Xylem Inc.



Gen 2 MultiSmart / RTU

RELEASE NOTE

Version: 3.3.7

|Copyright © MultiTrode Pty Ltd. This document contains information which is proprietary and |Status |ISSUED |

|confidential to MultiTrode Pty Ltd and is not to be communicated to any other company or person,| | |

|in whole or in part, by any process whatsoever, without the express permission of MultiTrode Pty| | |

|Ltd. | | |

| |File Name |002396 |

|Revision |Date |Release |Author |Authorised |

|21 |16/03/17 | |SCV | |

| | | | | |

Version 3.3.7

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

This release has many additional instructions. Please refer to the MultiSmart 3.3.7 Supplementary Release notes for more information. Here are basic instructions to upgrade to 3.3.7.

1 USB / SD Card Upgrade

1. Copy the multismart.img file obtained from the Xylem TPI website or from MultiTrode customer support onto a USB stick or SD card.

2. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

3. In order to upgrade the DSP, go to:

Settings->Software Modules->Upgrade DSP and press 'Upgrade'.

The DSP should start its upgrade process. When the DSP Upgrade is complete, please go to:

Info->I/O->System

and check that the version number of the DSP is 03.02.0rel0.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.3.7 |J:\Release Prod\D0037-MultiSmart_RTU\Software\V3.3.7 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|bootload_io_sciprog_slots1-8.gup |3.02.0 |J:\Release Prod\D0037-MultiSmart_RTU\Software\DSP V3.3.7 |

|bootload/bootload_gup2000.hex | | |

|bootload/bootload.out | | |

|bootload/bootload_host.hex | | |

|io/io_gup2000.hex | | |

|io/io.out | | |

|io/io_host.hex | | |

|setup-burnrtu.exe |3.3.7 |J:\Release |

| | |Prod\D0037-MultiSmart_RTU\Software\V3.3.7\burnrtu-26 |

5 Advice for Production Department

Any units in stock should be upgraded with the full upgrade. This will mean that Setup Wizard needs to be run again.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

7 New Features & Enhancements

|# |Subject |

| | |

|11619 |Blocking stations with Aquacom MRC telegram |

8 Issues Addressed

|# |Subject |

|12079 |Unused Reports Calculation Type and Extra Help |

|12009 |Isagraf Resource Crashes with Backwards Time Shift |

|11977 |Review DNP Slave Profile |

|11970 |MultiSmart rejects config if volumes at two levels are the same |

|11964 |Aquacom WGE response is missing start byte |

|11961 |Analog Watcher Integral Values Overflowing |

|11950 |DataFlash IC has been marked as end-of-life |

|11947 |Bulk Configuration Version Not Saved When Log Files Deleted |

|11945 |Power and Energy Calculations for 3PC |

|11837 |Faults log in trend viewer showing wrong date (epoch date) |

|11828 |Daylight Savings Stats Issue |

|11817 |Modbus Master can issue multiple simulaneous requests |

|11733 |Revision to Concertor DP Points List |

|11464 |Some tags are not copied to active profile |

|10812 |Pump 1 IRT fault is randomly activated |

| | |

Version 3.3.6

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

This release has many additional instructions. Please refer to the MultiSmart 3.3.6 Supplementary Release notes for more information. Here are basic instructions to upgrade to 3.3.6.

1 USB / SD Card Upgrade

4. Copy the multismart.img file obtained from the Xylem TPI website or from MultiTrode customer support onto a USB stick or SD card.

5. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

6. In order to upgrade the DSP, go to:

Settings->Software Modules->Upgrade DSP and press 'Upgrade'.

The DSP should start its upgrade process. When the DSP Upgrade is complete, please go to:

Info->I/O->System

and check that the version number of the DSP is 03.02.0rel0.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.3.6 |J:\Release Prod\D0037-MultiSmart_RTU\Software\V3.3.6 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|bootload_io_sciprog_slots1-8.gup |3.02.0 |J:\Release Prod\D0037-MultiSmart_RTU\Software\DSP V3.3.6 |

|bootload/bootload_gup2000.hex | | |

|bootload/bootload.out | | |

|bootload/bootload_host.hex | | |

|io/io_gup2000.hex | | |

|io/io.out | | |

|io/io_host.hex | | |

|setup-burnrtu.exe |3.3.6 |J:\Release |

| | |Prod\D0037-MultiSmart_RTU\Software\V3.3.6\burnrtu-26 |

5 Advice for Production Department

Any units in stock should be upgraded with the full upgrade. This will mean that Setup Wizard needs to be run again.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

7 New Features & Enhancements

|# |Subject |

| | |

|10831 |Aquacom as a master |

|11104 |Support for FGC400 Modbus Connection |

|11116 |Support for Concertor Modbus Connection |

|11196 |Split the Aquacom MCC telegram in chunks |

|11221 |Translate some HMI Security page words |

|11388 |CalcStats update default trend values |

|11602 |Decimals on values |

8 Issues Addressed

|# |Subject |

| | |

|10514 |Aquacom Crash on WGH Request |

|11094 |AquaCom Trends and Midnight Rollover |

|11107 |Wrong tag in a default HMI layout value |

|11165 |Deletion of AquaCom Trends |

|11172 |SMS reading issues for acknowledgement |

|11232 |Trends scale factor after upgrade |

|11390 |Aquacom export CSV and then Import bug |

|11418 |MultiSmart Unit Keeps Rebooting |

|11424 |Generating Aquaview template. Setpoint Strings should be channel type C, not T. |

|11434 |Cannot save Act / Deact setpoint for pump 4-6 in the HMI. |

|11451 |Analog Watcher Integral Accuracy |

|11511 |Unmanaged Log Files |

| | |

Version 3.3.5

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

This release has many additional instructions. Please refer to the MultiSmart 3.3.5 Supplementary Release notes for more information. Here are basic instructions to upgrade to 3.3.5.

1 USB / SD Card Upgrade

7. Copy the multismart.img file obtained from the Xylem TPI website or from MultiTrode customer support onto a USB stick or SD card.

8. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

9. In order to upgrade the DSP, go to:

Settings->Software Modules->Upgrade DSP and press 'Upgrade'.

