INSTRUCTIONS TO TENDERERS



ANNEX II + III : TECHNICAL SPECIFICATIONS + TECHNICAL OFFER

Contract title : Supply of equipment for the Energy Efficiency Laboratories in the framework of Developing and Adapting Professional Programs for Energy Efficiency in the Western Balkans Project p 1 /19

Publication reference : 543782-TEMPUS-1-2013-1-AL-JPCR

Columns 1-2 should be completed by the Contracting Authority

Columns 3-4 should be completed by the tenderer

Column 5 is reserved for the evaluation committee

Annex III - the Contractor's technical offer

The tenderers are requested to complete the template on the next pages:

• Column 2 is completed by the Contracting Authority shows the required specifications (not to be modified by the tenderer),

• Column 3 is to be filled in by the tenderer and must detail what is offered (for example the words “compliant” or “yes” are not sufficient)

• Column 4 allows the tenderer to make comments on its proposed supply and to make eventual references to the documentation

The eventual documentation supplied should clearly indicate (highlight, mark) the models offered and the options included, if any, so that the evaluators can see the exact configuration. Offers that do not permit to identify precisely the models and the specifications may be rejected by the evaluation committee.

The offer must be clear enough to allow the evaluators to make an easy comparison between the requested specifications and the offered specifications.

LOT 1: Control and measurement instruments and equipments

|1. |2. |3. |4. |5. |

|Item Number |Specifications Required |Specifications Offered |Notes, remarks, |Evaluation Committee’s notes |

| | | |ref to documentation | |

| | | | | |

| |Portable , multi-function instrument for air parameter measurements | | | |

|1 |( included : data loger & software data ) | | | |

| | | | | |

| |-Measures , of the simultaneous parameters according to the applications: Pressure, | | | |

| |Temperature , Humidity, Air Quality ( CO / CO2), Air Velocity & Airflow ( vane probes and | | | |

| |hotwire ) , Gas detection , Light , Tachometry and wireless probe for temperature and | | | |

| |humidity | | | |

| |-The equipment should have a big color display to simplify the navigation in menus and | | | |

| |easily should be transformed into micromanometer, thermo-hygrometer, co-meter or | | | |

| |thermometer. | | | |

| |-The equipment should have a PC software for the analysis, archiving and documentationof | | | |

| |measurement data (see versions) | | | |

| |-Guarantees shockproofing and comfortable to hold. A magnetic casing and probe holders to | | | |

| |allow for easier measurements | | | |

| |-Interchangeable probes and modules , including rotating vane and telescopic hotwire. | | | |

| |-All probes and modules of the instrument should be compatible with the device and | | | |

| |automatically recognized by it | | | |

| |- IAQ probe for evaluating Indoor Air Quality | | | |

| | | | | |

| |General data | | | |

| |Operating temperature : -20 to +50 °C | | | |

| |Storage temperature :-20 to +50 °C | | | |

| |Housing material : ABS/TPE/Metal | | | |

| |Protection class : IP54 | | | |

| |Warranty : 2 years or more | | | |

| | | | | |

| |Measure probes | | | |

| |-IAQ probe for the measurement of CO2, air temperature, indoor air humidity | | | |

| |and absolute pressure ( 0-50 °C ; 0 – 100 %RH; 0 – 10.000 ppm CO2 | | | |

| |-Thermal flow velocity probe with integrated temperature and air humidity measurement | | | |

| |Wireless probes for temperature measurements | | | |

| |-Ambient CO probe for detecting CO in building and rooms 0 – 500 ppm | | | |

| |Absolute pressure probe | | | |

| |-globe probe for measuring of the radiant heat | | | |

| |Wireless probe for air temperature and air humidity measurement | | | |

| |Lux probe for the measurement of light intensity | | | |

| |Temperature probe for determining U-value | | | |

| |Instrument equipment | | | |

| |Easy operation with user profiles | | | |

| |Illuminated display | | | |

| | | | | |

| |PC software for the analysis, archiving and documentation of the readings | | | |

| |Vane probe Ø 60 and 100 mm | | | |

| |-Vane telescopic probe Ø 16 mm | | | |

| |- Vane telescopic probe Ø 60 mm | | | |

| | | | | |

|2 |Thermo-anemometer | | | |

| | | | | |

| |Measuring elements : Air velocity Ambient & temperature | | | |

| |The equipment should have all the probes for measure the above measuring elements | | | |

