Revisions made to the original MasterSpec text are made solely by the Licensee and are not endorsed by, or representative of the opinions of, ARCOM or The American Institute of Architects (AIA). Neither AIA nor ARCOM are liable in any way for such revisions or for the use of this Product MasterSpec Section by any end user. A qualified design professional should review and edit the document to suit project requirements.

For more information, contact Avanti Systems, Inc., 200 Pemberwick Rd., Greenwich, CT 06831; Phone: (877) 282-6843; Fax: (914) 934-5992; Website: ; Email: sales@.

For information about MasterSpec, contact ARCOM at (800) 424-5080 or visit .

SECTION 084113 - ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS

TIPS:

To view non-printing Editor's Notes that provide guidance for editing, click on MasterWorks/Single-File Formatting/Toggle/Editor's Notes.

To read detailed research, technical information about products and materials, and coordination checklists, click on MasterWorks/Supporting Information.

Revise this Section by deleting and inserting text to meet Project-specific requirements.

1. RELATED DOCUMENTS

Retain or delete this article in all Sections of Project Manual.

A.

2. SUMMARY

A. Section Includes:

1. Storefront framing.

2. Manual-swing entrance doors.

3. PREINSTALLATION MEETINGS

Retain "Preinstallation Conference" Paragraph below if Work of this Section is extensive or complex enough to justify a conference.

A.

If needed, insert list of conference participants not mentioned in Section 013100 "Project Management and Coordination."

4.

A. Product Data: For each type of product.

1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes.

B. Sustainable Design Submittals:

"Product Data" Subparagraph below applies to LEED 2009 NC, CI, and CS; LEED v4; IgCC; ASHRAE 189.1; and Green Globes. Coordinate with requirements for sealants.

1.

"Laboratory Test Reports" Subparagraph below applies to LEED 2009, LEED v4, IgCC, ASHRAE 189.1, and Green Globes. Coordinate with requirements for sealants.

2.

"Product Certificates" Subparagraph below applies to LEED 2009, Materials and Resources Credit 5, "Regional Materials."

3.

"Product Certificates" Subparagraph below applies to LEED v4, Materials and Resources Credit "Building Product Disclosure and Optimization - Environmental Product Declarations, Option 2."

4.

"Product Certificates" Subparagraph below applies to ASHRAE 189.1, which requires that a minimum of 15 percent of building materials or products be extracted, harvested, manufactured, or recovered within 500 miles (800 km) of Project. See ASHRAE 189.1-2014, 9.4.1.2.

5.

Retain first three subparagraphs below to be eligible for LEED v4 credit. See the Evaluations.

6.

"Health Product Declaration" Subparagraph below applies to LEED v4 (all) MR Credit, "Building Product Disclosure and Optimization - Material Ingredients, Option 1 - Material Ingredient Reporting." Confirm with manufacturer that HPDs are available and meet requirements of the HPD Open Standard or approved USGBC program.

7.

"Sourcing of Raw Materials" Subparagraph below applies to LEED v4 (all) MR Credit, "Building Project Disclosure and Optimization - Sourcing of Raw Materials, Option 1 - Raw Material Source and Extraction Reporting." Confirm with manufacturer that corporate sustainability reports are available, have been prepared within the last year or are applicable to the year of production, and are by an organization approved by the USGBC.

8.

Subparagraphs below apply to Green Globes if products specified in the Section are used to meet the requirements of 3.5.2 "Interior Fit-out (including Finishes and Furnishings) - Path B," which requires that a certain percentage of the materials used in the interior fit-out have third-party certifications, and/or third-party life-cycle assessments.

9.

10. Third-Party Certified Life-Cycle Assessment: For each product.

C. Shop Drawings: For aluminum-framed entrances and storefronts. Include plans, elevations, sections, full-size details, and attachments to other work.

1. Include full-size details of each type of vertical-to-horizontal intersection of aluminum-framed entrances and storefronts, showing the following:

a. Joinery.

b. Anchorage.

c. Glazing.

