SECTION 263213 - PACKAGED ENGINE GENERATOR

The diesel-fuel, engine-generator set shall be rated for continuous standby service (defined as meeting NEMA MG 1 continuous temperature rise ratings for the duration of any power outage) at not less than the specified kW/kVA at 0.80 power factor. The generator shall be rated to operate at [480Y/277][208/120] Volts, three-phase, four-wire, wye ... ................
................