| |Measuring units, Measuring range, Accuracy and Resolution | | | |

| |Velocity : | | | |

| |m/s, fpm, km/h From 0.3 to 20 m/s | | | |

| |Airflow : | | | |

| |m³/h, cfm, l/s, m³/s | | | |

| |From 0 to 99 999 m³/h ; ±3% of reading ±0.03 * area (cm²) 1 m³/h | | | |

| |Temperature | | | |

| |°C, °F From 0 to +50 °C ±0.4 % of reading ±0.3 °C 0.1 °C | | | |

| |Dynamic range 0.5 s 100 dB | | | |

| |Data storage approx. 31000 measurements | | | |

| | | | | |

| |Sound level meter | | | |

|3 | | | | |

| |The sound level meter is reliable, easy to use and in accordance with metrology | | | |

| |requirements. | | | |

| |Measure : Sound-pressure level, Time averaged or equivalent continuous sound pressure level.| | | |

| |Five different measurement modes | | | |

| |The equipment should have all the probes for measure the above measuring elements | | | |

| | | | | |

| |Technical data | | | |

| |Measured parameters : LA et LAeq | | | |

| |Other displayed parameters : LAFmax, LAFmin, LASmax, LASmin | | | |

| |Frequency weighting : A | | | |

| |Measuring range : 30-130 dB | | | |

| |Resolution : 0,1 dB | | | |

| |Accessories | | | |

| |Automatic check of sound level meter | | | |

| | | | | |

| | | | | |

| |Hand-held luxmeter | | | |

|4 | | | | |

| |hand-held luxmeter, self-contained and automatic is specially designed to illuminance | | | |

| |measurement. | | | |

| |Dedicated to control and monitoring illuminance. | | | |

| |Measuring range : from 0,1 to 100 000 lux (from 0,01 to 13940 fc). | | | |

| |Uniformity: calculation of the min / ave ratio for determination of illuminance uniformity | | | |

| |at workstation according standards | | | |

| |Display illuminance for local measurements | | | |

| |With timed measurement : min., max. and average values | | | |

| |Pause function to eliminate any unrepresentative illuminance and display for | | | |

| |The equipment should have all the probes for measure the above measuring elements | | | |

| |Supplied with transport case. | | | |

| | | | | |

| |Technical data | | | |

| |Instantaneous illuminance: displaying of instantaneous / maximum / minimum values | | | |

| |Accuracy to DIN 13032-1:f1 = 6% = V (Lambda) adaptation ;f2 = 5% = cos like rating | | | |

| |Resolution :1 Lux (0 to +32000 Lux)10 Lux (0 to +100000 Lux) | | | |

| |Warranty 2 years | | | |

| |Connection Fixed cable, coiled | | | |

| |Memory 3000 | | | |

| |Oper. temp. 0 to +50 °C | | | |

| |Storage temp. -20 to +70 °C | | | |

| | | | | |

| |Solarimeter | | | |

|5 |Measurement and spot check of solar power (W/m2). | | | |

| |Supplied with calibration certificate and transport case. | | | |

| |The equipment should have all the probes for measure the above measuring parameters | | | |

| | | | | |

| |Technical data | | | |

| |Instantaneous, average, min/max values, hold function | | | |

| |Spectral response from 400 to 1100 nm | | | |

| |Calculation of energetic exposure in Wh/m2 | | | |

| |Recorder values | | | |

| |Results (Wh/m2) saved when instrument is switched off | | | |

| |Solar irrigation measuring range : from 1 W/m2 to 1300 W/m2 | | | |

| |Energetic exposure measuring range : from 1 Wh/m2 to 500 kWh/m2 | | | |

| |Frequency of measurement : 1/s | | | |

| | | | | |

| |Laser thermometer | | | |

|6 |( with integrated humidity module ) | | | |

| |-A tool to measure surface temperatures of hot objects, dangerous or difficult to access. | | | |

| |-Supplied in case holster. | | | |

| |-Switchable optics for measurements in the far-field (75:1) | | | |

| |and close focus (1 mm, distance 70 mm) | | | |

| |-Especially bright laser marking of actual measurement point | | | |

| |-Probe input for TC probes for determining emissivity | | | |

| |-Optical and audible alarm when limit values are violated | | | |

| |- infrared temperature measuring instrument with cross laser sighting incl. humidity | | | |