The DSP should start its upgrade process. When the DSP Upgrade is complete, please go to:

Info->I/O->System

and check that the version number of the DSP is 03.02.0rel0.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.3.5 |J:\Release Prod\D0037-MultiSmart_RTU\Software\V3.3.5 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|bootload_io_sciprog_slots1-8.gup |3.02.0 |J:\Release Prod\D0037-MultiSmart_RTU\Software\DSP V3.3.5 |

|bootload/bootload_gup2000.hex | | |

|bootload/bootload.out | | |

|bootload/bootload_host.hex | | |

|io/io_gup2000.hex | | |

|io/io.out | | |

|io/io_host.hex | | |

|setup-burnrtu.exe |3.3.5 |J:\Release |

| | |Prod\D0037-MultiSmart_RTU\Software\V3.3.5\burnrtu-26 |

5 Advice for Production Department

Any units in stock should be upgraded with the full upgrade. This will mean that Setup Wizard needs to be run again.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

7 New Features & Enhancements

|# |Subject |

| | |

|10930 |Changing Sensor Range Shouldn't Affect Start/Stop Levels |

|10892 |Updated Chinese Translations |

| | |

8 Issues Addressed

|# |Subject |

| | |

|11061 |AquaCom Setpoints with Menu Options |

|11054 |Scaling of ADAM Analog Inputs |

|11045 |Bad values in CalcStats for Aquacom |

|10937 |Invalid Flow Volumes |

|10838 |Failed Configuration Leaves EEPROM Locked |

|10836 |Web Server Fails for RTU Only |

| |

Version 3.3.4

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

This release has many additional instructions. Please refer to the MultiSmart 3.3.4 Supplementary Release notes for more information. Here are basic instructions to upgrade to 3.3.4.

1 USB / SD Card Upgrade

10. Copy the multismart.img file obtained from the Xylem TPI website or from MultiTrode customer support onto a USB stick or SD card.

11. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

12. In order to upgrade the DSP, go to:

Settings->Software Modules->Upgrade DSP and press 'Upgrade'.

The DSP should start its upgrade process. When the DSP Upgrade is complete, please go to:

Info->I/O->System

and check that the version number of the DSP is 03.02.0rel0.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.3.4 |J:\Release Prod\D0037-MultiSmart_RTU\Software\V3.3.4 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|bootload_io_sciprog_slots1-8.gup |3.02.0 |J:\Release Prod\D0037-MultiSmart_RTU\Software\DSP V3.3.4 |

|bootload/bootload_gup2000.hex | | |

|bootload/bootload.out | | |

|bootload/bootload_host.hex | | |

|io/io_gup2000.hex | | |

|io/io.out | | |

|io/io_host.hex | | |

|setup-burnrtu.exe |3.3.4 |J:\Release |

| | |Prod\D0037-MultiSmart_RTU\Software\V3.3.4\burnrtu-26 |

5 Advice for Production Department

Any units in stock should be upgraded with the full upgrade. This will mean that Setup Wizard needs to be run again.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

7 New Features & Enhancements

|# |Subject |

| | |

|10719 |Send SMS with SMS server in PDU mode to support any characters |

|10707 |AquaCom Alarm Delay |

|10494 |Make Analogue limit - State runtime save total runtime |

8 Issues Addressed

|# | |

|Subject | |

| | |

|10714 | |

|Modbus slave coil write always writes values regardless of WriteValue setting | |

| | |

|10702 | |

|Analog Watcher Fails if No Pumps Configured | |

| | |

|10596 | |

|Web Server Not Starting | |

| | |

|10463 | |

|Backup Probe is automatically added with remote level selection | |

| | |

|10459 | |

|Configuration B for Pump Station Remote Level Does not create a DNP Master in setup wizard | |

| | |

|10795 | |

|ResetPeriod tag missing for Interval Logs | |

| | |

Version 3.3.3

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

This release has many additional instructions. Please refer to the MultiSmart 3.3.3 Supplementary Release notes for more information. Here are basic instructions to upgrade to 3.3.3.

1 USB / SD Card Upgrade

13. Copy the multismart.img file obtained from the Xylem TPI website or from MultiTrode customer support onto a USB stick or SD card.

14. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

15. In order to upgrade the DSP, go to:

Settings->Software Modules->Upgrade DSP and press 'Upgrade'.

The DSP should start its upgrade process. When the DSP Upgrade is complete, please go to:

Info->I/O->System

and check that the version number of the DSP is 03.02.0rel0.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.3.3 |J:\Release Prod\D0037-MultiSmart_RTU\Software\V3.3.3 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|bootload_io_sciprog_slots1-8.gup |3.02.0 |J:\Release Prod\D0037-MultiSmart_RTU\Software\DSP V3.3.3 |

|bootload/bootload_gup2000.hex | | |

|bootload/bootload.out | | |

|bootload/bootload_host.hex | | |

|io/io_gup2000.hex | | |

|io/io.out | | |

|io/io_host.hex | | |

|setup-burnrtu.exe |3.3.3 |J:\Release |

| | |Prod\D0037-MultiSmart_RTU\Software\V3.3.3\burnrtu-26 |

5 Advice for Production Department

Any units in stock should be upgraded with the full upgrade. This will mean that Setup Wizard needs to be run again.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

7 New Features & Enhancements

|# |Subject |

|10441 |MultiSmart - ASCII Code Interpretation |

|10409 |AT Commands to Modems |

|10391 |Visualization of reversing in HMI |

|10365 |Modbus connection to MAS711 |

|10362 |Modbus Master Double Points Polling |

|10356 |Ability to Disable DHCP Server |

|10093 |Modbus Master Signed Registers |

| | |

8 Issues Addressed

|# |Subject |

|10331 |Pump faults when high level float is active |

|10322 |Fixes for WITS Self-Certification |

|10360 |DNP Slave Unsol Confirm Timeout |

|10380 |Increase Max Number of Log Generations |

|10403 |AquaCom setpoints (MCC) not working with empty string |

|10395 |Web pages not working on Safari |

|10466 |Invalid set point for IRT |

|10449 |ISaGRAF Resource Recovery |

| | |

Version 3.3.2

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

This release has many additional instructions. Please refer to the MultiSmart 3.3.2 Supplementary Release notes for more information. Here are basic instructions to upgrade to 3.3.2.

1 USB / SD Card Upgrade

16. Copy the multismart.img file obtained from the Xylem TPI website or from MultiTrode customer support onto a USB stick or SD card.

17. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

18. In order to upgrade the DSP, go to:

Settings->Software Modules->Upgrade DSP and press 'Upgrade'.

The DSP should start its upgrade process. When the DSP Upgrade is complete, please go to:

Info->I/O->System

and check that the version number of the DSP is 03.02.0rel0.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.3.2 |J:\Release Prod\D0037-MultiSmart_RTU\Software\V3.3.2 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|bootload_io_sciprog_slots1-8.gup |3.02.0 |J:\Release Prod\D0037-MultiSmart_RTU\Software\DSP V3.3.2 |

|bootload/bootload_gup2000.hex | | |

|bootload/bootload.out | | |

|bootload/bootload_host.hex | | |

|io/io_gup2000.hex | | |

|io/io.out | | |

|io/io_host.hex | | |

|setup-burnrtu.exe |3.3.2 |J:\Release |

| | |Prod\D0037-MultiSmart_RTU\Software\V3.3.2\burnrtu-26 |

5 Advice for Production Department

Any units in stock should be upgraded with the full upgrade. This will mean that Setup Wizard needs to be run again.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

7 New Features & Enhancements

No new features in this release.

