Trip units shall provide zone selective interlocking (ZSI) for the short-time delay and ground fault delay trip functions for improved system protection and arc energy reduction. For faults within the protected zone, the zone interlocking system shall override programmed time delays to allow the upstream breaker to trip with minimal time delay. ................
................