Calculate the maximum allowable amp load for the fuse / breaker. For motors with SF 1.15 or higher, multiply FLA by 140%. For motors with SF less than 1.15, multiply FLA by 130%. Compare this amp value with the standard amp ratings in NEC 240.6; if the calculated amp value is not a standard size, decrease to the next smaller standard fuse size. ................
................