A reset schedule is used: ECDWT setpoint equals the outside air wet bulb temperature plus 7 degrees F, but not lower than 65 degrees F, nor higher than 83 degrees F. The CT will try and maintain the ECDWT setpoint temperature by first modulating the normally open bypass valve, with no water going over the top of the tower. When the valve is in full bypass AND the ECDWT is greater than the ... ................
................