MATERIAL SAFETY DATA SHEET - Pyrogen
MATERIAL SAFETY DATA SHEET
PYROGEN FIRE EXTINGUISHING AEROSOL GENERATOR
|1 IDENTIFICATION OF THE SUBSTANCE/PREPARATION AND COMPANY/UNDERTAKING |
PRODUCT NAME: PYROGEN EXA FIRE EXTINGUISHING AEROSOL GENERATOR
PRODUCT No: EXA-Z3; EXA-Z6; EXA-1; EXA-2; EXA-5; EXA-10R; EXA-10L; EXA-20; EXA-30; EXA-50
SUPPLIER: PYROGEN TECHNOLOGIES (AUST) PTY LTD
18 BARRY AVENUE
MORTDALE NSW 2223
AUSTRALIA
Tel: 61-2-95863200
Fax: 61-2-95863211
|2 COMPOSITION/INFORMATION ON INGREDIENTS |
Pyrogen fire extinguishing aerosol generator is a non-pressurized metal canister containing a solid aerosol-generating compound. Upon activation of the canister the aerosol-generating compound undergoes a chemical reaction to produce an aerosol, which is the actual extinguishing medium. Therefore, the Safety Data below refers to two compounds:
- aerosol-generating compound [contained inside Pyrogen fire extinguishing aerosol generator];
- aerosol [formed and released only upon activation of Pyrogen fire extinguishing aerosol generator]
|AEROSOL-GENERATING COMPOUND |AEROSOL |
| |(data refers to a maximum design application density of 100g/m3, which is 100 g |
| |of aerosol-generating compound combusted in a 1m3 sealed enclosure) |
|Ingredients |Chemical Entity |CAS-No |Content |Ingredients |Chemical |CAS-No |Content |
| | | | | |Entity | | |
|Sucrose |C12H22O 11 |57-50-1 |20-25% |Nitrogen |N2 |17778-88-0 | |
|Melamine |C3H6N6 |108-78-1 |5-10% |Water vapour |H2O | |60.4mg/m3 |
|Magnesium Stearate |C36H70MgO4 |557-04-0 |1-2% |Carbon dioxide |CO2 |124-38-9 |1350mg/m3 |
| | | | |Carbon monoxide |CO |630-08-0 |1.63mg/m3 |
| | | | |Nitrogen oxides |NOx | |10.51mg/m3 |
| | | | |Ammonium |NH3 |7664-41-7 |2.83mg/m3 |
| | | | |Sulfur dioxide |SO2 |7446-09-5 |0.036mg/m3 |
| | | | |Hydrogen cyanide |HCN |74-90-8 |ND ((0.05)mg |
|3 HAZARD IDENTIFICATION |
|AEROSOL GENERATOR |AEROSOL-GENERATING COMPOUND |AEROSOL |
|Application of electric current causes activation |Flammable |Elevated temperatures on release |
|Heating above 300(C may cause activation |When combusted produces aerosol fire extinguishing |High obscuration on release |
| |agent. Does not displace oxygen. Stops combustion and | |
| |flame front | |
|Upon activation releases aerosol at the elevated | |Irritating to eyes and respiratory tracks |
|temperatures | | |
| | |Contains minor quantities of potentially toxic |
| | |by-products of combustion of the aerosol-generating |
| | |compound CO2 NOx |
|Hot surface upon activation | | |
|Propels upon activation if unsecured | | |
|4 FIRST-AID MEASURES |
|INTAKE/CONTACT |AEROSOL-GENERATING COMPOUND |AEROSOL |
|INHALATION |N/A |Remove to fresh air, lie down, and rest. If not |
| | |breathing - apply artificial respiration. Oxygen |
| | |may be given but only under supervision of a |
| | |trained person. Keep warm and transport to hospital|
| | |or doctor. |
|INGESTION |Give water and induce vomiting. |N/A |
|SKIN CONTACT |Wash affected areas with water. |Wash affected areas with water. |
|EYE CONTACT |N/A |Hold eyes open and wash continuously with water for|
| | |at least 15 minutes. |
|BURNS |Treat affected areas with cold water. If required |Treat affected areas with cold water. If required |
| |seek medical attention. |seek medical attention. |
|5 FIRE-FIGHTING MEASURES |
|GENERATOR |AEROSOL-GENERATING COMPOUND |AEROSOL |
