principal provide feedback? Summary of Principal's Feedback

Subhas Mohan Q314 Epic High School South - Queens No Yes Assistant Principal Luis Amaya, on behalf of the Principal has no comments regarding the physical condition of the building at this time.

Principal Name Organization Did you meet with this Principal? Did this Principal provide feedback? Summary of Principal's Feedback

Michael Potwardski I.S. 226 - Queens Yes Yes The Principal had no comments regarding the physical condition of the building at this time.

Principal Name Organization Did you meet with this Principal? Did this Principal provide feedback? Custodian Fireman Building Square Footage Comments on the Area Comments on the Stories (Floors) plus Basements Comments on the Number of Classrooms Comments on the Year Built Student Population Staff Population Weather

Debbie Edmonds P233Q (District 75) - Queens No No Robert Langone Jr. John Rabuse 209,000 None 4+B+PH 89 1974 1,679 196 Fair

PB/A&W

Page 1 of 45

Print Date: 6/28/2022

Architectural Inspection

Facade Photo

NYC Department of Education Building Condition Assessment Survey 2021 - 2022

Q226

Main Entrance Photo

Corner of Rockaway Blvd and 121st Street - Southeast View

Roof Photo

Facade A - Rockaway Blvd

PB/A&W

Roof 1 - Northeast View Page 2 of 45

Print Date: 6/28/2022

NYC Department of Education

Building Condition Assessment Survey 2021 - 2022

Architectural Inspection

Q226

Have any Systems/Major Building Components been upgraded?

Have there been any New Building Additions? Comments on New Building Additions Tandem Schools? Leased Space?

Yes

Systems:

Partial Roofing and Flashing repairs; Partial Coping and Roof Barrier replacement; Exterior Walls repointing and repairs; Foundation Walls waterproofing; Partial Exterior entry steps and pavement replacement.

Year:

Under Construction

Systems: (2) Students Toilet Rooms in the Original Building converted to HC compliance.

Year:

2021

Systems: Partial (3) Exterior Doors replacement; Partial Roofing and Bulkhead Roof waterproofing.

Year:

2020

Systems: Schoolyard upgrade.

Year:

2018

Systems: New Science Labs Rooms 207, 307.

Year:

2015

Systems:

Roofing and Flashing replacement at Roofs 1, 2, 4 and Penthouse Roofs 5, 6; Partial Parapets, Chimney and Bulkhead Walls repointing; Bulkhead Doors replacement; Library upgrade.

Year:

2012

Systems: Auditorium Roofing and Flashing replacement.

Year:

2006

Systems: Windows and Window Guards replacement; Exterior Doors replacement.

Year:

2002

Yes

2000 (+34,000 S.F.)

No

No

Priority Condition

Priority Condition Exist Last Year?

Yes

Priority Category

Potential Falling Debris

Condition Description

Severely rusted Stair is a potential safety hazard

Component Affected

Location Description

INTERIOR | STAIRS/RAMP S: INTERIOR | Ceiling

Stair C/3

Person(s) Notified

John Rabuse

Person(s) Title PhotoImage Fireman

Structural Engineer Required

Structural Condition Type

Condition Description

Component Affected

Location Description

Person(s) Notified

No condition recorded

Accessibility

Accessibility Status Question

Is the primary or secondary entrance on an accessible route? Is the building a multi-story building? Are all floors of the building accessible through compliant means? Accessible classrooms exists on each floor? Boys and Girls or Unisex accessible toilets exist on at least every other floor? If the following spaces exist, are they ALL accessible? Art Room, Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs

Person(s) Title

Response Yes Yes Yes Yes Yes Yes

PhotoImage

PB/A&W

Page 3 of 45

Print Date: 6/28/2022

Architectural Inspection

Physical Breakdown Structure

NYC Department of Education Building Condition Assessment Survey 2021 - 2022

Exists Required Complies Deficiency

FUNCTIONAL ACCESSIBILITY Exterior Routes Exterior Entrances & Exits Exterior H/C Lifts Exterior Ramps and Railings

Yes

No

No

No

No

Interior Routes Corridor and Lobby H/C Lifts Interior Corridor Doors and Hardware Interior Corridors and Lobbies Interior Elevators Interior Lobby Doors and Hardware Interior Ramps

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Rooms & Spaces Art Rooms

Room 441

Yes

Yes

Auditorium

1st Floor

Yes

Yes

Cafeteria

1st Floor Students - Addition, 1st Floor - Yes

Yes

Original Building, 1st Floor - Staff

Classrooms

1st-4th Floor

Yes

Yes

Computer Rooms

Rooms 282, 439

Yes

Yes

Gymnasium

2nd Floor

Yes

Yes

Library

Room 329

Yes

Yes

Main Office

Room 103 (I.S. 226); Room 176 (I.S. Yes

Yes

297); Room 381 (P233Q - District 75);

Room 403 (Epic HS South)

Multi-purpose Room

No

Nurse's Room

Rooms 117A, 378

Yes

Yes

Pool

No

Science Lab

Rooms 205, 207, 305, 405, 407

Yes

Yes

Toilet Rooms (Boys)