8 Issues Addressed

|# |Subject |

|10312 |Remove unused fields from the HMITool Compilation Models dialog |

|10310 |Populate the list of used Template Databases in the HMITool Project Settings dialog |

|10306 |Remove HMITool Refresh Button |

|10301 |Invalid Site Code after reboot the MultiSmart Unit |

|10296 |3.3.1 Station Op Values Misleading |

|10292 |3.3.1 Wizard fails Probe Backup |

|10287 |Clicking on Flygt Logo on HMI Causes Scroll Bars to Appear |

|10285 |Upgrades prior to 3.2.0 cause configuration failure |

|10283 |SMS Server handling Simultaneous Alarms |

| | |

Version 3.3.1

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

This release has many additional instructions. Please refer to the MultiSmart 3.3.1 Supplementary Release notes for more information. Here are basic instructions to upgrade to 3.3.1.

1 USB / SD Card Upgrade

19. Copy the multismart.img file obtained from the Xylem TPI website or from MultiTrode customer support onto a USB stick or SD card.

20. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

21. In order to upgrade the DSP, go to:

Settings->Software Modules->Upgrade DSP and press 'Upgrade'.

The DSP should start its upgrade process. When the DSP Upgrade is complete, please go to:

Info->I/O->System

and check that the version number of the DSP is 03.02.0rel0.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.3.1 |J:\Release Prod\D0037-MultiSmart_RTU\Software\V3.3.1 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|bootload_io_sciprog_slots1-8.gup |3.02.0 |J:\Release Prod\D0037-MultiSmart_RTU\Software\DSP V3.3.1 |

|bootload/bootload_gup2000.hex | | |

|bootload/bootload.out | | |

|bootload/bootload_host.hex | | |

|io/io_gup2000.hex | | |

|io/io.out | | |

|io/io_host.hex | | |

|setup-burnrtu.exe |3.3.1 |J:\Release |

| | |Prod\D0037-MultiSmart_RTU\Software\V3.3.1\burnrtu-26 |

5 Advice for Production Department

Any units in stock should be upgraded with the full upgrade. This will mean that Setup Wizard needs to be run again.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

7 New Features & Enhancements

No new features in this release.

8 Issues Addressed

|# |Subject |

|10221 |Cannot Edit CT Primary Value From Motor Protection Screen of LCD |

|10230 |Supply voltage selection Setup wizard HMI |

|10238 |Dictionary Translations December 2014 |

|10247 |Faults with Auto-Ack Not Displaying on HMI |

|10255 |Chinese Translations Missing in Setup Wizard |

|10257 |Selecting Spanish and Aquacom from Setup Wizard creates failed config |

|10259 |WebApp language translator doesn't support Chinese |

|10263 |Aquacom Slave is Added on Upgrade |

|10267 |Multiple Alarms not being Reported by SMS |

|10276 |Duplicate Entries in HMI Tool |

|10278 |Pump Name Not Translated for Fault Descriptions |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

Version 3.3.0

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

This is a major release that has many additional instructions. Please refer to the MultiSmart 3.3.0 Supplementary Release notes for more information. Here are basic instructions to upgrade to 3.3.0.

1 USB / SD Card Upgrade

22. Copy the multismart.img file obtained from the Xylem TPI website or from MultiTrode customer support onto a USB stick or SD card.

23. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

24. In order to upgrade the DSP, go to:

Settings->Software Modules->Upgrade DSP and press 'Upgrade'.

The DSP should start its upgrade process. When the DSP Upgrade is complete, please go to:

Info->I/O->System

and check that the version number of the DSP is 03.02.0rel0.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.3.0 |J:\Release Prod\D0037-MultiSmart_RTU\Software\V3.3.0 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|bootload_io_sciprog_slots1-8.gup |3.02.0 |J:\Release Prod\D0037-MultiSmart_RTU\Software\DSP V3.3.0 |

|bootload/bootload_gup2000.hex | | |

|bootload/bootload.out | | |

|bootload/bootload_host.hex | | |

|io/io_gup2000.hex | | |

|io/io.out | | |

|io/io_host.hex | | |

|setup-burnrtu.exe |3.3.0 |J:\Release |

| | |Prod\D0037-MultiSmart_RTU\Software\V3.2.6\burnrtu-26 |

5 Advice for Production Department

Any units in stock should be upgraded with the full upgrade. This will mean that Setup Wizard needs to be run again.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

7 New Features & Enhancements

|# |Subject |

|9785 |Support for multiple ADAM-6050 I/O expansion units - numbered nodes |

|9807 |Download Log Files and download/upload configs in Gen2 Web Interface |

|9858 |HMI Tool for Customizing Web Pages |

|9862 |DHCP Server |

|9870 |Setup Wizard via Web Interface |

|10006 |Auto-detection of URL for HMI |

|10030 |Backup Level Sensors in Setup Wizard |

|10091 |Modbus Master Polling Groups |

|10099 |Custom Tags that Obey Schemas |

|10113 |Priority of Modbus Commands |

|10129 |Modbus Master Priority Polling |

|10162 |Web page enhancements |

8 Issues Addressed

|# |Subject |

|9799 |New Events in Datalogger Show Enabled = True but after re-entering Screen they show up False |

|9822 |Info --> Network doesn't show second IP Address |

|10087 |Without Configurator Site Key, Configurator Says "Send Successful" But Fails |

|10210 |IP subnet mask is being reset to 0.0.0.0 on every reboot |

|10219 |PPP Manager locks up serial 1 |

|10232 |VFD Control for Independent Wells |

Version 3.2.6

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

Here are instructions to upgrade to 3.2.6.

1 USB / SD Card Upgrade

25. Copy the multismart.img file obtained from the Multitrode website or from MultiTrode customer support onto a USB stick or SD card.

26. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

27. In order to upgrade the DSP, go to:

Settings->Software Modules->Upgrade DSP and press 'Upgrade'.

