 SECTION 23 52 00HEATING BOILERS Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2016 - 2016 ARCAT, Inc. - All rights reserved** NOTE TO SPECIFIER ** Slant/Fin Corp.; boilers and baseboard heating equipment.This section is based on the products of Slant/Fin Corp., which is located at:100 Forest Dr.Greenvale, NY 11548Tel: 516-484-2600Fax: 516-484-5921Email: request info (marketing@)Web: [ Click Here ] for additional information.Since 1949Slant/Fin is America's largest manufacturer of baseboard heating equipment. We are a family owned business whose culture is built around customer service and building of trust and relationships. We are one of the top manufacturers of gas and oil fired hot water and steam boilers with manufacturing facilities in Greenvale, NY, Glen Cove, NY and Mississauga, Canada. Our service areas include all of North America as well as some parts of South America and China and Europe.

GENERAL

SECTION INCLUDES

Packaged, cast iron, gas fired hot water commercial and residential boilers.

Packaged, cast iron, gas fired steam commercial and residential boilers.

Packaged, cast iron, oil fired, hot water commercial and residential boilers.

Packaged, cast iron, oil fired, steam commercial and residential boilers.

Packaged cast iron, electric hot water commercial and residential boilers.

Packaged stainless steel water tube high efficiency gas fired hot water boilers

Packaged stainless steel fire tube high efficiency, gas fired hot water boilers.

Knocked-down, cast iron, oil fired, hot water boilers.

RELATED SECTIONS

** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add others as required.

Section 23 05 00 - Common Work Results for HVAC.

Section 26 05 00 - Common Work Results for Electrical.

REFERENCES

** NOTE TO SPECIFIER ** Delete references from the list below that are not actually required by the text of the edited section.

American National Standards Institute (ANSI):

ANSI Z21.13/ CSA 4.9 - Gas-fired low pressure steam and hot water boilers.

American Society of Heating and Refrigeration Engineers. (ASHRAE):

ASHRAE 103 - Method of Testing for Annual Fuel Utilization Efficiency of Residential Central Furnaces and Boilers

American Society of Mechanical Engineers (ASME):

ASME Boiler and Pressure Vessel Code.

CSA Group (CSA):

CSA 4.9 - Gas-Fired Low Pressure Steam and Hot Water Boilers.

CSA B140.7 - Oil-Burning Equipment: General Requirements.

Underwriters Laboratory (UL):

UL834 - Standard for Heating, Water Supply, and Power Boilers - Electric

UL 726 - Standard for Oil-Fired Boiler Assemblies

SUBMITTALS

Submit under provisions of Section 01 30 00 - Administrative Requirements.

Product Data: Manufacturer's data sheets on each product to be used, including:

Preparation instructions and recommendations.

Storage and handling requirements and recommendations.

Installation methods.

Warranty.

Shop Drawings: Include system components, utility requirements and connections, relationship with adjacent construction. Include required clearances and access for servicing.

QUALITY ASSURANCE

Manufacturer Qualifications: Minimum 5 years experience manufacturing similar equipment.

Installer Qualifications: Minimum 2 years experience installing similar equipment.

Standards: Boilers shall meet the requirements of the ASME Boiler and Pressure Vessel Code.

DELIVERY, STORAGE, AND HANDLING

Store products in manufacturer's unopened packaging until ready for installation.

PROJECT CONDITIONS

Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's recommended limits.

WARRANTY

Manufacture's standard residential limited warranty with the following warranty periods:

** NOTE TO SPECIFIER ** Gas: Sentinel, Sentry, Galazy, and Victory

1 year parts warranty.

Limited Lifetime cast-iron sections warranty.

20 year boiler vessel warranty.

Manufacture's standard commercial limited warranty.

PRODUCTS

MANUFACTURERS

Acceptable Manufacturer: Slant/Fin Corp., which is located at: 100 Forest Dr.; Greenvale, NY 11548; Tel: 516-484-2600; Fax: 516-484-5921; Email: request info (marketing@); Web:

** NOTE TO SPECIFIER ** Delete one of the following two paragraphs; coordinate with requirements of Division 1 section on product options and substitutions.