| |module, switchable optics for far-field and close focus measurement, PC software incl. USB | | | |

| |data transfer cable, aluminium case, battery and calibration protocol | | | |

| | | | | |

| |Technical data | | | |

| |Spectral response : 8 - 14 µm | | | |

| |Optical : 20:1 | | | |

| |Dual laser sighting : wave lenght : from 630 nm-670 mm | | | |

| |Emissivity : adjustable de 0.10 à 1.00 (pre-seat at 0.95) | | | |

| |Humidity module :0 to +100 %RH / 0 to +50 °C / -20 to +50 °C td | | | |

| | | | | |

|7 |Digital refrigerant leak detector | | | |

| |Product description | | | |

| |-Very high sensitivity of 〈3g/a allows the detection of the | | | |

| |smallest leaks | | | |

| |-Very long sensor life | | | |

| |-Optical and audible alarm for optimum leakage detection | | | |

| |-Permanent sensor check for fast and safe work | | | |

| |-Earphone connection for secure leakage detection in loud | | | |

| |surroundings | | | |

| |-Trend display shows maximum leakages | | | |

| |The | | | |

| |Suitable for fast and reliable detection of all common refrigerants.Including refrigerant | | | |

| |(HCFC, CFC, HFC, H2) sensor, The technical parameters | | | |

| |-Minimum sensitivity: 3g/ | | | |

| |-Reaction time: < 1 second | | | |

| |-Alarm: LCD and sound | | | |

| |-Start-up time 〈50 s (0 to +50 °C) 〈80 s (-20 to 0 °C) | | | |

| |-Oper. temp. -20 to +50 °C | | | |

| |-Oper. humidity 20 to 80 %RH | | | |

| |-Storage temp. -25 to +70 °C | | | |

| |-Proprietary sensor with lifetime of more than 3oo hours | | | |

| |-Detects all commercially available refrigerant | | | |

| |including refrigerant (HCFC, CFC, HFC, H2) R22;R134a; R407; R410A; | | | |

| |-should have : sensor, the instrument package, charger, ear plugs. | | | |

| |Product characteristics: | | | |

| |-Sound and light alarm | | | |

| |-Sensor continuous detection | | | |

| |In a noisy environment, can easily identify the leaking location through the ear | | | |

| |-In a noisy environment, can easily identify the leaking location through the ear | | | |

| |-Automatic calibration | | | |

| |Digital Testing Manifolds Refrigerant Pressure Vacuum Gauge | | | |

| |The manifold for measuring, analysing and documenting on a refrigeration system or heat | | | |

|8 |pump. | | | |

| | | | | |

| |Calculate superheating and subcooling simultaneously | | | |

| |Record pressure, temperature, current and vacuum | | | |

| |measurement in one instrument | | | |

| |Digital Testing Manifolds Refrigerant Pressure Vacuum Gauge with charging Hose ideal for | | | |

| |all measurement work on refrigeration systems and heat pumps. With clamps and storage bag. | | | |

| |The digital testing manifold must have a durable housing that protects the analyzer from the| | | |

| |everyday bumps and drops. | | | |

| |The equipment should have all the probes for measure the above measuring parameters | | | |

| |Features: | | | |

| |Measures high side / low side pressures and temperatures and displays saturation and | | | |

| |evaporation temperatures | | | |

| |Automatic superheat and sub-cooling calculations | | | |

| |A metal frame around the display has to be installed,making the instrument more robust | | | |

| |With sight glass | | | |

| |Transport case | | | |

| |USB connection cable, instrument-PC | | | |

| |-Measuring range : 50 bar -50 to +150 °C | | | |

| |-Accuracy (at 22 °C) 0.5% fs (±1 Digit) ±0.5°C (±1 Digit) | | | |

| |-Resolution 0.01 bar / 0,1 psi 0.1 °C/0.1 °F | | | |

| |-Probe connections 3 x 7/16" – UNF + 1 x 5/8'' – UNF 3 x plug-in (NTC) | | | |

