ACS550 SINGLE PHASE DE-RATE OPERATION - ABB
[Pages:2]ACS550 SINGLE PHASE DE-RATE OPERATION
Description:
Single phase operation of VFD's is a common request from OEM's in in many industries including food and exercise. While the ACS355 offers UL Listed single phase products up to 3Hp at 230 volt larger ratings will require use of the ACS550.
Process for De-Rating an ACS550:
The ACS550 can be de-rated for operation when single phase 230 volt is applied. As with any single phase 230 volt input the output is 3 phase 230 volt with 50% reduction in current. All drive parameters are factory set to operate with three phase input power. As such, the drives output current limit must be adjusted based on the de-rate. In order to achieve the 50% derated output current the input single phase power from the utility must be stiff. There will be some DC bus ripple if the input power quality is questionable or if the drive is operated at an output current rating above the 50% de-rate. Continuous operation above the 50% de-rate will cause nuisance DC overvoltage faults or phase loss faults due to excessive DC Ripple.. .
Documents or other reference material:
ACS550 Single Phase Current De-Rate
Code Type ACS550-U1-04A6-2
ACS550-U1-06A6-2 ACS550-U1-07A5-2 ACS550-U1-012A-2 ACS550-U1-017A-2 ACS550-U1-024A-2 ACS550-U1-031A-2 ACS550-U1-046A-2 ACS550-U1-059A-2 ACS550-U1-088A-2 ACS550-U1-114A-2 ACS550-U1-143A-2 ACS550-U1-178A-2 ACS550-U1-221A-2 ACS550-U1-248A-2
Frame R1 R1 R1 R1 R1 R2 R2 R3 R3 R4 R4 R6 R6 R6 R6
I2N A 2.3 3.2 4.2 6.0 6.8 9.6 15.2 22.0 28.0 44.0 57.0 70.1 68.0 110.5 124.0
Author: Jon Radde Regional Application Engineer External . Industry ? Industrial
Product Categories: ACS550
Date: 08/12/2014 Document #: LVD-EOTN71U-EN Revision: A
Corrective Actions:
The ACS550 can be operated using a 230 volt single phase input. The input power leads should be connected on U1 and W1. The application must reviewed so the drive is correctly sized for the load and output current listed in the above table. If there is an issue of DC bus ripple, Bus Stabilization may need to be adjusted. If this is case, contact your RAE for assistance.
Author: Jon Radde Regional Application Engineer External . Industry ? Industrial
Product Categories: ACS550
Date: 08/12/2014 Document #: LVD-EOTN71U-EN Revision: A
................
................
In order to avoid copyright disputes, this page is only a partial summary.
To fulfill the demand for quickly locating and searching documents.
It is intelligent file search solution for home and business.
Related download
- voltage tolerance boundary pacific gas and electric company
- instruction sheet for 208 230 460v conversion i3detroit
- using outback inverters for 3 phase 480v applications
- acs550 single phase de rate operation abb
- installation instructions and operation manual cornell iron
- motor circuit protection tables eaton
- electrical service types and voltages continental control systems llc
- 3 phase power what s the point phase changer
- 400v 60hz ups power piller
- power cable splicing and terminating guide dds
Related searches
- 480 240 single phase transformer
- single phase 480v
- 480 volt single phase transformer
- 480v single phase transformer
- 480 volt single phase wiring
- 3 phase single phase wiring
- single phase 208 vs 3 phase 208
- single phase to 3 phase inverter
- single phase to three phase converter
- single phase to three phase converters
- three phase to single phase converter
- single phase to 3 phase converters