Substitutions: Not permitted.

Requests for substitutions will be considered in accordance with provisions of Section 01 60 00 - Product Requirements.

PERFORMANCE REQUIREMENTS

** NOTE TO SPECIFIER ** Delete performance paragraphs not required.

Gas Fired Boilers:

CSA design approved to ANSI Z21.13/ CSA 4.9.

** NOTE TO SPECIFIER ** Paragraph below refers to boiler models TR, TRVD, EC-10, EC10-DV, and LD.

Oil Fired Boilers:

Design certified to UL 726 and CSA B140.7

Electric Boilers:

Design certified to UL 834 and CSA B140.7

Built to the requirements of Section IV of the ASME Boiler and Pressure Vessel Code.

Cast-Iron Boilers: Built to the requirements of Section IV of the ASME Boiler and Pressure Vessel Code.

Meet or exceed the National Appliance Energy Compliance Act.

AHRI approved ratings.

Boiler ratings with less than 300,000 Btuh input are established under ASHRAE Standard 103 as required by DOE and are verified annually by AHRI under the AHRI DOE Verification Program.

Boiler ratings with 300,000 Btuh input and greater are established by AHRI under AHRI test procedures.

Manufacturer to be holder of an ASME Certificate of Authorization and Code Stamp.

** NOTE TO SPECIFIER ** Delete Article if not required.

PACKAGED CAST IRON, GAS FIRED, HOT WATER COMMERCIAL AND RESIDENTIAL BOILERS

** NOTE TO SPECIFIER ** Delete Paragraph if not required

Basis of Design: Sentry S series and manufactured by Slant/Fin. Natural draft, atmospheric preassembled cast-iron heat exchanger with built in air separator, integral draft diverter, and vent damper.

Model S-34EDP:

Input Rating: 34 MBH (9.96 kW).

DOE Heating Capacity: 29000 BTUh (8.50 kW).

AHRI Net Output Rating: 25 MBH (7.33 kW).

Square Feet Equivalent Direct Radiation: 167 sq ft (15.51 sq m).

Annual Fuel Utilization Efficiency (AFUE): 84 percent.

Nominal Vent Diameter: 4 inch (102 mm).

Model S-60EDP:

Input Rating: 60 MBH (17.58 kW).

DOE Heating Capacity: 51000 BTUh (14.95 kW).

AHRI Net Output Rating: 44 MBH (12.89 kW).

Square Feet Equivalent Direct Radiation: 293 sq ft (27.22 sq m).

Annual Fuel Utilization Efficiency (AFUE): 84.4 percent .

Nominal Vent Diameter: 4 inch (102 mm).

Model S-90EDP:

Input Rating: 90 MBH (26.38 kW).

DOE Heating Capacity: 76000 BTUh (22.27 kW).

AHRI Net Output Rating: 66 MBH (19.34 kW).

Square Feet Equivalent Direct Radiation: 440 sq ft (40.88 sq m).

Annual Fuel Utilization Efficiency (AFUE): 84.2 percent.

Nominal Vent Diameter: 5 in (127 mm).

Model S-120EDP:

Input Rating: 120 MBH (35.17 kW).

DOE Heating Capacity: 101000 BTUh (29.60 kW).

AHRI Net Output Rating: 88 MBH (25.79 kW).

Square Feet Equivalent Direct Radiation: 587 sq ft (54.53 sq m).

Annual Fuel Utilization Efficiency (AFUE): 84.1 percent.

Nominal Vent Diameter: 6 in (152 mm).

Model S-150EDP:

Input Rating: 150 MBH (43.96 kW).

DOE Heating Capacity: 125000 BTUh (36.63 kW).

AHRI Net Output Rating: 109 MBH (31.94 kW).

Square Feet Equivalent Direct Radiation: 727 sq ft (67.54 sq m).

Annual Fuel Utilization Efficiency (AFUE): 83.4 percent.

Nominal Vent Diameter: 7 in (178 mm).