2. Include point-to-point wiring diagrams showing the following:

a. Power requirements for each electrically operated door hardware.

b. Location and types of switches, signal device, conduit sizes, and number and size of wires.

Retain "Samples for Initial Selection" and "Samples for Verification" paragraphs below for two-stage Samples.

D.

E. Samples for Verification: For each type of exposed finish required, in manufacturer's standard sizes.

F. Entrance Door Hardware Schedule: Prepared by or under supervision of supplier, detailing fabrication and assembly of entrance door hardware, as well as procedures and diagrams. Coordinate final entrance door hardware schedule with doors, frames, and related work to ensure proper size, thickness, hand, function, and finish of entrance door hardware.

Retain "Delegated-Design Submittal" Paragraph below if design services have been delegated to Contractor.

G.

5. INFORMATIONAL SUBMITTALS

Coordinate "Qualification Data" Paragraph below with qualification requirements in Section 014000 "Quality Requirements" and as may be supplemented in "Quality Assurance" Article.

A.

B. Energy Performance Certificates: For aluminum-framed entrances and storefronts, accessories, and components, from manufacturer.

Retain "Quality-Control Program" Paragraph below if Project includes two-sided structural glazing. ASTM C 1401 recommends establishing a written quality-control program for fabrication, installation, and post-construction maintenance of structural-sealant-glazed storefronts.

C.

D. Source quality-control reports.

E. Sample Warranties: For warranties.

6. CLOSEOUT SUBMITTALS

A. Maintenance Data: For aluminum-framed entrances and storefronts to include in maintenance manuals.

7. QUALITY ASSURANCE

A. Installer Qualifications: An entity that employs installers and supervisors who are trained and approved by manufacturer.

B. Product Options: Information on Drawings and in Specifications establishes requirements for aesthetic effects and performance characteristics of assemblies. Aesthetic effects are indicated by dimensions, arrangements, alignment, and profiles of components and assemblies as they relate to sightlines, to one another, and to adjoining construction.

Retain subparagraph below or revise to suit Project.

1.

8. WARRANTY

When warranties are required, verify with Owner's counsel that warranties stated in this article are not less than remedies available to Owner under prevailing local laws.

A.

Verify available warranties and warranty periods for finishes.

1.

PRODUCTS

Manufacturers and products listed in SpecAgent and MasterWorks Paragraph Builder are neither recommended nor endorsed by the AIA or ARCOM. Before inserting names, verify that manufacturers and products listed there comply with requirements retained or revised in descriptions and are both available and suitable for the intended applications. For definitions of terms and requirements for Contractor's product selection, see Section 016000 "Product Requirements."

1.

A. Source Limitations: Obtain all components of aluminum-framed entrance and storefront system, and accessories, from single manufacturer.

2. PERFORMANCE REQUIREMENTS

A. Deflection of Framing Members:

Based on Project conditions, more stringent deflection criteria than specified in "Deflection Normal to Wall Plane" and "Deflection Parallel to Glazing Plane" subparagraphs below may be required; see "Seismic Performance" Article in the Evaluations. First option in "Deflection Normal to Wall Plane" Subparagraph is based on IBC requirements for framing members supporting glass. Second option is based on AAMA TIR-A11 recommendations.

1.

First option in "Deflection Parallel to Glazing Plane" Subparagraph below is based on typical deflection criteria for glass. Second option is based on GANA's "Glazing Manual."

2.

a. Operable Units: Provide a minimum 1/16-inch (1.6-mm) clearance between framing members and operable units.

3. STOREFRONT SYSTEMS

Retain "Basis-of-Design Product" Paragraph and list of manufacturers below to identify a specific product or a comparable product from manufacturers listed. Retain option(s) if manufacturer's name and model number are indicated on Drawings.

A.

1. DORMA USA, Inc.

2. Nana Wall Systems, Inc.

3. ................
................