| |Overload rel. (LP/HP) 52 bar / 52 bar – | | | |

| |General technical data | | | |

| |-Display LCD graphics display | | | |

| |-IP42 | | | |

| |- Warranty 2 years | | | |

| |-Oil pressure probe to monitor the oil level with 2.9 m cable, refrigerant and oil resistant| | | |

| |Fixed cable 2.9 m | | | |

| |-Clamp probe for measurement on pipes for diameter 6 to 35 mm, | | | |

| |Hand-held laser distance&volume meter | | | |

| |( professional kit ) | | | |

|9 | | | | |

| |The Laser distance&volume meter is specially designed to measure precisely : | | | |

| |distance,area,volume,addition,subtraction easily. The laser distance meter is hand-held and| | | |

| |easy to operate. | | | |

| |-includes tool, tool bag, batteries, operating instructions and application brochure in | | | |

| |cardboard box, | | | |

| |Features : | | | |

| |meter is hand-held and easy to operate | | | |

| |Instant measurement of distance, area & volume with one button operation | | | |

| |Wide measuring range | | | |

| |High accuracy: +/-1.5mm; | | | |

| |Automatic calculation of Area and Volume | | | |

| |Data store/ recall function | | | |

| |Data Hold / Data clear function | | | |

| |Large LCD with backlight and multi-line display (4 lines) | | | |

| |Multifunction with intelligent calculation | | | |

| |Power Auto off | | | |

| |Range : up to 200m | | | |

| |Laser class : 635 nm ( classe 2 ) | | | |

| |Clamp Meter | | | |

| |A clamp meter is an electrical tester that combines a voltmeter with a clamp type current | | | |

|10 |meter. Like the multimeter, the clamp meter is the digital instrument.The clamp meter is a | | | |

| |troubleshooting tools for commercial and residential electricians, designed to verify the | | | |

| |presence of load current, AC voltage and continuity of circuits, switches, fuses and | | | |

| |contacts | | | |

| |Features ( measurement capability ) : | | | |

| |400 A ac and dc current measurement | | | |

| |600 V ac and dc voltage measurement | | | |

| |Resistance measurement up to 40 kΩ with continuity detection | | | |

| |Frequency measurement | | | |

| |Capacitance | | | |

| |0 to 100 mf | | | |

| |AC response | | | |

| |Backlight | | | |

| |Data hold | | | |

| |Slim,ergonomic design | | | |

| |Soft carrying case | | | |

| |Thermal imager | | | |

| |Thermal imager for building thermography | | | |

|11 |Detector type – 320x240 FPA | | | |

| |Super resolution - ( 4 x pixel upgrade ) 640 x 480 ( included ) | | | |

| |Thermal sensitivity – 50 mK | | | |

| |Visual camera – included | | | |

| |Video output via USB - included | | | |

| |Lens protection glass – included | | | |

| |Focus mode – manual & motor | | | |

| |Spectral range – 8 to 14 mm. | | | |

| |Image display – 3.5 “ LCD | | | |

| |Temperature range – 662 °F | | | |

| |Isotherm function – included | | | |

| |Solar mode – included | | | |

| |Surface moisture distribution – included | | | |

| |Storage device – 2GB SD card | | | |

| |Operating temperature range – 5 ° to 104 °F | | | |

| |Housing ABS plastic | | | |

| |Software system requirements – window XP , Vista , 7 & USB 2.0 port | | | |

| | | | | |

|12 |Flue gas analysers ( for boiler system with burner ) | | | |

| | | | | |

| |In this central measurement in the course of flue gas | | | |

| |analysis , you direc tly de termine CO a nd O2 content | | | |

| |as well as the ambient and flue gas temperatures. | | | |

| |From these values, and dependent on fuel-specific | | | |

| |parameters, the instrument automatically calculates all | | | |

| |other measurement parameters such as CO2 concen | | | |

| |tration, degree of effec tivity and flue gas loss. This | | | |

| |allows to confidently e valuate whether the heat - | | | |

| |ing system is correctly adjusted and working efficiently. If required, you can carry out an | | | |

| |optimization | | | |

| |which lowers fuel consumption, improves the degree | | | |

| |of effectivity of the heating system and saves . | | | |

| | | | | |

| |The equipment should have all the probes for measure the above measuring elements | | | |