Boiler Characteristics:

** NOTE TO SPECIFIER ** Delete one of the two following subparagraphs.

Fuel type: Natural Gas.

Fuel Type: Propane.

** NOTE TO SPECIFIER ** Delete one of the two following subparagraphs.

Base: Insulated.

Base: Constructed and Insulated for placement on combustible flooring.

Built in draft diverter.

Pre-assembled insulated flush jacket.

Gas Burners: Stainless steel.

Orifices: Brass.

Manifold: Steel.

Redundant combination gas valve including manual shut-off, pressure regulator, pilot adjustment.

Pilot ignition system: Intermittent spark.

Pressure and temperature gauge.

Pressure relief valve (ASME) 30 psi.

2-way combination control (hi-limit and circulator relay).

** NOTE TO SPECIFIER ** Choose one circulator from paragraphs below and delete those not required. Taco 007 is standard. If no circulator is desired, delete all of them.

Circulator: Taco 007, with 1-1/4" flange.

Circulator: Grundfos UPS 15-58F 1-1/4".

Circulator: B & G NRF 22 - 1-1/4".

Circulator: Taco 0010

Circulator: Taco 110 1-1/4"

Circulator: B & G model 100 1-1/4"

Drain cock.

Blocked Vent Safety Switch: Mounted and wired.

Rollout Safety Switch: Mounted and wired.

** NOTE TO SPECIFIER ** Optional. Delete if not required.

Outdoor reset sensor kit.

** NOTE TO SPECIFIER ** Optional. Delete if not required.

Air Package: Diaphragm expansion tank, automatic fill valve and pressure reducing valve, and automatic float air vent.

Control Features:

Thermal targeting technology to conserve fuel.

LWCO function - Auto or manual reset.

Thermal pre-purge option.

LED display for operational info.

Circulator relay - 3 function options.

** NOTE TO SPECIFIER ** Delete Paragraph if not required

Basis of Design: Sentinel SE series and manufactured by Slant/Fin. Natural draft, atmospheric preassembled cast-iron heat exchanger with built in air separator, and vent damper.

Model SE-70EDP:

Input Rating: 70 MBH (20.51 kW).

DOE Heating Capacity: 58000 BTUh (17 kW).

AHRI Net Output Rating: 50 MBH (14.65 kW).

Square Feet Equivalent Direct Radiation: 333 sq ft (30.9 sq m).

Annual Fuel Utilization Efficiency (AFUE): 82.0 percent (

Nominal Vent Diameter: 4 in (102 mm).

Model SE-105EDP:

Input Rating: 105 MBH (30.77 kW).

DOE Heating Capacity: 87000 BTUh (25.50 kW).

AHRI Net Output Rating: 76 MBH (22.27 kW).

Square Feet Equivalent Direct Radiation: 507 sq ft (47.1 sq m).

Annual Fuel Utilization Efficiency (AFUE): 82.1 percent.

Nominal Vent Diameter: 5 in (127 mm).

Model SE-140EDP:

Input Rating: 140 MBH (41.03 kW).

DOE Heating Capacity: 116000 BTUh (34.00 kW).

AHRI Net Output Rating: 101 MBH (29.60 kW).

Square Feet Equivalent Direct Radiation: 673 sq ft (62.5 sq m).

Annual Fuel Utilization Efficiency (AFUE): 82.2 percent.

Nominal Vent Diameter: 5 in (127 mm).

Model S-175EDP:

Input Rating: 175 MBH (51.29 kW).

DOE Heating Capacity: 145000 BTUh (42.49 kW).

AHRI Net Output Rating: 126 MBH (36.93 kW).

Square Feet Equivalent Direct Radiation: 840 sq ft (78 sq m).

Annual Fuel Utilization Efficiency (AFUE): 82.2 percent.

Nominal Vent Diameter: 6 in (152 mm).

Model S-210EDP:

Input Rating: 210 MBH (61.54 kW).

DOE Heating Capacity: 173000 BTUh (50.70 kW).

AHRI Net Output Rating: 150 MBH (43.96 kW).

