BASIC NEC CODE RULES AND DESIGN PRACTICE
Load: Unit Heater 10 KW, 230V, 3 phase, find I, wire size, circuit breaker size. Conduit Size. I = 10 KW = 25.1 Amp .23 KV (3. Wire Size- 25.1A = 31.3 Amp.8 NEC 310-16 Use #8 good for 45 amp, 3 #8 + 1 #8 ground in 1" RGC Table 3A . Circuit Breaker = 25.1A = 31.3 Amp so use 35A.8 Conduit Size if different size wires are used ................
................
To fulfill the demand for quickly locating and searching documents.
It is intelligent file search solution for home and business.
Related searches
- basic java code examples
- system analysis and design documentation
- systems analysis and design ebook
- system analysis and design 10th edition pdf
- modern systems analysis and design pdf
- systems analysis and design textbook
- system analysis and design pdf
- system analysis and design notes
- organizational structure and design pdf
- computer architecture and design pdf
- methodology and design research samples
- organization structure and design ppt