| |Technical data : | | | |

| |-Temperature (flue gas) : 0.0 to 800.0 °C | | | |

| |-Temperature (A mbient temperature): - 20 to +100 .0 °C | | | |

| |-O2 measurement : 0,0 to 21.0 vol.% | | | |

| | | | | |

| |-CO measurement (with out H 2 compensation) : 0 to 4000 ppm | | | |

| |-Ambient CO measurement : 0 to 4000 ppm | | | |

| | | | | |

| |-Standard gas sampling probes: Modular flue gas probes, available in 2 lengths, incl. probe | | | |

| |stop, NiCr-Ni thermocouple, aprox. 2 m hose and particle filter | | | |

| |-Modular flue gas probe with pre-filter Ø 14 mm 700 mm immersion depth, incl. cone, | | | |

| |thermocouple NiCr-Ni (TI)n Tmax 1000°C and NO2 /SO2 special hose aprox. 2 m | | | |

| |-Probe shaft with pre-filter, length 700 mm, incl. probe stop, Ø 8 mm, Tmax 1000 °C | | | |

| |-Spare sintered filter , Spare dirt filter, modular probe; | | | |

| |-Pitot tube, 350 mm long, stainless steel, measures flow velocity | | | |

| |-Mini ambient air probe; for separate ambient air temperature measurement; 0 to +80 °C | | | |

| | | | | |

| |-Thermocouple for exhaust gas temperature measurement, NiCr-Ni, length 400 mm, Tmax. +1000 | | | |

| |°C with 2.4 m | | | |

| | | | | |

| |HVAC Performance Multi-Function Meter Kit | | | |

|13 |The multifunction meter should be for monitoring, analyzing and diagnosing indoor air | | | |

| |quality anywhere we need to take important IAQ measurements. In addition, we can easily | | | |

| |pinpoint and troubleshoot problems with HVAC systems and see the results of corrections | | | |

| |immediately. | | | |

| |The equipment should have all the probes for measure the above measuring parameters | | | |

| |with memory, software & integral differential pressure | | | |

| |5/8" vane probe | | | |

| |Wireless module | | | |

| |2x wireless humidity probes | | | |

| |Case | | | |

| |Static tip | | | |

| |Integrated differential pressure measurements for flow velocity | | | |

| |Optional wireless (RF) temperature and humidity probes for remote measurement | | | |

| |Backlit LCD for easy viewing | | | |

| |Built-in memory stores up to 10,000 measurements | | | |

| |Data recording for 10,000 readings | | | |

| |ComSoft PC Software for analyzing, archiving, and documenting data | | | |

| | | | | |

|14 |Climate measuring instrument |Top of Form | | |

| |(Service Instrument for Air Conditioning / Ventilation Systems) |Bottom of Form | | |

| |The VAC instrument should have all the probes to measures : temperature, relative humidity, | | | |

| |dew point, absolute humidity, degree of humidity, enthalpy, all types of air velocity (in | | | |

| |ducts, duct openings or extractors), volume flow, pressure and indoor air quality . Included| | | |

| |climate measuring instrument. | | | |

| |Air velocity (in ventilation ducts, at duct outlets and on extractors) | | | |

| |Volume flow | | | |

| |Indoor air quality (CO2) | | | |

| |Temperature | | | |

| |Relative air humidity | | | |

| |Dew point | | | |

| |Absolute humidity | | | |

| |Degree of humidity | | | |

| |Enthalpy | | | |

| |Pressure | | | |

| |CO in indoor air | | | |

| |Features | | | |

| |Automatic mean calculation and volume flow measurement | | | |

| |Automatic allocation of duct cross-section to location (max. 99 locations) | | | |

| |Internal data logger (3,000 readings) | | | |

| |Simultaneous measurement of up to 6 parameters | | | |

| |The equipment should have all the probes for measure the above measuring parameters | | | |

| |Characteristic : | | | |

| |measuring range | | | |

| |temperature : - 50 to +150 °C ; | | | |

| |humidity : 0 to 100% ; | | | |

| |velocity : 1 to 20 m/s ; | | | |

| |ambient CO : 0 to 500 ppm CO | | | |

| |ambjent CO2 : 0 to 10.000 ppm | | | |

| |Housing – ABS ; | | | |

| |Warranty – 2 years ; | | | |

| |Display type – LCD ; | | | |

| |Display size – 4 lines ; | | | |

| |Memory – 3.000 measuring values | | | |

| | | | | |

| |Thermal comfort level measurement | | | |

|15 |(Digital temperature, humidity and air flow meter) | | | |

| |measurements in ducts, temperature measurements in laboratories, humidity measurements in | | | |

