SUMMARY REPORT - Elevator Consulting Services



MAY 2015

Elevator QEI & Maintenance

and Recommendation Report

PASSENGER ELEVATOR 1

U.S. BANK

PORTAGE MAIN-SITE 4008

238 WEST WISCONSIN

PORTAGE, WI 53901

By: ELEVATOR CONSULTING SERVICES, INC.

SUMMARY OF ELEVATORS

The elevator equipment this location was inspected by Tom Branham of Elevator Consulting Services, Inc. on May 28. 2015. Tom is certified by NAESA. NAESA is the National Association of Elevator Safety Authorities and his QEI number is C 1339. We have identified maintenance deficiencies that in our opinion need to be addressed by the elevator contractor. They are free to offer an explanation or dispute any individual item within the report but we can offer a reasonable reason for each and every negative evaluation. They are evaluated on and for the ASME 17.2 Code for Inspectors Manual and normal preventive maintenance parameters within the elevator industry.

KEY

UNSAT Unsatisfactory NW Not Working

NC Not Checked NA Not Applicable

OK Satisfactory NI Needs Improvement

ITEMS IN RED ARE THE RESPONSIBILITY OF THE ELEVATOR CONTRACTOR

ITEMS IN BLUE ARE THE RESPONSIBILITY OF THE BUILDING OWNER

Equipment Inventory

Control Type: SELECTIVE COLLECTIVE

OTIS HVP 2000

Contract Speed: 125 FPM

Machine Type: BOREHOLE

OTIS HVP PUMP UNIT

OTIS PUMP UNIT

Door Equipment: OTIS 7300

Door Size/Type: 36” WIDE X 84” HIGH - 1SSS

Number of Openings: 3 FRONT- IN LINE

Travel: NO DATA

Floors Served: * 1, 2, 3

State Number: 15979

WISC

Capacity: 2000 LBS

Fire Service Log: N/A

Maintenance Log: NI (1 ENTRY FOR 2015)

Oil Monitoring Log: NI

MSDS Documentation: NI

ALL OILS, LUBRICANTS, SOLVENTS

Inspector’s Key Box: N/A

Inspector’s Keys: NI (LUNAR KEY)

Service Vendor: SCHINDLER

PERFORMANCE

Speed Up: 125 FPM

Speed Down: 125 FPM

Perform Up: 16.3 SEC

1-2

Perform Down: 15.3 SEC

Door Open: 2.4 SEC

Door Close: 4.8 SEC

Hall Call Dwell: 3.5 SEC

Car Call Dwell: 3.5 SEC

Nudging: N/A

Door Torque: 5 LBS

Ride Quality

Ride: OK

Deceleration Up: OK

Deceleration Down: OK

Noise: OK

Acceleration Up: OK

Acceleration Down: OK

Stop: OK

Leveling: OK

Equipment Room

Access: OK

Headroom: OK - MINIMUAL

Enclosure: NI

STONEWALL DETERIORATION

Lighting: NI- NON CONFORMING

1 INCANDESCENT

Cleanliness: NI

Air Circulation, Ventilation: OK

Pipes, Ducts, Non Elevator: NONE

Parts: MINOR

GFIC Receptacles: REG ONLY

Fire Extinguisher: NONE

Guarding: OK

Self-Closing, Locking Labeled door: NO CLOSURE

Numbering of units: N/A

Sprinkler in room: NO

Lockable, Fused Disconnect: OK

BREAKER 125 A

110 Volt Disconnect: 20 AMP BREAKER IN MR

Equipment Power Supply: 208-VOLTS

Earth Ground Present: NO

Shunt trip protection: N/A

Shunt Trip Monitored: N/A

Equipment Room Continued

Signage on door: OK APO

Smoke Detector: NO

Heat Head: NO

Emergency Evacuation Guides: NO

Control Panel

Type of Control: HVP 2000 SELECTIVE COLLECTIVE

Manufacturer: OTIS

Installation Date: 2-23-76

Installation Code: ASME 17.1 /1974

Controller Data Tag: NO

Cleanliness: OK

Identification: OK

SALES JOB # 325899 SERIAL # 246111 BP (OR 248111 BP)