The DSP should start its upgrade process. When the DSP Upgrade is complete, please go to:

Info->I/O->System

and check that the version number of the DSP is 03.02.0rel0.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.2.6 |J:\Release Prod\D0037-MultiSmart_RTU\Software\V3.2.6 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|bootload_io_sciprog_slots1-8.gup |3.02.0 |J:\Release Prod\D0037-MultiSmart_RTU\Software\DSP V3.2.6 |

|bootload/bootload_gup2000.hex | | |

|bootload/bootload.out | | |

|bootload/bootload_host.hex | | |

|io/io_gup2000.hex | | |

|io/io.out | | |

|io/io_host.hex | | |

|setup-burnrtu.exe |3.2.6 |J:\Release |

| | |Prod\D0037-MultiSmart_RTU\Software\V3.2.6\burnrtu-26 |

5 Advice for Production Department

Production does not need to upgrade any units in stock. If an upgrade does occur, the Host Processor Board Firmware only needs to be upgraded.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

7 New Features & Enhancements

|# |Subject |

|10141 |Intellimax modem support in MultiSmart |

| | |

8 Issues Addressed

|# |Subject |

|10146 |Motor protection module fails on initialisation if no MP board is used |

|10144 |Updates to Spanish Translations |

|10137 |Digital Output Sources all need Verification |

| | |

Version 3.2.5

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

Here are instructions to upgrade to 3.2.5.

1 USB / SD Card Upgrade

28. Copy the multismart.img file obtained from the Multitrode website or from MultiTrode customer support onto a USB stick or SD card.

29. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

30. In order to upgrade the DSP, go to:

Settings->Software Modules->Upgrade DSP and press 'Upgrade'.

The DSP should start its upgrade process. When the DSP Upgrade is complete, please go to:

Info->I/O->System

and check that the version number of the DSP is 03.02.0rel0.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.2.5 |J:\Release Prod\D0037-MultiSmart_RTU\Software\V3.2.5 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|bootload_io_sciprog_slots1-8.gup |3.02.0 |J:\Release Prod\D0037-MultiSmart_RTU\Software\DSP V3.2.5 |

|bootload/bootload_gup2000.hex | | |

|bootload/bootload.out | | |

|bootload/bootload_host.hex | | |

|io/io_gup2000.hex | | |

|io/io.out | | |

|io/io_host.hex | | |

|setup-burnrtu.exe |3.2.5 |J:\Release |

| | |Prod\D0037-MultiSmart_RTU\Software\V3.2.5\burnrtu-26 |

5 Advice for Production Department

Production does not need to upgrade any units in stock. If an upgrade does occur, the Host Processor Board Firmware only needs to be upgraded.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

7 New Features & Enhancements

No new features in this release.

8 Issues Addressed

|# |Subject |

|10117 |Generator total runtime |

|10119 |Triggering Float Switch High Level Starts All Pumps Immediately |

|10121 |Upgrading 3PC Configurations to 3.2.4 Causes Configuration Failure |

|10123 |Pump Statistics Wrong for Maintenance Run |

| | |

Version 3.2.4

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

Here are instructions to upgrade to 3.2.4.

1 USB / SD Card Upgrade

31. Copy the multismart.img file obtained from the Multitrode website or from MultiTrode customer support onto a USB stick or SD card.

32. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

33. In order to upgrade the DSP, go to:

Settings->Software Modules->Upgrade DSP and press 'Upgrade'.

The DSP should start its upgrade process. When the DSP Upgrade is complete, please go to:

Info->I/O->System

and check that the version number of the DSP is 03.02.0rel0.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.2.4 |J:\Release Prod\D0037-MultiSmart_RTU\Software\V3.2.4 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|bootload_io_sciprog_slots1-8.gup |3.02.0 |J:\Release Prod\D0037-MultiSmart_RTU\Software\DSP V3.2.4 |

|bootload/bootload_gup2000.hex | | |

|bootload/bootload.out | | |

|bootload/bootload_host.hex | | |

|io/io_gup2000.hex | | |

|io/io.out | | |

|io/io_host.hex | | |

|setup-burnrtu.exe |3.2.4 |J:\Release |

| | |Prod\D0037-MultiSmart_RTU\Software\V3.2.4\burnrtu-26 |

5 Advice for Production Department

Production does not need to upgrade any units in stock. If an upgrade does occur, the Host Processor Board Firmware only needs to be upgraded.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

7 New Features & Enhancements

|# |Subject |

|10101 |Renaming Generator |

|10103 |Single Phase Current Monitoring Via Analog Inputs |

|10105 |Exercising Per Pump |

8 Issues Addressed

No issues addressed in this release.

Version 3.2.3

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

Here are instructions to upgrade to 3.2.3.

1 USB / SD Card Upgrade

34. Copy the multismart.img file obtained from the Multitrode website or from MultiTrode customer support onto a USB stick or SD card.

35. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

36. In order to upgrade the DSP, go to:

Settings->Software Modules->Upgrade DSP and press 'Upgrade'.

The DSP should start its upgrade process. When the DSP Upgrade is complete, please go to:

Info->I/O->System

and check that the version number of the DSP is 03.02.0rel0.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.2.3 |J:\Release Prod\D0037-MultiSmart_RTU\Software\V3.2.3 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|bootload_io_sciprog_slots1-8.gup |3.02.0 |J:\Release Prod\D0037-MultiSmart_RTU\Software\DSP V3.2.3 |

|bootload/bootload_gup2000.hex | | |

|bootload/bootload.out | | |

|bootload/bootload_host.hex | | |

|io/io_gup2000.hex | | |

|io/io.out | | |

|io/io_host.hex | | |

|setup-burnrtu.exe |3.2.3 |J:\Release |

| | |Prod\D0037-MultiSmart_RTU\Software\V3.2.3\burnrtu-26 |

5 Advice for Production Department

Production does not need to upgrade any units in stock. If an upgrade does occur, the Host Processor Board Firmware only needs to be upgraded.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

7 New Features & Enhancements

|# |Subject |

|10043 |Comparison of configured number of pumps to enable code |

|10073 |Setup Wizard Prompt for DNP3, Modbus, or AquaCom |

|10065 |Add Tester for 3G Internal Modem |

8 Issues Addressed

|# |Subject |

|10034 |DOUT Source of Pump x Unavailable registers as No Pumps Running |

|10051 |Integrate Triangle Library 3.16.02 code |

|10079 |Security Flaw in OpenSSL |

|10053 |Unable to Configure High Level Alarm DOUT |

|10061 |DNP3 Integral deadband functionality update |

|10067 |Improve Template generation for AquaView 7 |

|10077 |Assigning Pump Reversing to a Digital Output via Configurator |

Version 3.2.2

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

Here are instructions to upgrade to 3.2.2.

1 USB / SD Card Upgrade

37. Copy the multismart.img file obtained from the Multitrode website or from MultiTrode customer support onto a USB stick or SD card.

38. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

39. In order to upgrade the DSP, go to:

Settings->Software Modules->Upgrade DSP and press 'Upgrade'.