Square Feet Equivalent Direct Radiation: 1000 sq ft (92.9 sq m)

Annual Fuel Utilization Efficiency (AFUE): 82.3 percent.

Nominal Vent Diameter: 7 in (178 mm).

Boiler Characteristics:

** NOTE TO SPECIFIER ** Delete one of the two following subparagraphs.

Fuel type: Natural Gas.

Fuel Type: Propane.

** NOTE TO SPECIFIER ** Delete one of the two following subparagraphs.

Base: Insulated.

Base: Constructed and Insulated for placement on combustible flooring.

Pre-assembled insulated flush jacket.

External Draft hood.

Gas Burners: Stainless steel.

Orifices: Brass.

Manifold: Steel.

Redundant combination gas valve including manual shut-off, pressure regulator, pilot adjustment.

Pilot ignition system: Intermittent spark.

Pressure and temperature gauge.

Pressure relief valve (ASME) 30 psi.

2-way combination control (hi-limit and circulator relay).

** NOTE TO SPECIFIER ** Choose one circulator from paragraphs below and delete those not required. Taco 007 is standard. If no circulator is desired, delete all of them.

Circulator: Taco 007, with 1-1/4"

Circulator: Grundfos UPS 15-58F 1-1/4".

Circulator: B & G NRF 22 - 1-1/4".

Circulator: Taco 0010.

Circulator: Taco 110 1-1/4".

Circulator: B & G model 100 1-1/4".

Drain cock.

Blocked vent safety switch: Not mounted.

Motorized vent damper.

Rollout safety switch.

** NOTE TO SPECIFIER ** Optional. Delete if not required.

Outdoor reset sensor kit.

** NOTE TO SPECIFIER ** Optional. Delete if not required.

Air Package: Diaphragm expansion tank, automatic fill valve and pressure reducing valve, and automatic float air vent.

Control Features:

Thermal targeting technology to conserve fuel.

LWCO function - Auto or manual reset.

Thermal pre-purge option.

LED display for operational info.

Circulator relay - 3 function options.

** NOTE TO SPECIFIER ** Delete Paragraph if not required

Basis of Design: Galaxy GG series and manufactured by Slant/Fin. Natural draft, atmospheric preassembled cast-iron heat exchanger with built in air separator and vent damper.

Model GG-250HEDP:

Input Rating: 250 MBH (73.27 kW).

DOE Heating Capacity: 209000 BTUh (61.25 kW).

AHRI Net Output Rating: 182 MBH (53.34 kW).

Square Feet Equivalent Direct Radiation: 1211.3 sq ft (112.5 sq m).

Annual Fuel Utilization Efficiency (AFUE): 82.8 percent.

Nominal Vent Diameter: 8 in (203 mm).

Model GG-275HEDP:

Input Rating: 275 MBH (80.59 kW).

DOE Heating Capacity: 228000 BTUh (66.82 kW).

AHRI Net Output Rating: 198 MBH (58.03 kW).

Square Feet Equivalent Direct Radiation: 1322.0 sq ft (122.8 sq m).

Annual Fuel Utilization Efficiency (AFUE): 82.7 percent.

Nominal Vent Diameter: 8 in (203 mm).

Model GG-300HEDP:

Input Rating: 300 MBH (87.92 kW).

Gross Output Rating: 243000 BTUh (71.22 kW).

AHRI Net Output Rating: 211 MBH (61.84 kW).

Square Feet Equivalent Direct Radiation: 1407.0 sq ft (130.7 sq m).

Annual Fuel Utilization Efficiency (AFUE): 81.1 percent.

Nominal Vent Diameter: 8 in (203 mm).

Model GG-350HEDP:

Input Rating: 350 MBH (102.57 kW).

Gross Output Rating: 285000 BTUh (83.52 kW).

AHRI Net Output Rating: 253 MBH (74.15 kW).

Square Feet Equivalent Direct Radiation: 1653 sq ft (153.6 sq m).

Annual Fuel Utilization Efficiency (AFUE): 81.4 percent.

Nominal Vent Diameter: 9 in (229 mm).