Software Version: N/A

Guarding: OK

U.L. / CSA Labeled: NO

Fire Service Alternate Floor: N/A

Components-Controller

Relays: OK

Enclosure / Open Style: OPEN

Contacts: OK

Resistors: OK

P.C. Boards / Timers: OK

Capacitors: OK

Wiring: OK

Performance: OK

Camera Wire: NO

Telephone: NA

Starters

Manufacturer: OTIS

Type: ACROSS LINE

Size: 6830 RELAY

Contacts: OK

Wiring: OK

Mounting: OK

Phase Protection: OK

Up Starts: NO DATA

Battery Rescuvator

Existing: NO

Manufacturer: N/A

Model: N/A

Serial #: N/A

Battery: N/A

Wiring: N/A

Operational: N/A

Pump Unit

Manufacturer: OTIS

Model: STANDARD HVP

Cleanliness: OK

Leaks: NONE

Noise: OK

Sheave: OK

Belts: OK

Hose Condition: OK

Oil level: OK

Oil: OK

Pump: OK

IMO 217

Oil Line Shut Offs: NO

Subs / Dry: DRY

Valves: OK

EECO UV-5

Muffler: FREEMAN IN LINE

Seals: NI

Covers: OK

Annual No Load Test: OK

Tagged: 3/10/15

Motor

Manufacturer: IMPERIAL

Type: 80

Isolation: OK

Grounded: OK

Bearings: OK

Covers: OK

Frame: 215 T

HP: 20 HP

RPM: 3480

AMPS: 48/24

Starts/Hour: 80

NEMA Code: G

Oil Coolers

Existing: NO

Manufacturer: N/A

Hoses: N/A

Wiring: N/A

Leaks: N/A

HP: N/A

Oil Filter: N/A

Motor: N/A

Hoistway

Selector Car Top Device

Cleanliness: OK

Vanes: OK

Switches: OK

Tape: N/A

Magnets: N/A

Limit Switches

Roller Noise: OK

Operation: OK

Type: OTIS STND

Rails

Cleanliness: OK

Lubrication: OK

Type: T / 8 LBS

Fastening: OK

Solid Shoes: OK

OTIS ORIGINAL

Cable Condition

Traveling: OK

Type: NEOPRENE

Suspension: OK

Spares: OK

Kellum Grips: OK

Hoist cables: N/A

(Roped hydro)

Shackles: N/A

(Roped Hydro)

