Obs-



301 Industrial Boulevard

Tullahoma, TN 37388

Phone: 931.454.9940 ~ Fax: 931.454.2338

Dollar Tree MEP Site Observation Report

|Mall Name: Gulf Harbor Plz |Date: 23DEC14 |

|Address: 4758 – 4770 US Hwy 19 |Deal #: 8739 |

|City, State: New Port Richey, FL |ORA File: 617114 |

General Summary:

Space is LLB with new HVAC by DTS per SLM. Space has adequate HVAC capacity with the 8 units existing but has old equipment for the most part. Several units are horizontal discharge above the roof and with changing should be changed to conventional downflow units. Space needs about 32 tons with the west storefront, space has insulation on top of grid. Space shows signs of roof leaks also. Ductwork is ductboard and food service comprised the larger space and needs replacing, probably better to replace it all. Space has power, water, sewer, and sprinkler. Space has no basement, no mezzanine, no wood construction was noted. Grease waste will need to be avoided for sewer service.

The (2) 200A 208Y120V services in spaces 4760 and 4762 could possibly be used for the DTS fit-out if there is no freezer/cooler package, If there is a f/c package, then a 600A service may be required. The distribution wireway is directly behind the DTS space.

LOI Summary:

Not Available VB LLB AS-IS Expansion

HVAC By: DTS LL

Utility Separation DTS LL LL Stub-In Only

General Info:

Storefront Direction: North South East West

Power Still On: Yes No

Insul. Top of Grid: Yes No

Roof Height 13’-1 Fixed Ladder Required: Yes No

Sprinkler Main Height 10’-3

Permanent Fixed Ladder Location N/A

Roof Insulation Thickness UTD

Does the building have a Basement Yes No Partial

Does the building have a Mezzanine Yes No

Is there Wood Construction Yes No Partial

Mechanical:

HVAC Equipment Information:

Unit |Mfgr |Model |Serial # |Size |Age |SASD |RASD |Comments | |1 |ICP |PA5560 |L99323841 |5 |15 | | | | |2 |ICP |PA5560 |G050511130 |5 |9 | | | | |3 |UTD |UTD |UTD |5? | | | | | |1a |Trane |TSC060 |632102745L |5 |8 | | | | |2a |Trane |TSC060 |636103164L |5 |8 | | | | |3a |Trane |TSC060 |638100930L |5 |8 | | | | |4a |Carrier |TFF008 |1904G30303 |7.5 |10 | | | | |8 |Trane |SA00B856 |C85F067L8 |7 |24 | | | | |Total area: 10500 sqft @ 45? tons EXISTING= 233 sqft/ton Existing

Estimated Requirement: @ 325 sf/ton – 32.3 tons Estimated As Referenced by LOI

How much of the ductwork can be reused? Majority Half None

If Ductwork Re-used, existing Diffusers Need Replacing Clean/Paint/Reuse Likely

The ductwork is constructed of: Sheet Metal Fiber Ductboard.

Insulation: Lined Wrapped

Ductwork Clearance Issues: Yes None Noted       Inches Clear above 12’ Ceiling/Below Struct.

Water & Sewer:

Utility Company No Info On Meter

Phone #:

Meter #

Water Meter /service location: Rear: Left Center Right Outside DTS Space:       FT Left Right

Front: Left Center Right

Side: Left Right Front Center Rear

Water Into Space Yes No Location: Rear: Left Center Right

Size:

Sewer Location: Rear: Left Center Right Outside DTS Space:       FT Left Right

Front: Left Center Right

Side: Left Right Front Center Rear

Manhole Location: Rear: Left Center Right       FT

Front: Left Center Right       FT

Side: Left Right Front Center Rear

Toilet room location: Rear: Left Center Right Outside DTS Space:       FT Left Right

Front: Left Center Right

Side: Left Right Front Center Rear

Gas:

Utility Company LP Tanks

Phone #:

Meter #

Gas meter/service location: Rear: Left Center Right Outside DTS Space:       FT Left Right

Front: Left Center Right

Side: Left Right Front Center Rear

Gas Piping Routed: Above Ceiling On Roof

Fire Sprinkler:

Sprinkler riser location: Rear: Left Center Right Outside DTS Space:       FT Left Right

Front: Left Center Right

Side: Left Right Front Center Rear

Sprinkler Co. Tag Missing – No Info

Phone #:

Gauge Pressure 90 PSI

Electrical:

Utility Company Progress Energy Florida

Phone #:

Meter # 470-119-184-533 / 4768-139-82-613 / 4764-119-184-532 / 4760-119-184-534 /

4758-119-185-047 / (House) 4776-119-185-049

Electrical Service: Single Service Multiple Services / 6 Services

Overhead Underground

Can Multiple Meters be Used Yes No Unknown

Served by Multiple Transformers Yes No Unknown

Electrical Service Voltage: 277/480V/3ph 120/208V/3ph 120/208/1ph       Other?

208/120 XFMR /       kVA Inside DTS Space

Riser Diagram Attached

The (2) 200A 208Y120V services in spaces 4760 and 4762 could possibly be used for the DTS fit-out if there is no freezer/cooler package, If there is a f/c package, then a 600A service may be required. The distribution wireway is directly behind the DTS space.

Service amperage size: (2) * 200A + (4) * 100A Amps Clarify if Multiple

Estimated Required Service: 400 Amps WITHOUT C/F Package

Estimated Required Service: 600 Amps WITH C/F Package

New Service Needed/Estimated

Electrical meter location: Rear: Left Center Right Outside DTS Space:       FT Left Right

Front: Left Center Right

Side: Left Right Front Center Rear

Inside LL Meter Room LL Meter Room Part of DTS Space

Service Disc.t location: Rear: Left Center Right Outside DTS Space:       FT Left Right

Front: Left Center Right

Side: Left Right Front Center Rear

Inside LL Meter Room LL Meter Room Part of DTS Space

Panel location: Rear: Left Center Right Outside DTS Space:       FT Left Right

Front: Left Center Right

Side: Left Right Front Center Rear

Inside LL Meter Room LL Meter Room Part of DTS Space

Panel Type: MLO Main Circuit Breaker Both

Panelboards: Re-usable Need Replacing (Mostly)

Wiring: Pipe & Wire MC Cable

Romex Other:

Lighting: T-8 T-12

Ballast Verification: N/A

Sales - Lamps per Fixture      

Incandescent Other:

Fire Alarm:

Control Panel: Rear: Left Center Right Outside DTS Space:       FT Left Right

Front: Left Center Right

Side: Left Right Front Center Rear

The fire alarm was only in spaces 4760 and 4762.

................
................