1st-4th Floor

Yes

Yes

Toilet Rooms (Girls)

1st-4th Floor

Yes

Yes

Toilet Rooms (Staff)

1st-4th Floor

Yes

Yes

Q226

Assistive Fire Listening Alarm System Strobe

FM

Yes

FM

Yes

FM

Yes

PB/A&W

Page 4 of 45

Print Date: 6/28/2022

NYC Department of Education

Building Condition Assessment Survey 2021 - 2022

Architectural Inspection

Q226

Building Template

Inspection

Question Architectural

EXTERIOR AREAWAY Instance on AW1, AW4 Instance Quantity Instance Quantity Uom

Instance on AW2, AW3 Instance Condition Instance Quantity Instance Quantity Uom Deficiency AWNINGS AND CANOPIES CHIMNEY Material Type(s) Condition Deficiency

Roof Plan reference

PB/A&W

Deficiency Quantity Quantity Uom Potential Action Urgency of Action

Response

Inspected Inspected Inaccessible 2 EACH Inspected 2 - Between Good and Fair 2 EACH No deficiencies recorded Inaccessible Inspected Masonry 3 - Fair BRICK: DETERIORATED LADDER

1 EACH REPLACE PRIORITY 3

Page 5 of 45

Print Date: 6/28/2022

Architectural Inspection

Question EXTERIOR CHIMNEY Purpose of Action Deficiency Photo1

NYC Department of Education Building Condition Assessment Survey 2021 - 2022

Response

LEVEL 2

Q226

Violations COPING CORNICE DOORS

DOORS AND FRAMES Condition Deficiency

Roof Plan reference

Roof 1 No violations recorded.

Under Construction Does not Exist Inspected Inspected 3 - Fair METAL: DETERIORATED DOOR AND FRAME - MINOR DETERIORATION

Deficiency Quantity Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo1 Violations

DOOR HARDWARE Condition Deficiency

LINTELS Condition Deficiency

TRANSOM/SIDE LIGHT Condition Deficiency

EXTERIOR WALLS Material Type(s) Replacement Quantity

PB/A&W

9 EACH MAINTENANCE PRIORITY 3 LEVEL 2 No photo recorded No violations recorded.

Inspected 3 - Fair No deficiencies recorded Inspected 2 - Between Good and Fair No deficiencies recorded Inspected 2 - Between Good and Fair No deficiencies recorded Inspected Masonry, Concrete 50,000

Page 6 of 45

Print Date: 6/28/2022

Architectural Inspection

Question EXTERIOR EXTERIOR WALLS Replacement Uom Instance on All Facades Instance Quantity Instance Quantity Uom

EXTERIOR SOFFITS Condition Deficiency

LOADING DOCK LOUVER

Condition Deficiency Roof Plan reference

NYC Department of Education Building Condition Assessment Survey 2021 - 2022

Response

S.F. Under Construction 50,000 S.F. Inspected 2 - Between Good and Fair No deficiencies recorded Does not Exist Inspected 3 - Fair MAJOR RUSTING

Q226

Elevation

Deficiency Quantity Quantity Uom Potential Action Urgency of Action Purpose of Action Deficiency Photo1

Violations PARAPETS

Material Type(s) PB/A&W

10 S.F. REPLACE PRIORITY 4 LEVEL 2

Facade B No violations recorded.

Inspected Masonry, Concrete Page 7 of 45

Print Date: 6/28/2022

NYC Department of Education

Architectural Inspection

Question EXTERIOR PARAPETS Replacement Quantity Replacement Uom Instance on All Facades Instance Condition Instance Quantity Instance Quantity Uom Deficiency PLAZA DECK ROOF Roofing Replacement Quantity Replacement Uom

Building Condition Assessment Survey 2021 - 2022

Response

8,000 C.F. Inspected 2 - Between Good and Fair 8,000 C.F. No deficiencies recorded Does not Exist Inspected Inspected 66,000 S.F.

ROOF HATCH/SMOKE HATCH Condition Deficiency

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Condition Deficiency

ROOF BARRIER Condition Deficiency

ROOF CAGE ROOF FENCE ROOFING

Instance on Modified Bitumen: Roofs 1, 2, 5, 6 Instance Condition Instance Quantity Instance Quantity Uom Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? Installation Year Source of Installation Deficiency Instance on Built-Up: Roof 3 Instance Condition Instance Quantity Instance Quantity Uom Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? Installation Year Source of Installation Deficiency Instance on Single Ply, Fully Adhered Roof: Roof 4 Instance Condition Instance Quantity Instance Quantity Uom Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing?

Inspected 2 - Between Good and Fair No deficiencies recorded Inspected 2 - Between Good and Fair No deficiencies recorded Inspected 2 - Between Good and Fair No deficiencies recorded Does not Exist Does not Exist Inspected Inspected 2 - Between Good and Fair 46,000 S.F. No

2012 Custodial Staff No deficiencies recorded Inspected 3 - Fair 10,000 S.F. No

2006 Custodial Staff No deficiencies recorded Inspected 3 - Fair 10,000 S.F. No

PB/A&W

Page 8 of 45

Q226 Print Date: 6/28/2022

................
................