Model GG-375HEDP:

Input Rating: 375 MBH (109.90 kW).

Gross Output Rating: 303000 BTUh (88.80 kW).

AHRI Net Output Rating: 263 MBH (77.08 kW).

Square Feet Equivalent Direct Radiation: 1753 sq ft (162.9 sq m).

Annual Fuel Utilization Efficiency (AFUE): 80.9 percent.

Nominal Vent Diameter: 10 in (254 mm).

Model GG-399HEDP:

Input Rating: 399 MBH (116.93 kW).

Gross Output Rating: 322000 BTUh (94.37 kW).

AHRI Net Output Rating: 284 MBH (83.23 kW).

Square Feet Equivalent Direct Radiation: 1867 sq ft (173.5 sq m).

Annual Fuel Utilization Efficiency (AFUE): 80.6 percent.

Nominal Vent Diameter: 10 in (254 mm).

Boiler Characteristics:

** NOTE TO SPECIFIER ** Delete one of the two following subparagraphs.

Fuel type: Natural Gas.

Fuel Type: Propane.

** NOTE TO SPECIFIER ** Delete one of the two following subparagraphs.

Base: Insulated.

Base: Constructed and Insulated for placement on combustible flooring.

Pre-assembled insulated flush jacket.

Flu collector.

Gas Burners: Stainless steel.

Orifices: Brass.

Manifold: Steel.

Redundant combination gas valve including manual shut-off, pressure regulator, pilot adjustment, and 100 percent shutoff.

Pilot ignition system: Intermittent spark.

Pressure, temperature, and altitude gauge.

Pressure relief valve (ASME) 30 psi.

2-way combination control (hi-limit and circulator relay).

Hi-limit control.

Draft hood (field installed).

** NOTE TO SPECIFIER ** Choose one circulator from paragraphs below and delete those not required. Taco 0010 is standard. If no circulator is desired, delete all of them.

Circulator: Taco 0010 for GG-225 thru GG-399 X.

Flange for circulator: 1-1/4";1-1/2" (GG-250 thru GG-399) X.

Circulator manifold.

Circulator: Taco 110 (GG-225 thru GG-399) 39.

Circulator: B&G 100 (GG-225 thru GG-399).

Drain cock.

Blocked vent safety switch: Not mounted.

Motorized vent damper.

Rollout safety switch.

** NOTE TO SPECIFIER ** Optional. Delete if not required.

Outdoor reset sensor kit.

** NOTE TO SPECIFIER ** Optional. Delete if not required.

Air Package: Diaphragm expansion tank, automatic fill valve and pressure reducing valve, and automatic float air vent.

Control Features:

Thermal targeting technology to conserve fuel.

LWCO function - Auto or manual reset.

Thermal pre-purge option.

LED display for operational info.

Circulator relay - 3 function options.

** NOTE TO SPECIFIER ** Delete Paragraph if not required

Basis of Design: Galaxy GXH series and manufactured by Slant/Fin. Natural draft, atmospheric preassembled cast-iron heat exchanger with built in air separator, vent damper, and tankless water heater.

Model GXH-105EDPT:

Input Rating: 150 MBH (43960.7 kW).

DOE Heating Capacity: 87000 BTUh (25.5 kW).

AHRI Net Output Rating: 76 MBH (22273.4 kW).

Square Feet Equivalent Direct Radiation: 500 sq ft (46.4 sq m).

Annual Fuel Utilization Efficiency (AFUE): 82.5 percent.

Nominal Vent Diameter: 5 in (127 mm).

Model GXH-125EDPT:

Input Rating: 126 MBH (36926.9 kW).

DOE Heating Capacity: 104000 BTUh (30.5 kW).

AHRI Net Output Rating: 90 MBH (26376.4 kW).

Square Feet Equivalent Direct Radiation: 600 sq ft (55.7 sq m).

Annual Fuel Utilization Efficiency (AFUE): 82.5 percent.

Nominal Vent Diameter: 6 in (152 mm).

Model GXH-150EDPT:

Input Rating: 147 MBH (43081.4 kW).

