Power Supply - 24V, 10 A, 240 W, Three-phase Input ...

Reference Manual

Original Instructions

Power Supply - 24V, 10 A, 240 W, Three-phase Input

Catalog Number 1606-XLE240E-3

Important User Information

Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.

If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

Labels may also be on or inside the equipment to provide specific precautions.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.

ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).

Table of Contents

Additional Resources

Terminology and Abbreviations

Power Supply - 24V, 10 A, 240 W, Three-phase Input

Topic Additional Resources Terminology and Abbreviations

Product Overview Installation Notes AC Input DC Input Input Inrush Current DC Output Hold-up Time Efficiency and Power Loss Functional Diagram Front Side and User Elements

Page Topic

Page

3

Connection Terminals

14

3

Lifetime Expectancy and Mean Time between 15

Failure

4

EMC

16

6

Environment

17

8

Protection Features

18

9

Safety Features

18

9

Dielectric Strength

19

10

Standards Compliance and Approvals

20

11

Approximate Dimensions and Weight

21

12

Accessories

22

13

Application Notes

23

13

These documents contain additional information concerning related products from Rockwell Automation.

Resource

1606-XL Power Supply Technical Data, publication 1606-TD001

Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1

Product Certifications website,rok.auto/certifications

Description

Provides specifications and certifications for the 1606-XL240E-3 power supply.

Provides general guidelines for installing a Rockwell Automation? industrial system.

Provides declarations of conformity, certificates, and other certification details.

You can view or download publications at . To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.

Term PE and symbol Earth, Ground 4000V AC

50 Hz vs. 60 Hz

Definition

PE is the abbreviation for Protective Earth and has the same meaning as the symbol.

This document uses the term`earth'which is the same as the U.S. term`ground.'

A figure with the unit (V AC) at the end is a momentary figure without any additional tolerances included.

As long as not otherwise stated, AC 100V and AC 230V parameters are valid at 50 Hz mains frequency. AC 120V parameters are valid for 60 Hz mains frequency.

Rockwell Automation Publication 1606-RM002A-EN-P - March 2019

3

Power Supply - 24V, 10 A, 240 W, Three-phase Input

Product Overview

The 1606 Essential line are cost optimized power supplies without compromising quality, reliability, and performance. The most outstanding features of 1606-XLE240E-3 are the high-efficiency, electronic inrush-current limitation, active input-transient filter, and wide-operational temperature range. The small size is achieved by a synchronous rectification and further technological design details.

The 1606-XLE240E-3 is equipped with conformal coated circuit-boards that are preferred for applications in harsh areas.

The 1606 Essential line includes all essential basic functions. The devices have a power reserve of 20% included, which may even be used continuously at temperatures up to 45 ?C (113 ?F). Additionally, the 1606-XLE240E-3 can deliver three times the nominal output current for 10 ms which helps to trip fuses on faulty output branches.

The power supply features: ? 3x 380...480V AC wide-range input ? 2 or 3-phase operation possible ? Width only 62 mm (0.039 in.) ? Efficiency up to 92.9% due to synchronous rectifier ? Excellent partial load efficiency ? 20% output power reserves ? Easy fuse tripping due to high overload current ? Input-transient blanking circuit included ? Minimal inrush current surge ? Three input fuses included ? Current sharing feature for parallel use ? Full power between -25 ?C...+60 ?C (-13 ?F...+140 ?F)

4

Rockwell Automation Publication 1606-RM002A-EN-P - March 2019

Power Supply - 24V, 10 A, 240 W, Three-phase Input

Attribute Output voltage Adjustment range Output current

Input voltage AC Mains frequency Input current AC Power factor AC inrush current Efficiency Losses Hold-up time Temperature range Size (W x H x D)

Weight

Figure 1 - Main Approvals

Description 24V DC 24...28V 12.0...10.3 A 10.0...8.6 A 7.5...6.5 A

3x 380...480V AC 50...60 Hz 0.7/0.6 A 0.53/0.52 A 4/4 Apk 92.8/92.9% 18.6/18.3 W 34/54 ms

-25...+70 ?C(-13...+158 ?F)

62 x 124 x 117 mm (2.44 x 4.88 x 4.60 in.) 750 g (1.65 lb)

Nominal Factory setting 24.1V

Below 45 ?C (113 ?F) ambient 60 ?C(140 ?F) ambient 70 ?C(158 ?F) ambient Derate linearly between 45...70 ?C (113...158 ?F)

-15%/+20% ?6% 3x 400/480V 3x 400/480V

3x 400/480V

3x 400/480V 3x 400/480V

3x 400/480V

?

Without DIN rail

Without DIN rail

IND. CONT. EQ.

UL 60950-1

See page 20 for a complete list of approvals.

Rockwell Automation Publication 1606-RM002A-EN-P - March 2019

5

................
................

In order to avoid copyright disputes, this page is only a partial summary.

Google Online Preview   Download