|Activates upon application of electric current or |Flammable. Ignites when in contact with heat above |Extinguishing medium. Does not represent a fire |
|heat above 300(C or continued exposure naked flame. |300(C or naked flame. Able to burn without air. Upon |hazard. Generator / Extinguisher is not pressurized |
|Produces fire extinguishing aerosol upon activation.|ignition produces extinguishing aerosol. If amount of | |
| |aerosol is insufficient under given conditions and | |
| |fire gets out of control, use water fog or spray, | |
| |carbon dioxide, dry powder or foam. Wear respirator | |
| |and fire protective clothing. Withdraw all personnel | |
| |from the area and warn against entry. | |
|6 ACCIDENTAL RELEASE MEASURES |
|GENERATOR |AEROSOL-GENERATING COMPOUND |AEROSOL |
| | | |
|UNINTENDED ACTIVATION: |SPILLS: |AEROSOL RESIDUE: |
|Clear the area of all personnel. Do not re-enter |No smoking or naked flame. Clear the area of all |Can be brushed, blown or washed away. Can be |
|until the area has been fully ventilated. Wear a |personnel. Do not walk on material. Keep combustibles |disposed of into general sewage. |
|respirator in case immediate re-entry is necessary. |such as wood, paper, oil and etc away from spilled | |
|Follow clean up procedure for aerosol. |material. Wearing protective gloves absorb small | |
| |spills with sand or other non-combustible material for| |
| |later disposal, then, if practicable, hose the area | |
| |with water. Disposal is in accordance with the | |
| |National Regulations for flammable materials. | |
|7 HANDLING AND STORAGE |
Keep generators in ventilated stores at normal ambient temperatures away from heaters and direct sunlight. If kept in quantities exceeding 1,000 kg shall be stored in a depot constructed of a non-combustible material.
|8 EXPOSURE CONTROLS/PERSONAL PROTECTION |
|AEROSOL |
|(data refers to a maximum design application density of 100g/m3, which is 100 g of aerosol-generating compound combusted in a 1m3 sealed enclosure) |
|Potentially hazardous ingredients |
|PARAMETER |AEROSOL-GENERATING COMPOUND |AEROSOL |
|APPEARANCE |Whitish solid mixture |Smoke-like whitish mixture of micron-sized solids and|
| | |gases |
|ODOUR |No specific odour |Characteristic of combustion products |
|DENSITY |1.7 g/cm3 |1.29 g/cm3 |
|MELTING BOILT |N/A |N/A |
|IGNITION TEMPERATURE |180(C |N/A |
|FLASH POINT |300(C |N/A |
|SOLUBILITY |Insoluble in water, reacts with organic solvents, such|Soluble in water |
| |as acetone | |
|10 STABILITYAND REACTIVITY |
|PARAMETER |AEROSOL-GENERATING COMPOUND |
|STABILITY |Stable under normal temperature conditions. |
|CONDITIONS TO AVOID |Avoid heat, flames and other sources of ignition. Avoid contact with organic solvents. |
|HAZARDOUS DECOMPOSITION PRODUCTS |When combusted produces potentially hazardous carbon monoxide CO and nitrogen oxides NOx. ................
................
In order to avoid copyright disputes, this page is only a partial summary.
To fulfill the demand for quickly locating and searching documents.
It is intelligent file search solution for home and business.
Related searches
- world population data sheet 2018
- excel data sheet sample
- baking soda safety data sheet
- product data sheet template
- product data sheet examples
- free safety data sheet posters
- hydrogen peroxide safety data sheet
- sodium carbonate safety data sheet
- na2co3 safety data sheet
- ghs safety data sheet example
- global harmonization safety data sheet
- acrylic safety data sheet