DOE Heating Capacity: 122000 BTUh (35.7 kW).

AHRI Net Output Rating: 106 MBH (31065.5 kW).

Square Feet Equivalent Direct Radiation: 706 sq ft (65.6 sq m).

Annual Fuel Utilization Efficiency (AFUE): 82.5 percent.

Nominal Vent Diameter: 7 in (178 mm).

Model GXH-170EDPT:

Input Rating: 168 MBH (49235.9 kW).

DOE Heating Capacity: 140000 BTUh (41 kW).

AHRI Net Output Rating: 122 MBH (35754.7 kW).

Square Feet Equivalent Direct Radiation: 813 sq ft (75.5 sq m).

Annual Fuel Utilization Efficiency (AFUE): 82.5 percent.

Nominal Vent Diameter: 7 in (178 mm).

Model GXH-190EDPT:

Input Rating: 189 MBH (55390.4 kW).

DOE Heating Capacity: 158000 BTUh (46.3 kW).

AHRI Net Output Rating: 137 MBH (40150.7 kW).

Square Feet Equivalent Direct Radiation: 913 sq ft (84.8 sq m).

Annual Fuel Utilization Efficiency (AFUE): 82.5 percent.

Nominal Vent Diameter: 7 in (178 mm).

Boiler Characteristics:

** NOTE TO SPECIFIER ** Delete one of the two following subparagraphs.

Fuel type: Natural Gas.

Fuel Type: Propane.

** NOTE TO SPECIFIER ** Delete one of the two following subparagraphs.

Base: Insulated.

Base: Constructed and Insulated for placement on combustible flooring.

Pre-assembled insulated flush jacket

Flu collector.

Gas Burners: Stainless steel.

Orifices: Brass.

Manifold: Steel.

Redundant combination gas valve including manual shut-off, pressure regulator, pilot adjustment, and 100 percent shutoff.

Pilot ignition system: Intermittent spark.

Pressure, temperature, and altitude gauge

Pressure relief valve (ASME) 30 psi

3-way combination control (hi-limit circulator relay, and lo-limit with differential).

** NOTE TO SPECIFIER ** Choose one circulator from paragraphs below and delete those not required. Taco 007 is standard. If no circulator is desired, delete all of them.

Circulator: Taco 007 (GXH-105 thru GXH-190); X.

Circulator Flange: 1-1/4" (GXH-105 thru GXH-190) X.

Circulator manifold.

Circulator: Grundfos UPS 15-58F 1-1/4".

Circulator: B & G NRF 22 - 1-1/4".

Circulator: Taco 0010.

Circulator: Taco 110 1-1/4".

Circulator: B & G model 100 1-1/4".

Drain cock.

** NOTE TO SPECIFIER ** Tankless heater is optional. Delete if not required.

Tankless heater.

Blocked vent safety switch: Not mounted.

Motorized vent damper.

Rollout safety switch.

** NOTE TO SPECIFIER ** Optional. Delete if not required.

Outdoor reset sensor kit.

** NOTE TO SPECIFIER ** Optional. Delete if not required.

Air Package: Diaphragm expansion tank, automatic fill valve and pressure reducing valve, and automatic float air vent.

Control Features:

Thermal targeting technology to conserve fuel.

LWCO function - Auto or manual reset.

Thermal pre-purge option.

LED display for operational info.

Circulator relay - 3 function options.

** NOTE TO SPECIFIER ** Delete Paragraph if not required

Basis of Design: Victory II VHS series and manufactured by Slant/Fin. Power vent, preassembled cast-iron heat exchanger with built in air eliminator.

Model VHS-30EP

Input Rating: 30 MBH (8.79 kW).

DOE Heating Capacity: 26000 BTUh (7.62 kW).

AHRI Net Output Rating: 23 MBH (6.74 kW).

Square Feet Equivalent Direct Radiation: 150 sq ft ( sq m).

Annual Fuel Utilization Efficiency (AFUE): 84.5 percent.

Pressure Vent Diameter: 3 in (76 mm).

