Bulletin 1606 Switched Mode Power Supplies

Reference Manual

Bulletin 1606 Switched Mode Power Supplies

Catalog Number: 1606-XLS240-UPSD

Index

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

General Description ............................................1

Specification Quick Reference .............................1

Catalog Numbers .....................................................1

Certification Marks ...................................................1

Input ............................................................................3

Output in Normal Mode ........................................4

Output in Buffer Mode ............................................5

Battery Input ..............................................................7

Buffer Time ...............................................................8

Efficiency and Power Losses ...............................10

Functional Diagram ...........................................10

Check Wiring and Battery Quality Tests ..........11

Relay Contacts and Inhibit Input .....................12

Front Side User Elements ....................................13

Terminals and Wiring ...........................................14

16.

17.

18.

19.

20.

21.

22.

23.

24.

25

26.

Reliability .......................................................... 15

EMC ...................................................................... 16

Environment ................................................... 17

Protection Features .................................... 17

Safety .................................................................. 18

Certifications ..................................................... 18

Environmental Compliance ......................... 19

Physical Dimensions and Weight .............. 19

Installation Notes ......................................... 20

Accessories ........................................................ 21

Application Notes ......................................... 22

26.1. Battery Replacement Intervals ...... 22

26.2. Parallel and Serial Use ....................... 23

26.3. Using the Inhibit Input ..................... 24

26.4. Troubleshooting ................................. 24

Terminology and Abbreviations

? DC UPS¡ªUninterruptible power supply with DC input.

? Normal mode¡ªDescribes a condition where the battery is charged, the input voltage is in range and the output is loaded within the

allowed limits..

? Buffer mode¡ªDescribes a condition where the input voltage is below the transfer threshold level, the unit is running on battery (buffering)

and the output is loaded within the allowed limits.

? Charging mode¡ªDescribes a condition where the battery is being charged, the input voltage is in range and the output is loaded within the

allowed limits.

? Inhibit mode¡ªDescribes a condition where buffering is disabled intentionally by using the inhibit input of the DC UPS (e.g. for service

actions or to save battery capacity).

? Buffer time¡ªEquivalent to the term ¡°hold-up time.¡±

? T.b.d.¡ªTo be defined, value or description will follow later.

Bulletin 1606 Switched Mode Power Supplies

DC-UPS, Dual Output

¡ö

¡ö

¡ö

¡ö

¡ö

¡ö

¡ö

¡ö

¡ö

24V DC-UPS With an Additional 12V Output for

Various Applications

Only One 12V Battery Required

Stable Output Voltage in Buffer Mode

Superior Battery Management for Longest Battery Life

Comprehensive Diagnostic and Monitoring Functions

Replace Battery Signal Included

Electronically Overload and Short Circuit Protected

50% Power Reserves

3 Year Warranty

1. Description

2. Specification Quick Reference

The 1606-XLS240-UPSD uninterruptible power

supply (UPS) controller along with a standard 24V

power supply and one 12V battery can bridge power

failures or voltage fluctuations. This unit can supply

and bridge both a 24V load as well as a 12V load at

the same time. The 12V is generated by a DC/DC

converter from the 24V output. Therefore, systems that

use 24V control circuits and require 12V for e.g.

remote radio telemetry can be supplied with

only one 1606-XLS240-UPSD DC-UPS controller.

Input voltage

The DC-UPS includes a professional battery

management system which charges and monitors

the battery to achieve the longest battery service life

as well as many diagnostic functions that ensure a

reliable operation of the entire system.

24VDC

AC

24V

Power

Supply

DC-UPS

Dual

output

1606XLS240UPSD

24V

Load

12V

Load

e.g.: radio

transmitter

e.g.: PLC

Output voltage

(normal mode)

24Vdc

22.5-30Vdc

0.23V lower as

input voltage

12V

Nominal

Input range

Typ., 24V output

12V output

Output voltage

(buffer mode)

Output current

(normal mode)

Output current

(buffer mode)

22.25V

12V

0 - 15A

0 - 5A

0 - 10A

10 ¨C 15A for 5s

0 - 5A

Total output

360W

power

240W

Allowed batteries 3.9Ah to 40Ah

Temperature range -25 to +70¡ãC

Derating

6W/¡ãC

Dimensions

49x124x117mm

Buffer time

typ. 6¡¯30¡±

typ. 54¡¯

12VDC

24V output at 10A

12V output at 5A

24V output

12V output

24V output

24V output

12V output

Normal mode

Buffer mode

VRLA lead acid

Operational

+50 to +70¡ãC

WxHxD

7Ah battery module

24V 7A, 12V 5A

26Ah module

24V 7A, 12V 5A

12V Battery

3. Catalog Numbers

DC-UPS

1606-XLS240-UPSD

24V and 12V output

Accessories 1606-XLSBATASSY1 Battery module 12V 7Ah

1606-XLSBATBR1

Mounting kit w/o battery

1606-XLSBATASSY2 Battery module 12V 26Ah

1606-XLSBARBR2

Mounting kit w/o battery

1606-XLB

Panel/Wall mount bracket

2

4. Certification Marks

IND. CONT. EQ.

UL 508

Marine RINA

UL 60950-1

EMC, LVD

GOST R

All parameters are specified at an input voltage of 24V, 10A output load, 25¡ãC ambient and after a 5 minutes run-in time unless noted otherwise.

It is assumed that the input power source can deliver a sufficient output current.

Rockwell Automation Publication 1606-RM017A-EN-P ¡ª February 2014

C-TICK

Bulletin 1606 Switched Mode Power Supplies

Intended Use

? This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office,

communication, and instrumentation equipment.

? Do not use this power supply in aircraft, trains, nuclear equipment or similar systems where malfunction may cause severe personal injury or

threaten human life.

? This device is designed for use in hazardous (pending), non-hazardous, ordinary or unclassified locations.

All parameters are specified at an input voltage of 24V, 10A output load, 25¡ãC ambient and after a 5 minutes run-in time unless noted otherwise.

It is assumed that the input power source can deliver a sufficient output current.

Rockwell Automation Publication 1606-RM017A-EN-P ¡ª February 2014

3

Bulletin 1606 Switched Mode Power Supplies

5. Input

nom.

nom.

Input voltage

Input voltage ranges

DC 24V

22.5 to 30Vdc

30 to 35Vdc

35Vdc

0 to 22.5Vdc

Allowed input voltage ripple

max.

Allowed voltage between input

and earth (ground)

Turn-on voltage

max.

Input current **)

typ.

1.5Vpp

1Vpp

60Vdc or

42.4Vac

22.8Vdc

max.

typ.

typ.

23Vdc

140mA

1.1A

External capacitors on the input

Continuous operation, see Fig. 5-1

Temporarily allowed, no damage to the DC-UPS *)

Absolute maximum input voltage with no damage to the

DC-UPS

The DC-UPS switches into buffer mode and delivers

output voltage from the battery if the input was above

the turn-on level before and all other buffer conditions

are fulfilled.

Bandwidth ................
................