| |production, pressure difference measurements in clean rooms. Digital temperature, humidity | | | |

| |and air flow meter with a wide range of optional sensors that allow us to measure, analyse | | | |

| |and log all relevant ventilation and indoor air quality parameters . It should provide | | | |

| |independent experts, consultants, technical service providers and HVAC technicians in the | | | |

| |field of ventilation and indoor air quality with an efficient means of carrying out all | | | |

| |their measurements – i.e. norm-compliant setting and adjustment of air conditioning and | | | |

| |ventilation systems in offices, residential and industrial buildings – using just one single| | | |

| |device. It also should check quality parameters in production and processing quickly and | | | |

| |reliably. | | | |

| |Product characteristicss: | | | |

| |The equipment should have all the probes and a wide range of high-quality optional sensors| | | |

| |for carrying out the following measurements: | | | |

| |Air flow and volume flow (also fume cupboard measurements) | | | |

| |Temperature | | | |

| |Humidity | | | |

| |Pressure (difference and absolute pressure) | | | |

| |CO2 | | | |

| |Illumination intensity | | | |

| |PMV/PPD | | | |

| |Heat radiation | | | |

| |Degree of turbulence | | | |

| |WBGT Index | | | |

LOT 2: Installation maintenance instruments and equipments

|1. |2. |3. |4. |5. |

|Item Number |Specifications Required |Specifications Offered |Notes, remarks, |Evaluation Committee’s notes |

| | | |ref to documentation | |

| | | | | |

|1 |Air Vacuum Pump | | | |

| | | | | |

| |Two-stage rotary vane pump | | | |

| |Compact, portable device for vacuum and cleansing of refrigeration systems of all kinds. | | | |

| |Key features: | | | |

| |-Magnetic safety valve to protect the refrigeration cycle from oil contamination during | | | |

| |power outage | | | |

| |-Vacuum meter with integrated drag indicator enables simple and fast control of the vacuum | | | |

| |process | | | |

| |-Gas ballast valve for reduction of water vapour in the oil container | | | |

| |-Specially designed filter to reduces oil mist on nozzle | | | |

| |-Gauge-glass enables easy oil level monitoring | | | |

| |-Capacity : 100 L/min | | | |

| |Multi split air conditioner inverter | | | |

|2 |2x 9000 btu indoor unit ( one indoor unit : on the wall split type and one other duct | | | |

| |split type ) | | | |

| | | | | |

|3 |Roflare Tools | | | |

| |( revolver type ) | | | |

| | | | | |

| |RoFlare revolver is a Compact Flaring Tool, 3/16 to 5/8-inch includes RoFlare basic tool | | | |

| |with multiblock. Compact Flaring Tool, foldable For producing precision 45-degrees single | | | |

| |flares on copper, brass, aluminum and precision steel tubes up to 0.04-inch (1 mm) in wall | | | |

| |thickness. Ideal for mobile applications and for pipes in refrigeration . Double and | | | |

| |180-degrees flares are also possible with the RoFlare double flare attachment. | | | |

| |• Hardened and polished flare cone: High quality flare sealing surface | | | |

| |• Multi block multi-clamping calipers: Firm, quick, off-center clamping of the tube and | | | |

| |automatic self-centering tubes don't slip | | | |

| |• Mold available in metric and English measurements | | | |

| |• Special screw thread: Allows smooth, efficient deformation of material | | | |

| |• Made from high quality steel: Long-lasting | | | |

| | | | | |

| |Copper Pipe Cutter | | | |

|4 | | | | |

| |High precision, smooth action telescopic tube cutter with tightest possible constant turning| | | |

| |radius for cutting copper, brass and aluminum | | | |

| |Compact construction, with sturdy aluminum casting, black plated, enclosed threaded spindle | | | |

| |to protect against dirt and jamming | | | |

| |Foldaway reamer and integral spare cutter wheel in handle knob. | | | |

| |Enclosed feed action with sturdy aluminum body guarantees sharp and accurate cuts time after| | | |