The DSP should start its upgrade process. When the DSP Upgrade is complete, please go to:

Info->I/O->System

and check that the version number of the DSP is 03.02.0rel0.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.2.2 |J:\Release Prod\D0037-MultiSmart_RTU\Software\V3.2.2 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|bootload_io_sciprog_slots1-8.gup |3.02.0 |J:\Release Prod\D0037-MultiSmart_RTU\Software\DSP V3.2.2 |

|bootload/bootload_gup2000.hex | | |

|bootload/bootload.out | | |

|bootload/bootload_host.hex | | |

|io/io_gup2000.hex | | |

|io/io.out | | |

|io/io_host.hex | | |

|setup-burnrtu.exe |3.2.2 |J:\Release |

| | |Prod\D0037-MultiSmart_RTU\Software\V3.2.2\burnrtu-26 |

5 Advice for Production Department

Production does not need to upgrade any units in stock. If an upgrade does occur, the Host Processor Board Firmware only needs to be upgraded.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

7 New Features & Enhancements

|# |Subject |

| | |

|10021 |Support for Priority 2 Languages |

8 Issues Addressed

|# |Subject |

| | |

|10039 |Analog Sensor OverRangeSetPoint incorrectly calculated |

|10059 |76800 Baud option should be 57600 |

|10063 |AquaCom remote control bug |

Version 3.2.1

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

Here are instructions to upgrade to 3.2.1.

1 USB / SD Card Upgrade

40. Copy the multismart.img file obtained from the Multitrode website or from MultiTrode customer support onto a USB stick or SD card.

41. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

42. This release involves an update to the DSP code. In order to upgrade the DSP, go to:

Settings->Software Modules->Upgrade DSP and press 'Upgrade'.

The DSP should start its upgrade process. When the DSP Upgrade is complete, please go to:

Info->I/O->System

and check that the version number of the DSP is 03.02.0rel0.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.2.1 |J:\Release Prod\D0037-MultiSmart_RTU\Software\V3.2.1 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|bootload_io_sciprog_slots1-8.gup |3.02.0 |J:\Release Prod\D0037-MultiSmart_RTU\Software\DSP V3.2.1 |

|bootload/bootload_gup2000.hex | | |

|bootload/bootload.out | | |

|bootload/bootload_host.hex | | |

|io/io_gup2000.hex | | |

|io/io.out | | |

|io/io_host.hex | | |

|setup-burnrtu.exe |3.2.1 |J:\Release |

| | |Prod\D0037-MultiSmart_RTU\Software\V3.2.1\burnrtu-26 |

5 Advice for Production Department

Production does not need to upgrade any units in stock. If an upgrade does occur, the Host Processor Board Firmware only needs to be upgraded.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

7 New Features & Enhancements

|# |Subject |

| | |

|9920 |DNP3 file transfer of the isagraf file |

|9946 |WITS Point Overrides |

|9948 |Enhancements to Enable Code Web Utility |

|9978 |Better Support for Analog Level Sensors |

8 Issues Addressed

|# |Subject |

| | |

|9824 |Minimum for Well Washer activation start point is too high |

|9826 |Use right-arrow to expand branch of advanced menu |

|9830 |Fault context list box doesn't scroll - can't see context 9+ |

|9855 |Isagraf info screen displays the wrong compile date |

|9879 |PumpView password is no longer secure |

|9885 |2 Well Configuration - Request to Run |

|9887 |2 Well Config - Fail Safe Mechanism |

|9890 |Pump Alternation help screen |

|9925 |Flowmeter per pump assigns the inputs to the wrong pump when pumps are renamed - orders names alphabetically but assignments|

| |by pump number |

|9964 |AquaCom MCC with more than 255 setpoints |

|9966 |AquaCom WGS answer |

|9970 |Update WITS Default Connection Detail Record |

|9980 |Current Pump Flow Rates |

|9984 |Updates to language translations |

|9988 |AquaCom MCC response SCE |

|9995 |DNP Slave Buffer size limited to 1000 in triangle stack (TMWCNFG_MAX_EVENTS) |

|10000 |Security Config Causes Crash |

|10017 |AquaCom trend failure |

|10028 |Invalid Default Modbus Master |

Version 3.2.0

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

Here are instructions to upgrade to 3.2.0.

1 USB / SD Card Upgrade

43. Copy the multismart.img file obtained from the Multitrode website or from MultiTrode customer support onto a USB stick or SD card.

44. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

45. This release involves an update to the DSP code. In order to upgrade the DSP, go to:

Settings->Software Modules->Upgrade DSP and press 'Upgrade'.

The DSP should start its upgrade process. When the DSP Upgrade is complete, please go to:

Info->I/O->System

and check that the version number of the DSP is 03.02.0rel0.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.2.0 |J:\Release Prod\D0037-MultiSmart_RTU\Software\V3.2.0 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|bootload_io_sciprog_slots1-8.gup |3.02.0 |J:\Release Prod\D0037-MultiSmart_RTU\Software\DSP V3.2.0 |

|bootload/bootload_gup2000.hex | | |

|bootload/bootload.out | | |

|bootload/bootload_host.hex | | |

|io/io_gup2000.hex | | |

|io/io.out | | |

|io/io_host.hex | | |

|setup-burnrtu.exe |3.2.0 |J:\Release |

| | |Prod\D0037-MultiSmart_RTU\Software\V3.2.0\burnrtu-26 |

5 Advice for Production Department

Production does not need to upgrade any units in stock. If an upgrade does occur, the Host Processor Board Firmware only needs to be upgraded.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

7 New Features & Enhancements

|# |Subject |

|8524 |Self-learning of nominal efficiency |

|9510 |Calculate Efficiency When a Pump is Run Externally |

|9787 |Integrate APP800 HMI with MultiSmart |

|9797 |LCD Language Translation |

|9801 |Aquacom Driver |

|9866 |Enable Code as a Hosted Application |

| | |

8 Issues Addressed

|# |Subject |

|8401 |MODBUS TCPIP--- Multiple masters stats wont be shown in info screen, cannot use lower range ports as well |

|9212 |Info screen Modbus slave values |

|9252 |Cannot assign Pump General Faults to DINs via LCD |

|9254 |When using metered flow and a probe, the flow reading will not always show on the home screen |

|9359 |2 Well 6MP DuoProbe bug |

|9395 |Res Mon (2.4.5 firmware) does not show level device config |

|9411 |Message log flooded when viewing Info --> IO --> Bottom Board --> IRT |

|9471 |Missing tags for Faults for Bottomboard AIN |

|9536 |Snapshot -> Log Interval stays in HHH:MM:SS format when Interval Type is Months |

|9546 |Change Info --> "ISaGRAF 5" button to just "ISaGRAF", now that we are using ISaGRAF 6 |

|9610 |Can not define a min and max value for an attribute integer tag |

|9616 |Problem with multiple DNP3 slaves configured and doing an upgrade. |

|9815 |Entering Motor Protection without MP Enabled can cause Lockup |

|9868 |RS485 channel can miss reception of messages |

|9872 |MultiSmart NHPB RS232 baud rate issues |

|9875 |DNP Unsolicited Responses with Authentication Failures |

|9913 |Crisis Logs not being saved |

|9927 |LCD Crashes when changing probe sensitivity |

|9930 |Unresponsive IO on Unit 2 |

|9933 |DSP Upgrade for Gen2 |

| | |

Version 3.1.1

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

Here are instructions to upgrade to 3.1.1.