Hoistway Venting

Existing: NO

Motorized: NO

Key Switch: NO

Safety Bars: NO

Size (3%): NO

Hoistway Equipment

Car Top

Cleanliness: OK

Maintenance Station: OK

Stop Switch: OK

Data Plate: OK

Light: OK

Light Guards: OK

Guides: OK

OTIS ORIGINAL

GFIC Receptacle: NO

Escape hatch locked: OK

Windows in Hoistway: NONE

Multiple Hoistways: N/A

Car Top Railing: NO

Stenciled: N/A

Door Operator

Type: OTIS 7300

Cleanliness: OK

Door Protection: SAFETY EDGE ONLY

Lubrication: OK

Belts: N/A

Chains OK

Hangers: OK

Arms: OK

Bearings: OK

Noise: OK

Tracks: OK

Upthrusts: OK

Restrictor: NO

Gibs: OK

Car Enclosure

Ventilation: OK

FAN

Walls: LAMINANT STAND OFF PANELS- 3 WALLS

SS FRONT

Returns: STAINLESS STEEL # 4

Car Lighting: OK

2 FLORESCENT

Ceiling: OK

3 PANELS- MILK PLASTIC PANELS

Position Indicators: NONE

Handrails/Bumpers: NONE

Flooring: CARPET

Car Doors: STAINLESS STEEL

Sills: ALUMINUM

Platform: SQUARE / OK

Certificate Frame: NO

Car Riding Lantern: NO

Camera: NO

Card Reader: NO

Entrance Equipment

Cleanliness: OK

Lubrication: OK

Tracks: OK

Hangers: OK

Gibs: OK

Interlocks: OK

OTIS 6940

Bell Crank Release Rollers: OK

Bell Crank Release Assemblies OK

Noise: OK

Upthrust: OK

Closers/Spirators: OK

SPIRATORS

Braille: NONE

Running Clearance: 1 ¼ “

Sills: OK

ALUMINUM

Escutcheons: YES

ALL FLOORS

Star of Life: NO

Elevator Identification Tactile: N/A

Emergency Fire Box

Main Egress Landing: 1ST FLOOR

Existing in lobby: NO

Machine room key: N/A

Phase I, II keys: N/A

Lunar key: N/A

Vent Key: N/A

Keys Tagged: N/A

Fixtures

Car Operating Panel

Type: OTIS

Style: MECHANICAL

Condition: OK

Illuminated: YES

Height Compliance: NON CONFORMING

Braille Identification: NO

Buttons: OK

Phone: NONE

Phone Monitored: NO

Call Back Number: N/A

Alarm Button: NON CONFORMING

53” TO CENTER

Stop Switch: PUSH PUL / COP

Emergency Light: NONE

Capacity Plate / Engraved: OK

2000 LBS

Certificate Frame: YES

Certificate: NO

Service Cabinet

Light Switch: OK

KEYED

Fan Switch: N/A

Independent Service: N/A

Access Enable: N/A

Emergency Light Test: N/A

Inspection: OK

Stop Switch PUSH PULL

GFI Outlet: N/A

Door Hold: N/A

Fire Service Cabinet

Fire Fighters Instructions: N/A

Phase II key Switch: N/A

Call Cancel Button: N/A

Stop Switch: N/A

Fire Hat: N/A

Phone Jacks: N/A

Door Open Front: N/A

Door Open Rear: N/A

Door Close Front: N/A

Door Close Rear: N/A

Hall Buttons

Manufacturer: OTIS

Type: MECHANICAL

Condition: OK

Illuminated: OK

Height: OK

42” TO CENTER

Mechanical: OK

Lanterns: N/A

Braille: NO

Fire Signage: NO

Phase I key switch: N/A

Phase I instructions: N/A

Fire Hat / Indicator Light: N/A

Vent Key: N/A

Vent Light: N/A

Main Lobby Panel: N/A

Concealed Riser: N/A

Card Reader(s): N/A

Main Lobby Panel

Existing: NO

Location: N/A

Position Indicators: N/A

Emergency Power Key Switch: N/A

Emergency Power Independent Light: N/A

Fire Service Key Switch: N/A

Selection Switch: N/A

Pit Equipment

Bottom Inspection Access: WALK IN PIT

Run by: OK

Cleanliness: OK

Comp Guides: N/A

Car Buffer: OK

Counter Weight Buffer: N/A

Counter Weight Guard: N/A

Lights: OK

1 INCANDESCENT

Light Switch: OK

Light Guard: MISSING

Stop Switch: BY LADDER ONLY

Ladder: OK

GFIC Receptacles: REG ONLY

Jack Seal: OK

PVC Liner: N/A

Oil Line Shut Offs: OK

Piston Pans: N/A

Piston: OK

Rupture Valves: NO

High Pressure Vics: NO

Sump Hole / Drain: DRAIN ONLY

Pit Equipment Continued

Sump Pump: NO

Sump Pump Cover: N/A

Pit Bucket: N/A - RETURN LINE

Sprinkler: NO

Heat Head: NO

Smoke Detector: NO

Scavenger Pump: NO

Oil Return / Jack Line: YES

Governor Sheaves: N/A

(Roped Hydro)

Cables: N/A

(Roped Hydro)

Cable Tie: N/A

(Roped Hydro)

Bottom of Car

Cleanliness: OK

Static Weights: NO

Safeties (Visual Only): N/A

Traveling cable suspension: OK

Toe guard length: NI

13”

Toe Guard Stenciled: N/A

Isolation: OK

Light Fixture: OK

Light Guard: MISSING

Solid Shoes: ORIGINAL OTIS

Receptacle: OK

PORCELAIN FIXTURE

GFI Receptacle: NO

Platform-Fire Rated: OK

U.S. BANK

PORTAGE MAIN-SITE 4008

PASSENGER ELEVATOR 1

CORRECTIVE ITEMS

The following minimum items need corrective action taken:

Annual No Load Test: 3-10-15

1. Seal up relief valve per code. Perform the 5 year test again if mandated by the AHJ.

Completed ________________ Initialed ___________

2. Adjust open check on door operator to eliminate the harsh slams.

Completed ________________ Initialed ___________

3. Clean machine room.

Completed ________________ Initialed ___________

U.S. BANK

PORTAGE MAIN-SITE 4008

PASSENGER ELEVATOR 1

RECOMMENDATIONS

Short term

1. GFI outlet in machine room. Upgrade the existing receptacle or add a GFI receptacle to the machine room or pit. NEC 620-85 Code requires a GFI receptacle. Upgrade the existing receptacles in the machine room, pit and car top with a GFI receptacle. Machine room and pit normally provided and installed by non-elevator personnel. Elevator personnel normally assist in identifying location in the pit. Budget $ 1,800.00

2. Fire extinguisher. Install a fire extinguisher in the machine room. Needs to be an ABC unit, minimum of 5 lb unit, properly mounted and serviced within normal guidelines. Budget $ 100.00