| |time | | | |

| |Features: | | | |

| |Handy cutting tool for 6mm - 35mm copper tubes | | | |

| |Heavy duty telescopic action precision tube cutting | | | |

| | | | | |

|5 |Pipe bending tool | | | |

| | | | | |

| |One Handed Bender for exact bending up to 90° of tubes made of: | | | |

| |Soft copper and aluminum tubing         | | | |

| |Universal application in the following areas: plumbing, refrigeration, air-conditioning. | | | |

| | | | | |

| |Key features | | | |

| |Precision tube bending even in confined spaces | | | |

| |Eliminates the need for manufactured fittings | | | |

| |Bends are formed with the minimum tube distortion for optimum flow rates | | | |

| |Bending formers are quick and easy to change for use with different tube sizes | | | |

| |Heavy Duty Brazing Torch Includes Swirl Flame burner - For soft and hard soldering | | | |

| |Brazing torch ideal for soldering and brazing use in plumbing heating refrigeration air | | | |

|6 |conditioning and other associated trades. This tool has to provides the highest standards in| | | |

| |concentrating high temperatures for fast and effective soldering and brazing. | | | |

| |Features : | | | |

| |Stainless steel burn tube. | | | |

| |Turbine flame burner tip for brazing up to 28mm OD | | | |

| |Brazing torch is complete with piezo ignition | | | |

| |Can be used with map or propane gas | | | |

| |Instant automatic ignition | | | |

| |Solid die cast torch body | | | |

| |Works in any position - even upside down | | | |

| |Professional performance | | | |

| |Machine for recycling,regeneration,washing,leak hunting,vacuum pumping,affusing, | | | |

| |oil-changing and refueling for all the refrigerant system components | | | |

|7 |The machine has many functions, such as recycling, regeneration, washing, leak hunting, | | | |

| |vacuum pumping, affusing and refueling. the operating keyboard is navigating type and easy | | | |

| |to understand, freely switching between manually and automatically. The pipe link is simple | | | |

| |and convenient, it can work only connecting the tube to the air conditioner maintenance | | | |

| |interface. The electronic weigher measures accurately. The electronic sensor controls | | | |

| |recycling, leak hunting, washing, vacuum pumping and affusing. The speed of recycling of | | | |

| |high-power compressor is fast. The LCD screen is briefed on the regular maintenance content | | | |

| |automatically. Measure and diagnose whether the air conditioner system is unloaded and | | | |

| |leaked automatically. Automatically recycle refrigerant and reutilize it. Pump the vacuum | | | |

| |automatically. Affusing refrigerant automatically. Get rid of the moisture content , | | | |

| |something acid and impurity from old refrigerant automatically. When system works | | | |

| |abnormally, the warning functions can show information of trouble in LCD screen. It can wash| | | |

| |the air conditioner pipeline | | | |

| |Technical Parameters: | | | |

| |Speed of pumping vacuum: 3 liters per second | | | |

| |Speed of recycling : >3 grams per second | | | |

| |Speed of affusing: 18 grams per second | | | |

| |Precision of weighing: + 5 grams | | | |

| |Precision of affusing: + 5 grams | | | |

| |Precision of measuring the pressure: 0.0015 Mpa Power:220V/50HZ | | | |

| |Working tankage size: 10 kilograms/15 kilograms | | | |

| |The kind of refrigerant interface: R134a , R22 , R 410 , R 12. Etc | | | |

LOT 3: Software

|1. |2. |3. |4. |5. |

|Item Number |Specifications Required |Specifications Offered |Notes, remarks, |Evaluation Committee’s notes |

| | | |ref to documentation | |

| |HVAC software | | | |

|22 |Software for : | | | |

| |Thermal load calculation ( heating and cooling ) for residential as well as for commercial| | | |

| |applications | | | |

| |Duct calculations ( for ventilation and A/C system ) with parameters such as m3/ore,load and| | | |

| |pressure drop, system losses, fan static pressure requirement,fan selection, duct sizing | | | |

| |and drawing of the duct work in both 2D and 3D. | | | |

| |HVAC system and equipment design,components sizing for a wide variety HVAC system type ( | | | |

| |duct system , chiller system , fancoil ( including here infrastructure and water pipe | | | |

| |dimensions for chilling system ) , AHU, boiler plumbing etc ) | | | |

| |For residential , commercial and industrial applications | | | |

................
................