1 USB / SD Card Upgrade

46. Copy the multismart.img file obtained from the Multitrode website or from MultiTrode customer support onto a USB stick or SD card.

47. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.1.1 |R:\D0037-MultiSmart_RTU\Software\V3.1.1 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|enablecode-setup.exe |3.1.1 |R:\D0037-MultiSmart_RTU\Software\V3.1.1\enablecode |

|setup-burnrtu.exe |3.1.1 |R:\D0037-MultiSmart_RTU\Software\V3.1.1\burnrtu-26 |

5 Advice for Production Department

Production does not need to upgrade any units in stock. If an upgrade does occur, the Host Processor Board Firmware and the bootloader (u-boot) need to be upgraded.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

The lists of tickets defined below include all tickets from release 2.5.1 (Gen1 HPB), as well as tickets specifically for the 3.1.1 release.

7 New Features & Enhancements

No new features in this release.

8 Issues Addressed

|# |Subject |

|9793 |Multiple Modbus Packets Sent Together |

|9805 |MultiSmart config fails when a pump is added to a new group. |

|9813 |Restoring Configurations via CF card |

|9820 |Disabled Event Logs Cause Log File Corruptions |

| | |

Version 3.1.0

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

Here are instructions to upgrade to 3.1.0.

1 USB / SD Card Upgrade

48. Copy the multismart.img file obtained from the Multitrode website or from MultiTrode customer support onto a USB stick or SD card.

49. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.1.0 |R:\D0037-MultiSmart_RTU\Software\V3.1.0 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|enablecode-setup.exe |3.1.0 |R:\D0037-MultiSmart_RTU\Software\V3.1.0\enablecode |

|setup-burnrtu.exe |3.1.0 |R:\D0037-MultiSmart_RTU\Software\V3.1.0\burnrtu-26 |

5 Advice for Production Department

Production does not need to upgrade any units in stock. If an upgrade does occur, the Host Processor Board Firmware and the bootloader (u-boot) need to be upgraded.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

The lists of tickets defined below include all tickets from release 2.5.0 (Gen1 HPB), as well as tickets specifically for the 3.1.0 release.

7 New Features & Enhancements

|# | |

|Subject | |

| | |

|9795 | |

|Generation of over-range events | |

| | |

|9755 | |

|Faster access to web pages | |

| | |

|9709 | |

|WITS Analogue Units | |

| | |

|9697 | |

|Support both versions of Burnrtu on the same PC | |

| | |

|9690 | |

|Support for on-board modem | |

| | |

|9688 | |

|WITS Connection Details and Callback Data Sets | |

| | |

|9684 | |

|Analog Watcher average only when run/enable tag is active | |

| | |

|9655 | |

|WITS Profiles and Profile Control Values | |

| | |

|9644 | |

|Web Page Security | |

| | |

|9628 | |

|Information screens especially IP and MAC. | |

| | |

|9568 | |

|Indicate on Info --> ISaGRAF when ISaGRAF is not licenced by enable code | |

| | |

|9566 | |

|Support for DNP Security V5 | |

| | |

|9473 | |

|Flow.VolumeLastMonth missing | |

| | |

|9100 | |

|Include reversing statistics under Info --> Pump Info --> Starts | |

| | |

|9096 | |

|Show time until reset for deactivating faults in Faults page | |

| | |

|9094 | |

|On faults screen, put most recent alarm at top of page | |

| | |

|9049 | |

|In Digital Output source list, change "Pump x Running" to "Pump x Call to Run" | |

| | |

|8940 | |

|Show Energy use on info screen with 1 decimal precision | |

| | |

|8920 | |

|Power Factor and Low Efficiency Fault settings in 2 places - Motor Protection and Faults | |

| | |

|8908 | |

|IRT Interval | |

| | |

|8896 | |

|Enable code change during setup wizard | |

| | |

|8892 | |

|Level Sim Active tag, include in default event log | |

| | |

|8808 | |

|Pump Reset Button input | |

| | |

|8806 | |

|Pump Not In Auto standard fault | |

| | |

|8712 | |

|Pump Cleanout by looking at the current drawn | |

| | |

|8686 | |

|Create directory for all log file backups | |

| | |

|8548 | |

|Need to find out an easy way for configuring DNP control outputs from the master in MultiSmart RTU | |

| | |

|8544 | |

|SMS Server in MultiSmart RTU | |

| | |

|8519 | |

|First Time Power Up Timestamp | |

| | |

|8515 | |

|Configurable Temperature Alarms | |

| | |

|8481 | |

|Bootstrap keypress to force firmware upgrade before config load | |

| | |

|8339 | |

|Delay Fail Fault should trigger any time a pump is running, not just when pump is starting | |

| | |

|8307 | |

|Data Logger to Capture Power Factor Deadbands | |

| | |

|7913 | |

|Manual Reset Required Tag per fault / fault group - only true after auto-resets have expired | |

| | |

|7910 | |

|Check Enable Code and Warn when restoring config | |

| | |

|7902 | |

|Concurrent Runtime logging | |

| | |

|7780 | |

|Record failed login attempts in History | |

| | |

|7774 | |

|Profiles to be able to Holdout specific pumps | |

| | |

|7674 | |

|Show IRT Voltage and Test Interval on IRT Fault page | |

| | |

|7548 | |

|Setup Wizard Redesign - Cover all our features | |

| | |

|7497 | |

|Pump Efficiency Calcs for VFD Pumps | |

| | |

|7294 | |

|Auto set volumes from depth of well / probe model | |

| | |

|7038 | |

|Ability to interface an Inflow Meter to MultiSmart | |

| | |

|6746 | |

|Default fault log for Low Level Alarm | |

| | |

|5531 | |

|Additional Text (Ticket 2872) | |

| | |

|5252 | |

|Max Pumps Run Bug - Pumps Stop & Restart Under Certain Conditions | |

| | |

|5101 | |

|Levels of Security | |

| | |

| | |

| | | | | | | |

8 Issues Addressed

|# |Subject |

|9783 |Upgrade Problems |

|9779 |Lockup if MP Config is changed but not Saved |

|9761 |Upgrades causing duplicate calcstat entries |

|9659 |WITS Data Sets Being Sent in Integrity Poll |

|9657 |DNP Read File Should Not Request Confirmation |

|9653 |ISaGRAF WriteFloat fb for analog tags |

|9576 |Manual should state CAN ID must be 1, 2 or 3 |

|9540 |Message log flooded when web browser showing main screen 304rc3 |

|9491 |Modbus points list CSV export adds "Object" column heading |

|9479 |New Point Limit scaling of limit and hysteresis tags |

|9045 |Volume entry screen rounds up and shows error "Sensor 1 level must be less than or equal to the depth of the well" |