Model VHS-60EP

Input Rating: 60 MBH (17.58 kW).

DOE Heating Capacity: 50000 BTUh (14.65 kW).

AHRI Net Output Rating: 43 MBH (12.60 kW).

Square Feet Equivalent Direct Radiation: 287 sq ft ( sq m).

Annual Fuel Utilization Efficiency (AFUE): 83.4 percent.

Pressure Vent Diameter: 3 in (76 mm).

Model VHS-90EP

Input Rating: 90 MBH (26.38 kW).

DOE Heating Capacity: 75000 BTUh (21.98 kW).

AHRI Net Output Rating: 65 MBH (19.05 kW).

Square Feet Equivalent Direct Radiation: 433 sq ft ( sq m).

Annual Fuel Utilization Efficiency (AFUE): 82.8 percent.

Pressure Vent Diameter: 3 in (76 mm).

Chimney or Type "B" Vent: 5 in (127 mm).

Model VHS-120EP

Input Rating: 120 MBH (35.17 kW).

DOE Heating Capacity: 100000 BTUh (29.31 kW).

AHRI Net Output Rating: 87 MBH (25.50 kW).

Square Feet Equivalent Direct Radiation: 5580 sq ft ( sq m).

Annual Fuel Utilization Efficiency (AFUE): 82.2 percent.

Pressure Vent Diameter: 3 in (76 mm).

Chimney or Type "B" Vent: 5 in (127 mm).

Model VHS-150EP

Input Rating: 150 MBH (43.96 kW).

DOE Heating Capacity: 125000 BTUh (36.63 kW).

AHRI Net Output Rating: 109 MBH (31.94 kW).

Square Feet Equivalent Direct Radiation: 727 sq ft ( sq m).

Annual Fuel Utilization Efficiency (AFUE): 82.1 percent.

Pressure Vent Diameter: 3 in (76 mm).

Chimney or Type "B" Vent: 5 in (127 mm).

Model VHS-180EP

Input Rating: 180 MBH (52.75 kW).

DOE Heating Capacity: 149000 BTUh (43.67 kW).

AHRI Net Output Rating: 130 MBH (38.10 kW).

Square Feet Equivalent Direct Radiation: 867 sq ft ( sq m).

Annual Fuel Utilization Efficiency (AFUE): 82.0 percent.

Pressure Vent Diameter: 3 in (76 mm).

Chimney or Type "B" Vent: 5 in (127 mm).

Boiler Characteristics:

** NOTE TO SPECIFIER ** Delete one of the two following subparagraphs.

Fuel type: Natural Gas.

Fuel Type: Propane.

** NOTE TO SPECIFIER ** Delete one of the two following subparagraphs.

Base: Insulated.

Base: Constructed and Insulated for placement on combustible flooring.

Pre-assembled insulated flush jacket.

Flu collector.

Gas Burners: Stainless steel.

Orifices: Brass.

Manifold: Steel.

Redundant combination gas valve including manual shut-off, pressure regulator, pilot adjustment, and 100 percent shutoff.

Pilot ignition system: Intermittent spark.

Pressure and temperature gauge.

Pressure relief valve (ASME) 30 psi.

Inducer assembly

Airflow proving switch.

Condensate Drain, Trap, and Vent Pipe Adapter: Built-in, stainless steel.

** NOTE TO SPECIFIER ** Choose one circulator from paragraphs below and delete those not required. Taco 007 is standard. If no circulator is desired, delete all of them.

Circulator: Taco 007, 1-1/4 in (32 mm).

Circulator: Grundfos UPS 15-58F, 1-1/4 in (32 mm)

Circulator: B&G NRF 22, 1-1/4 in (32 mm)

Circulator: Taco 110, 1-1/4 in (32 mm).

Circulator: B&G 100, 1-1/4 in (32 mm)

Drain cock.

Rollout safety switch.

** NOTE TO SPECIFIER ** Optional. Delete if not required.

Outdoor reset sensor kit.

