SECTION 15855

5-25 TON DX AIR HANDLING UNITS WITH HOT GAS REHEAT

1 GENERAL

01 Section Includes

A. Packaged air handling units.

B. Refrigeration components

02 RELATED SECTIONS

A. Section 15170 - Motors

B. Section 15242 - Vibration Isolation.

C. Section 15290 - Ductwork Insulation.

D. Section 15890 - Ductwork.

E. Section 15910 - Ductwork Accessories: Flexible duct connections.

F. Section 15952 - Controls and Instrumentation

G. Section 16180- Equipment wiring systems.

03 REFERENCES

A. ANSI/ASHRAE 15 - Safety Code for Mechanical Refrigeration.

B. ANSI/ASHRAE/IES 90 A - Energy Conservation in New Building Design Standard.

C. AHRI 210/240 - Unitary Air-Conditioning Equipment and Air-Source Heat Pump Equipment, (less than 135,000 Btuh).

D. AHRI 360 - Commercial and Industrial Unitary Air Conditioning Equipment testing and rating standard, (equipment greater than 135,000 Btuh).

E. AHRI 340 - Commercial and Industrial Unitary Heat pump Equipment, (heat pumps above 135,000 Btuh).

F. ANSI Z21.47/UL1995 - Unitary Air Conditioning Standard for safety requirements.

04 QUALITY ASSURANCE

A. Air Handling Units: Product of manufacturer regularly engaged in production of components who issues complete catalog data on total product.

05 SUBMITTALS

A. Submit unit performance data including: capacity, nominal and operating performance.

B. Submit Mechanical Specifications for unit and accessories describing construction, components and options.

C. Submit shop drawings indicating overall dimensions as well as installation, operation and service clearances. Indicate lift points and recommendations and center of gravity. Indicate unit shipping, installation and operating weights including dimensions.

D. Submit data on electrical requirements and connection points. Include recommeded wire and fuse sizes or MCA, sequence of operation, safety and start-up instructions.

06 DELIVERY, STORAGE, AND HANDLING

A. Comply with manufacturer's installation instructions for rigging, unloading, and transporting units.

B. Store in clean dry place and protect from weather and construction traffic. Handle carefully to avoid damage to components, enclosures, and finish.

07 ENVIRONMENTAL REQUIREMENTS

A. Do not operate units for any purpose, temporary or permanent, until ductwork is clean, filters are in place, bearings lubricated, and fan has been test run under observation.

08 WARRANTY

A. Provide one year parts warranty.

1 PRODUCTS

09 SUMMARY

A. The contractor shall furnish and install air handling units(s) as shown as scheduled on the contract documents. The unit(s) shall be installed in accordance with this specification and perform at the specified conditions as scheduled.

B. APPROVED MANUFACTURERS

1. Trane Odyssey Morganizer:

2. Aaon:

3. Addison:

10 GENERAL

A. Provide indoor-mounted, draw-thru, packaged air handling unit(s). Unit(s) shall be factory-assembled including direct-expansion evaporator and reheat coil, modulating face and bypass dampers, Belimo actuator, expansion valve(s), check valves, condensate drain pan, centrifugal fan assembly with fan motor(s) and mounting bracket sheaves, drives and belts, filters, and DDC controls. Units shall be suitable for either horizontal or vertical airflow configuration and be used with or without ductwork.

11 CASING

A. Unit casing shall be constructed of zinc-coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized and finished with a baked enamel finish. Casing shall meet ASTM B117, 672 hour Salt Spray Test.

B. Unit casing shall be completely insulated with fire-retardant, permanent, foil-faced, ½” 1 pound glass fiber material.

12 FANS

A. Provide fan section with forward curved, double width, double inlet, centrifugal type fan belt driven type.

B. Provide self-aligning, grease lubricated, ball or roller bearings with permanent lubrication fittings.

C. Factory mount motor on slide rails. Provide access to motor, drive, and bearings through removable casing panels.

D. Provide shafts constructed of solid hot rolled steel, ground and polished, with key-way, and protectively coated with lubricating oil.

E. Provide cast iron or steel variable and adjustable pitched sheaves, dynamically balanced, bored to fit shafts and keyed.

13 EVAPORATOR AND REHEAT COILS

A. Provide configured aluminum fin surface mechanically bonded to copper tubing coil. Enclose coils with headers and return bends fully contained within casing. Coil shall have factory installed expansion valves and factory pressure tested at 660 psig.

B. Provide double sloped condensate drain pan constructed of PVC with external connections on either side of unit under the evaporator coil. The drain pan shall be removable for cleaning.

14 FILTERS

A. Provide one or two inch throwaway filters, factory installed. Provide access from side panel for removal. Filter rack shall be field convertible to two inch capability with field provided two inch throwaway filters.

15 CONTROLS

A. Provide microprocessor unit mounted control (UCM) which when used with an electronic discharge air sensor mounted on the DX coil provides proportional, integral, and derivative supply air control. This UCM shall perform all unit functions by making all heating, cooling and ventilating decisions through resident software logic. The microprocessor shall include several temperature functions. A discharge air sensor mounted after the evaporator coil shall maintain the specified dehumidification temperature. The second temperature sensor shall modulate the hot gas reheat coil face and by pass damper to maintain the specified supply or space air temperature. The third temperature sensor shall monitor suction temperature and lockout compressors to keep the evaporator coil from freezing. The fourth temperature sensor shall monitor liquid line temperature to modulate condenser fans to maintain head pressure. The fifth sensor is a space adjustable temperature or humidity input. The last temperature sensor monitors outdoor air temperature and makes the decision on when to lock out the compressors. All functions of the microprocessor shall be fully programmable. The UCM shall be LONtalk or BACnet compatible.

1 EXECUTION

16 INSTALLATION

A. Install in accordance with manufacturer's instructions.

-----------------------