|9035 |2.4.0 Intermittent High Alarm Present & Muted |

|9012 |Well depth able to be changed in two different locations |

|9007 |Remove decimal places from resistance reading in Info --> I/O --> Digital Inputs |

|8995 |Invalid character in user PIN |

|8993 |Duplicate iButton users |

|8987 |LCD Heartbeat is using default value of 60 |

|8979 |Setpoints not saved when profile switched |

|8973 |ACS800 Missing tags from snapshot |

|8957 |Differing date formats for the one region |

|8944 |Manual and LCD help - show warning that modbus values may roll over if scaling is incorrect |

|8912 |Missing Ain faults when bottom board is a 3PC card |

|8906 |Change Edit to Configure |

|8886 |Units indication required on new Profile Config screen |

|8884 |N to M Alternation Ratio - Must Press Save First |

|8872 |Analog Watcher for RTU and ResMon |

|8870 |Clarify Well Clean Out Level Adjustment help |

|8857 |DNP Slave Message Queue when inactive |

|8843 |N to M Alternation Ratio edit screen should show pump labels |

|8839 |Config backup - "Yes" confirmation button not displayed (under a special case) |

|8798 |Unit Restarts when Restart Later option selected after clearing modbus master slave points list |

|8784 |Digital Output info screens should show mode |

|8775 |no restriction on having multiple points which has the same DNP3 point number |

|8680 |Second Save Prompt for Benchmark Efficiency Appearing |

Version 3.0.7

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

Here are instructions to upgrade to 3.0.7.

1 USB / SD Card Upgrade

50. Copy the multismart.img file obtained from the Multitrode website or from MultiTrode customer support onto a USB stick or SD card.

51. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.0.7 |R:\D0037-MultiSmart_RTU\Software\V3.0.7 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|enablecode-setup.exe |3.0.7 |R:\D0037-MultiSmart_RTU\Software\V3.0.7\enablecode |

|setup-burnrtu.exe |3.0.7 |R:\D0037-MultiSmart_RTU\Software\V3.0.7\burnrtu-26 |

5 Advice for Production Department

Production does not need to upgrade any units in stock. If an upgrade does occur, the Host Processor Board Firmware and the bootloader (u-boot) need to be upgraded.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

The lists of tickets defined below include all tickets from release 2.4.11 (Gen1 HPB), as well as tickets specifically for the 3.0.7 release.

7 New Features & Enhancements

|# | |

|Subject | |

| | |

|9638 | |

|Pump start to start delay | |

| | |

|9748 | |

|Generate null unsolicited message when buffers nearly full | |

| | |

| | |

| | |

| | |

| | |

| | | | | | | |

8 Issues Addressed

|# | |

|Subject | |

| | |

|9017 | |

|VFD Pump Settings screen update | |

| | |

|9682 | |

|Fault module and statistics | |

| | |

|9715 | |

|Profile activation by DIN | |

| | |

|9721 | |

|Top Sensor Count Increases and Fail Safe Errors | |

| | |

|9729 | |

|DNP3 crisis logging | |

| | |

|9731 | |

|Max Run Time settings | |

| | |

|9753 | |

|Modbus master multiple slaves | |

| | |

|9759 | |

|Disabled modbus master slave | |

| | |

|9765 | |

|New modbus writemode tag | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

Version 3.0.6

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

Here are instructions to upgrade to 3.0.6.

1 USB / SD Card Upgrade

52. Copy the multismart.img file obtained from the Multitrode website or from MultiTrode customer support onto a USB stick or SD card.

53. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.0.6 |R:\D0037-MultiSmart_RTU\Software\V3.0.6 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|enablecode-setup.exe |3.0.6 |R:\D0037-MultiSmart_RTU\Software\V3.0.6\enablecode |

|setup-burnrtu.exe |3.0.6 |R:\D0037-MultiSmart_RTU\Software\V3.0.6\burnrtu-26 |

5 Advice for Production Department

Production does not need to upgrade any units in stock. If an upgrade does occur, the Host Processor Board Firmware and the bootloader (u-boot) need to be upgraded.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

The lists of tickets defined below include all tickets from release 2.4.10 (Gen1 HPB), as well as tickets specifically for the 3.0.6 release.

7 New Features & Enhancements

|# | |

|Subject | |

| | |

| | |

|8355 | |

|Write Multiple Holding Registers | |

| | |

| | |

|9622 | |

|Maximum pumps to run | |

| | |

| | |

|9626 | |

|Well Washer | |

| | |

| | |

|9632 | |

|Isagraf variables screen | |

| | |

| | |

|9634 | |

|Digital input and output config screens | |

|  | |

| | |

|9661 | |

|Modbus Master Sleep Period | |

|  | |

| | |

|9663 | |

|Hide LCD Invert Button | |

|  | |

| | |

|9665 | |

|Max ON time and Max Runtime enhancements | |

|  | |

| | |

| | |

| | |

| | |

| | |

| | |

8 Issues Addressed

|# | |

|Subject | |

| | |

|9676 | |

|Changing Deadbands via DNP Settings not Working | |

| | |

| | |

| | |

| | |

|9678 | |

|Set Point config issue if DuoProbe level device is used | |

| | |

|9694 | |

|Semi manual mode for fill setup | |

| | |

|9674 | |

|Configuration Conversion from HPB1 to HPB2 not copying all Telemetry parameters | |

| | |

|9686 | |

|ISaGRAF Advanced Function Blocks | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

| | |

Version 3.0.5

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

Here are instructions to upgrade to 3.0.5.

1 USB / SD Card Upgrade

54. Copy the multismart.img file obtained from the Multitrode website or from MultiTrode customer support onto a USB stick or SD card.

55. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.0.5 |R:\D0037-MultiSmart_RTU\Software\V3.0.5 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|enablecode-setup.exe |3.0.5 |R:\D0037-MultiSmart_RTU\Software\V3.0.5\enablecode |

|setup-burnrtu.exe |3.0.5 |R:\D0037-MultiSmart_RTU\Software\V3.0.5\burnrtu-26 |

5 Advice for Production Department

Production does not need to upgrade any units in stock. If an upgrade does occur, the Host Processor Board Firmware and the bootloader (u-boot) need to be upgraded.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

The lists of tickets defined below include all tickets from release 2.4.9 (Gen1 HPB), as well as tickets specifically for the 3.0.5 release.

7 New Features & Enhancements

|# |Subject |

|9587 |Conversion of HPB Gen1 configuration files to Gen2 |

| | |

8 Issues Addressed

|# |Subject |

|8559 |LCD Dim after Power Up |

|9477 |LCD makes noise on startup with new HPB |

|9525 |Enable log file when redundancy slave channel is active will trigger application failure and keep rebooting |

| |the MultiSmart |

|9552 |Config fails to load if directory has spaces in name |

| | |

|9596 |Modification of Generated CSV File Tags from Unit_1/Unit_2 to MotorProt |

|9600 |Corrupt USB Images |

|9604 |Gen2 Bottom row of buttons missing on backup screen |

|9651 |Setting Date/Time on Gen 2 HPB |

|9602 |LCD crash if General Digital Input button is pressed when all DINs are assigned to faults |

|9614 |PV3 AT&T Sony Ericsson Chat is Incorrect _ Ref: Ticket # 9483 |

Version 3.0.4

1 System Requirements

A MultiSmart RTU Generation 2, 256MB Version.

2 Advice for Existing Users

Only upgrade to this version of firmware if you have a problem with the issues listed in section 1.8 or needing to take advantage of new features listed in section 1.7.

3 Upgrade Details

Here are instructions to upgrade to 3.0.4.

1 USB / SD Card Upgrade

56. Copy the multismart.img file obtained from the Multitrode website or from MultiTrode customer support onto a USB stick or SD card.

57. Insert the USB stick / SD card in your unit and reboot/power off. You will be prompted as to whether you want to proceed with the upgrade, which you will need to confirm. The progress of the upgrade can be viewed via the progress bar at the bottom of the screen.

4 Release Contents

|Item |Version |Location |

|burnrtu.properties |3.0.4 |R:\D0037-MultiSmart_RTU\Software\V3.0.4 |

|config.jffs2 | | |

|initrd.img | | |

|root.cramfs | | |

|u-boot.img | | |

|uImage.img | | |

|update.img | | |

|update-full.img | | |

|HPB2_Prod_V01.jed | | |

|MultiSmart2.txt | | |

|enablecode-setup.exe |3.0.4 |R:\D0037-MultiSmart_RTU\Software\V3.0.4\enablecode |

|setup-burnrtu.exe |3.0.4 |R:\D0037-MultiSmart_RTU\Software\V3.0.4\burnrtu-26 |

5 Advice for Production Department

Production does not need to upgrade any units in stock. If an upgrade does occur, the Host Processor Board Firmware and the bootloader (u-boot) need to be upgraded.

6 Advice for Customer Support Staff

Customers that are affected by the issues listed in Section 1.8 should upgrade their units.

The lists of tickets defined below include all tickets from release 2.4.8 (Gen1 HPB), as well as tickets specifically for the 3.0.4 release.

7 New Features & Enhancements

|# |Subject |

|9585 |Modify Default DNP3 Session Settings When Activating Selecting PumpView |

|9570 |Testing of New PumpView Parameters |

|9533 |Add /etc/ppp/peers directory by default |

|9529 |Maintenance Mode / Alarm Masking |

|9522 |Display Version on Info/Isagraf page |

|9498 |Pump Alternation Special Mode Definition |

|9489 |Message log flooded for RTU only configuration, when LCD is showing the home screen |

|9483 |New PumpView Parameters |

|9467 |New Isagraf function for executing a command line instruction |

|9455 |Add Commit Setpoint to dbviewer command-line options |

|9449 |Ability to delay DNP3 during device startup |

|9401 |Increase Start and Stop Delays |

|9399 |Change default datalog for motor currents/power/energy from IO.unit._1.BottomBoard.IIN._1.AmpsA to |

| |MotorProt.Pump._1.IIN.AmpsA |

|9387 |Profile SP updates should update active SP, if the profile is the currently selected one |

|9355 |WITS Enhancements for Thames TEP1 |

|9337 |MultiWell Setpoints need to be configured separately |

|9302 |Ability to switch channels for DNP Slave |

|9150 |TON and TOFF ISaGRAF function blocks |

|8698 |Invert Colors for SunSmart Display |

|9564 |Upgrade ISaGRAF runtime to 5.30 |

|9379 |Info Web Pages |

| | |

8 Issues Addressed

|# |Subject |

|9592 |Calcstats FreezeOffset isn't working properly |

|9572 |Analog Watcher Uses GMT, not Local Time |

|9562 |PSTN After Idle Timeout |

|9558 |Standby Starts (blocked pump detection) trips on first standby start if Contactor Aux configured |

|9531 |PSTN Reconnection Attempts |

|9527 |PPP2 Manager Max Delay |

|9520 |Interval logs not returned in WITS log from older generations |

|9516 |The Snapshot sleep period of 5 seconds leads to inaccurate interval logs |

|9514 |DNP Slave Should Ignore Disabled Analog Limits |

|9512 |Snapshot fails to notify itself of changed index |

|9504 |Current Level (Scaled) value not present in event log |

|9500 |2.4.8 RC3 PPPM2 Application Failure |

|9463 |Adding Modbus Master to RTU-only |

|9453 |Upgraded config with 2 DNP3 slaves, 2 Wells |

|9451 |Pump Group Alternation |

|9445 |Restore config with Isagraf |

|9435 |Intermittent High Level with Fail Safe |

|9391 |Upper Case (/Capslock) button doesn't work in setup wizard |

|9496 |3.0.3 Backup of Log Files Missing |

|9554 |HPB 2: Unable to copy logic engine scripts from USB to MultiSmart |

|9447 |New HPB DIES if DSP Upgrade Initiated. |

|9481 |Deleting routing table entries from Configurator |

|9574 |HPB 2: Unable to export information to SD card |

|9589 |Routing not working on new HPB |

|9485 |Monthly tags in the calcstat |

|9548 |V303 Backup options describe CF card as target |

Troubleshooting & Support Contact

By Phone:

Ph: (07) 3340 7000 (Australia)

Fx: (07) 3340 7077 (Australia)

By Email:

support@.au

By Web:

.au

By Mail:

18 Brandl Street

PO Box 4633

Eight Mile Plains QLD 4113

................
................

In order to avoid copyright disputes, this page is only a partial summary.