** NOTE TO SPECIFIER ** Optional. Delete if not required.

Venting System: 3 in (76 mm) diameter Saf-T EZ Seal venting system

Control Features:

Thermal targeting technology to conserve fuel.

LWCO function - Auto or manual reset.

Thermal pre-purge option.

LED display for operational info.

Circulator relay - 3 function options.

** NOTE TO SPECIFIER ** Delete Paragraph if not required

Basis of Design: Victory VSPH series and manufactured by Slant/Fin. Sealed combustion, direct vent, preassembled cast-iron heat exchanger with built in air eliminator.

PACKAGED, CAST-IRON. GAS-FIRED STEAM COMMERCIAL AND RESIDENTIAL BOILERS

Basis of Design: Galaxy GXH/GXHA series and manufactured by Slant/Fin. Natural draft, atmospheric preassembled cast-iron heat exchanger with built in air separator, vent damper, and tankless water heater.

PACKAGED, CAST-IRON. OIL-FIRED HOT WATER COMMERCIAL AND RESIDENTIAL BOILERS

Basis of Design: Intrepid TR Hot Water series and manufactured by Slant/Fin. Preassembled cast-iron heat exchanger.

Basis of Design: Intrepid TRDV Hot Water series and manufactured by Slant/Fin. Preassembled cast-iron heat exchanger.

Basis of Design: Eutectic EC-10 series and manufactured by Slant/Fin. Preassembled cast-iron heat exchanger.

Basis of Design: XL-2000, XL series and manufactured by Slant/Fin. Preassembled cast-iron heat exchanger.

PACKAGED, CAST-IRON. OIL-FIRED STEAM COMMERCIAL AND RESIDENTIAL BOILERS

Basis of Design: Intrepid TR Steam series and manufactured by Slant/Fin. Preassembled cast-iron heat exchanger.

PACKAGED, CAST-IRON. ELECTRIC HOT WATER COMMERCIAL AND RESIDENTIAL BOILERS

Basis of Design: Monitron EH series and manufactured by Slant/Fin. Preassembled cast-iron heat exchanger.

Basis of Design: Monitron Deluxe EH series and manufactured by Slant/Fin. Preassembled cast-iron heat exchanger.

PACKAGED STAINLESS STEEL WATER TUBE HIGH EFFICIENCY GAS-FIRED HOT WATER BOILERS

Basis of Design: Lynx, LX series and manufactured by Slant/Fin. Aluminum monobloc-iron heat exchanger.

Basis of Design: Lynx, LX Combi (CB) series and manufactured by Slant/Fin. Aluminum monobloc-iron heat exchanger.

Basis of Design: Jaguar, J390 series and manufactured by Slant/Fin. Aluminum monobloc-iron heat exchanger.

PACKAGED STAINLESS STEEL FIRE TUBE HIGH EFFICIENCY GAS-FIRED HOT WATER BOILERS

Basis of Design: Victory VSL series and manufactured by Slant/Fin. Preassembled stainless steel heat exchanger.

Basis of Design: Victory VSL II series and manufactured by Slant/Fin. Preassembled titanium, stainless steel heat exchanger.

Basis of Design: CHS, CHS series and manufactured by Slant/Fin. Preassembled stainless steel heat exchanger.

Basis of Design: CHS, CHS Multiple series and manufactured by Slant/Fin. Preassembled stainless steel heat exchanger.

KNOCKED-DOWN, CAST IRON, OIL FIRED, HOT WATER BOILERS

Basis of Design: Intrepid TR KD series and manufactured by Slant/Fin. Cast-iron heat exchanger.

Basis of Design: Eutectic EC-20 series and manufactured by Slant/Fin. Cast-iron heat exchanger.

EXECUTION

EXAMINATION

Do not begin installation until substrates have been properly prepared.

If substrate preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding.

PREPARATION

Clean surfaces thoroughly prior to installation.

Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions.

INSTALLATION

Install in accordance with manufacturer's instructions. Test for proper operation.

PROTECTION

Protect installed products until completion of project.

Touch-up, repair or replace damaged products before Substantial Completion.

END OF SECTION ................
................