3. Upgrade or provide emergency lights in the elevator. Emergency light unit with a 4 hour capability shall be installed in the car to provide light on the main car operating panel. Light shall not be less than 2.2 lx or 0.2 ftc. Shall include the alarm button backup with the battery device. The battery shall be marked with the date installed to assist in replacement frequency. ASME 17.3 Rule 3.11.1 Budget $ 1,800.00

4. Two way communication is required by ASME 17.3 Rule 3.11.1 A two-way device, hands free phone with Braille identification, indicator light when a connection is made and a call back feature shall be provided in each unit. Needs to auto dial a 24 hour number whether a phone center or 24 hour manned security desk Includes a phone cabinet, a shielded pair within an existing traveling cable or a new code conforming cable

5. Upgrade the existing door protection to an infra-red scanner assembly. Will improve reliability, safety to pedestrian users.

6. Seal the machine room walls. They are brick that is crystalizing. Clean up all the brick debris and seal the wall. Budget $ 2,400.00

7. Recommend additional lighting to meet the 19 foot candles required by Code. Budget $1,125.00

8. Fire signage. Install Appendix O“ In Case Of Fire “ fire signage at each landing other than the main landing. Appendix O has a pictoral recommended as the signage description. ASME 17.1 Rule 211. Budget 100.00

9. Add a door restrictor. Door Restrictor is needed for compliance with ASME A17.3 – 2002. Rule 2.7.4. restricted opening of hoistway doors and/or car doors on passenger elevators. Provide and install an approved method of restriction. Includes a restrictor clutch or angle method. Due to age, may include a recommended upgrade with a closed loop operator.

Restrictor Clutch modification ------------------------ $ 600.00

or

Angle method ---------------------------------------------$ 2,400.00

10. Identify the controller installation code on the controller door or main line disconnect per ASME 17.3 Code for Existing Elevators and Escalators. ASME 17.1 Rule 309, 908.1 Budget $ 100.00

11. Upgrade pit lighting. Provide enough lighting to meet the 10 foot candle requirement per code. Includes proper guards. Elevator personnel should spot and secure the elevator, the proper non-elevator personnel should perform required work. ASME 17.3 Rule 2.2.3

Currently has one 60 watt bulb. Budget $ 1,800.00

12. ADA REQUIREMENTS,

13. Replace car operating panel and hall fixtures. Will improve reliability, maintenance costs. Recommend Innovation or EPCO style units with LED cluster lights.

Long term

14. Upgrade the elevator in 3 to 5 years. The main controller is original and over 39 years old. There is nothing urgent but an upgrade should be considered within a few years for reliability and maintenance concerns. Budget 145,000.00 This number includes all of above and the low voltage, electrical etc of non elevator work to complete the project.

U.S. BANK

PORTAGE MAIN-SITE 4008

PASSENGER ELEVATOR 1

A. D. A. RECOMMENDATIONS

RULE 4.10.3 HALL CALL BUTTONS

EXISTING DOES NOT MEET REQUIREMENTS

NEEDS TO BE MECHANICAL, CENTER LINE AT 42”

RULE 4.10.4 HALL LANTERNS

EXISTING DOES MEET REQUIREMENTS

RULE 4.10.5 BRAILLE

EXISTING DOES NOT MEET REQUIREMENTS

NEEDS TO BE ON BOTH SIDES OF ENTRANCE AT 60” TO CENTER

RULE 4.10.6 DOOR PROTECTION & REOPENING

EXISTING DOES NOT MEET REQUIREMENTS (ONLY SE)

NEED TO HAVE AN INFARED CURTAIN STYLE INSTALLED

RULE 4.10.10 FLOOR SURFACE

EXISTING DOES MEET REQUIREMENTS

RULE 4.10.11 LIGHT LEVEL IN CAB

EXISTING DOES MEET REQUIREMENTS OF 10FCL

RULE 4.10.12 CAR CONTROLS

EXISTING DOES NOT MEET HEIGHT AND STYLE REQUIREMENTS

ALARM BELL NEED TO BE AT 35” FROM THE FLOOR

RULE 4.10.13 CAR POSITION INDICATORS

EXISTING DOES NOT MEET ALL REQUIREMENTS

NEEDS PASSING FLOOR GONG OR INDICATION

RULE 4.10.14 EMERGENCY COMMUNICATIONS

EXISTING DOES NOT MEET INTENT AND REQUIREMENT

NEEDS TO BE HANDSFREE, ADA COMPLIANT

ADAAG RULE 11 HANDRAILS

EXISTING DOES NOT MEET REQUIREMENTS (NONE CURRENTLY)

NEEDS A ROUND UNIT AT 32 INCHES FROM THE FLOOR

................
................