Section 23 09 11 - INSTRUMENTATION AND CONTROL FOR BOILER ...

g.The steam header pressure transmitter(s) shall be dedicated to header pressure control. Suppressed range transmitter(s), each with range +/- 20 percent of required set point. If two set points are required that are more than 138 kPa (20 psi) apart, provide two transmitters. Locate transmitters adjacent to main steam header. ................
................