MOTOR HP & AMPS ELECTRICAL WIRE, FUSE & BREAKER SIZES
ENGINEERING DATA SHEET
DATE
SUPERSEDES
C1-2-2-345
January 2000
CE103
MOTOR HP & AMPS
ELECTRICAL WIRE, FUSE & BREAKER SIZES
The following table gives wire, breaker and fuse sizes based on horsepower, voltage and phase. Motor full load amps are
taken from motors currently used by Champion. The wire, breaker and fuse sizes are provided as a reference for the installer
and are based on the 1996 National Electrical Code. All wiring should be performed by a licensed electrician or electrical
contractor and must meet all applicable codes for the area where installed.
Motor
HP
Voltage
Typical
Motor F.L.A.
?
?
?
?
1
1
1?
1?
2
2
3
3
5
7?
115V
208V / 230V
115V
208V/ 230V
115V
208V / 230V
115V
208V / 230V
115V
208V / 230V
115V
208V / 230V
208V / 230V
208V / 230V
8.4
4.4 / 4.2
11
5.5 / 5.4
12.4
6.5 / 6.2
18
9.5 / 9
24
12.6 / 12
32
16.8 / 16
25.5 / 24
33 / 31
Copper Conductor
75¡ã C Rating ¨C
30¡ã C Ambient
Wire Size Awg No.
Dual Element, Time Delay
UL Class RK5 Fuse
(Used with Properly Sized
O/L Relay)
Circuit Breaker
(Instantaneous Trip
Circuit Breaker)
Continuous Amp Rating
SINGLE PHASE UNITS
14
14
12
14
12
14
10
14
10
14
8
10
8
6
15A
8A / 7A
15A
12A / 10A
20A
12A / 10A
20A
15A / 10A
35A
20A
50A
30A / 25A
40A
50A
15A
7A
15A
15A
15A
15A
30A
15A
30A
15A
50A
30A
50A / 30A
50A
8A
4A
12A / 10A
5A
12A
7A
25A
12A
40A / 35A
15A
50A / 45A
20A
75A / 60A
30A
100A / 90A
45A
125A / 110A
50A
150A / 125A
60A
7A
3A
15A
7A
15A
7A
30A
15A
30A
15A
50A
30A
100A / 50A
30A
100A
50A
100A
50A
150A / 100A
50A
THREE PHASE UNITS
1?
1?
2
2
3
3
5
5
7?
7?
10
10
15
15
20
20
25
25
30
30
1.
2.
200V / 230V
460V
200V / 230V
460V
200V / 230V
460V
200V / 230V
460V
200V / 230V
460V
200V / 230V
460V
200V / 230V
460V
200V / 230V
460V
200V / 230V
460V
200V / 230V
460V
5 / 4.8
2.4
6.8 / 6.4
3.2
8.5 / 8
4
14.8 / 14
7
23 / 22
11
30 / 28
14
44.8 / 39
19.5
61 / 53
26.5
74 / 65
32.5
87 / 76
38
14
14
14
14
14
14
10 / 12
14
8 / 10
14
8
12
6
10
4
8
3/4
8
2/3
6
To ensure proper coordination between the heater element and short circuit protective device, consult the heater table
packaged with the motor controller.
Maximum branch-circuit, short-circuit protective device ratings shown in the manufacturer¡¯s overload relay table for use
with a motor controller, or otherwise marked on the equipment, shall not be exceeded.
Copyright ? 2000 Gardner Denver, Inc.
EDS C1-2-2-345 P1/1
................
................
In order to avoid copyright disputes, this page is only a partial summary.
To fulfill the demand for quickly locating and searching documents.
It is intelligent file search solution for home and business.
Related download
- engineering info masterdrive inc
- 4 0 engine power ratings
- motor protection tables littelfuse
- diesel engine power to fuel consumption table
- how to calculate required horsepower for circular saws
- motor hp amps electrical wire fuse breaker sizes
- pesticides calculations for homeowners
- update of engine categories emission rates and speciation
Related searches
- direct burial electrical wire chart
- hp to amps chart
- hp to amps converter
- motor hp sizes chart
- breaker sizes chart
- wire size for 40 amps 240 volts
- electrical breaker sizes list
- 30 amp breaker wire size
- nec circuit breaker sizes table
- wire size for 50 amps 240v
- 40 amp breaker wire size
- electrical wire size chart