Multimeter 560CVD03 - ABB
[Pages:6]RTU560
Data Sheet Multimeter 560CVD03
Multimeter 560CVD03
Without LCD Display
There are several versions available:
Type Displa y
L O H I 1 A 5 A
Figure 1 With LCD Display
Versions 560 CVD 03 R0031 560 CVD 03 R0035 560 CVD 03 R0051 560 CVD 03 R0055
560 CVD 03 R0021 560 CVD 03 R0025 560 CVD 03 R0041 560 CVD 03 R0045
3U3I 3U3I 3U3I 3U3I 3U3I 3U3I 3U3I 3U3I
x x
x
x x
x
x
x x
x
x
x
x
x
x
x
x x
x
x
Figure 2
Application
The Multimeter 560CVD03 is used for monitoring input signals from three independent phases with 3 or 4 wire connections. For each phase voltage, current and power are measured directly, and a number of other parameters derived from these in software. The results are transmitted to the RTU560.
Power Measuring Display
It automatically changes the screen of measurement page, and each screen display for six seconds.
If you change it to button push mode, each screen will automatically display for 240 seconds. The scroll mode can be set up by RTUtil560
Characteristics
The Multimeter is a microprocessor-based Intelligent Electronic Device (IED) intended for current, voltage, power and energy measurement. Derived parameters are calculated once in 500ms then scaled by user programmed constants for current and voltage transformers. Current and voltage inputs of the 560CVD03 are connected via adequate transformer only (see Figure 3 and 4). The Multimeters are designed for montage on DIN rails 35mm.
Doc-No.: 1KGT 150 788 V001 1
1
RTU560
Data Sheet Multimeter 560CVD03
Meter Operation
The following metered parameters are available
Instantaneous Meter Values
Measured by true RMS conversion and transmission to the RTU560 of following values
Measurement
Measuring Path
Voltage
Phase 1-N, 2-N, 3-N
Voltage
Phase 1-2, 2-3, 1-3
Current
Phase 1, 2, 3
Active Power
Phase 1, 2, 3,
Reactive Power
Phase 1, 2, 3,
Apparent Power
Phase 1, 2, 3,
Power Factor (PF) Phase 1, 2, 3,
Frequency
System
Phase rotation
Positive/Negative sequence
Figure 3: Example 3-phase 3 wire connection
Derived Meter Values
Calculation of accumulated values (intermediate and end of period readings) for
x active energy (positive, inductive) x active energy (negative, capacitive) x reactive energy (positive, inductive) x reactive energy (negative, capacitive)
Voltage / Current Distortion (THD)
The 560CVD03 provides a measure of the distortion, in each phase voltage and current waveform, as a percentage deviation from pure 50Hz or 60Hz sine waves by Fast Fourier Transform algorithm (FFT).
x U1, U2, U3 % THD
x I1, I2, I3 % THD
Figure 4: Example 3-phase 4 wire connection
2
Doc.-No.: 1KGT 150 788 V001 1
RTU560
Data Sheet Multimeter 560CVD03
Technical Data
In addition to the RTU560 general technical data, the following applies:
Input Channels
85-400 V AC
Voltage U1, U2, U3
3 Phase, 3 or 4 Wire Load: < 0.3 VA per phase Measurement range 0.2% to
120%
R0021, R0031, R0041
R0051: 1 A,
Current I1, I2, I3 R0025, R0035, R0045,
R0055: 5 A,
Load: < 0.3 VA per phase
Frequency
45...65Hz
Samples Harmonics
32 samples/cycle Up to 15th harmonic for 50/60Hz
Accuracy
Phase I
0.2% System W 0.5%
Neutral I
0.2% System VA 0.5%
Phase U
0.2% System var 0.5%
Ph-Ph U
0.2% System PF ?0.2?
Phase W
?0.05 0.5% Frequency
Hz
Phase VA
0.5% %THD I
?0.5%
Phase var
0.5% %THD U ?0.5%
Phase PF
?0.5% Timebase 100ppm
12
bits + A/D converter
sign
bit
Power Supply voltage
Power Supply Voltage (LO)
Power Supply Voltage (HI)
24/48 V DC ?15% 85 ...265 V AC / DC
Power Consumption
3 VA AC 2W DC
Mechanical Layout
Width
87.5 mm
Height
72 mm
Depth
59 mm
Enclosure Din rail type / bottom mount type
Connection Type
Wiring
Screw Terminal
connection type.
Serial Ports
Modbus RTU Protocol
RS485
Diagnostic Port RS232
Baud Rate (same for RS232 and RS485)
Always configure to 19.2k bps
Load
Up to 32 devices
Test Voltage
Dielectric Strength IEC 255-5
2kV AC rms, 1 minute
Doc-No.: 1KGT 150 788 V001 1
3
RTU560
Data Sheet Multimeter 560CVD03
Stability
Stability
max. 100ppm/?C (Temperature range -10 to +50?C)
Environmental Conditions
Operating Temperature
Storage Temperature Relative humidity
-25 to +70 ?C Start up at -40?C Temp. cycle +85?C for 8 hours
-40 to +80 ?C
10 ... 95 % non condensing
Immunity Test
ANSI / IEEE C37.90.1-1989
3 kV SWC
IEC 61000-4-12
Class III SWC
Fast Transient / Burst Class IV SWC IEC 61000-4-4
Surge Immunity Test Class IV Impulse IEC 61000-4-5
Ordering Information
560 CVD03 R0021 1KGT 028 000 R0021 In = 1A, 3 voltage, 3 current, Version LO 560 CVD03 R0031 1KGT 028 000 R0031 In = 1A, 3 voltage, 3 current, Version LO, Display 560 CVD03 R0041 1KGT 028 000 R0041 In = 1A, 3 voltage, 3 current, Version HI 560 CVD03 R0051 1KGT 028 000 R0051 In = 1A, 3 voltage, 3 current, Version HI, Display 560 CVD03 R0025 1KGT 028 000 R0025 In = 5A, 3 voltage, 3 current, Version LO 560 CVD03 R0035 1KGT 028 000 R0035 In = 5A, 3 voltage, 3 current, Version LO, Display 560 CVD03 R0045 1KGT 028 000 R0045 In = 5A, 3 voltage, 3 current, Version HI 560 CVD03 R0055 1KGT 028 000 R0055 In = 5A, 3 voltage, 3 current, Version HI, Display Configuration kit 1KGT 030 800 R0001 560KCA01 R0001 (Tool CD, cable)
4
Doc.-No.: 1KGT 150 788 V001 1
RTU560
Data Sheet Multimeter 560CVD03
Doc-No.: 1KGT 150 788 V001 1
5
RTU560
Data Sheet Multimeter 560CVD03
Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.
We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents - in whole or in parts ?is forbidden without prior written consent of ABB AG.
Copyright? 2012 ABB All rights reserved
6
Doc.-No.: 1KGT 150 788 V001 1
................
................
In order to avoid copyright disputes, this page is only a partial summary.
To fulfill the demand for quickly locating and searching documents.
It is intelligent file search solution for home and business.
Related download
- current transformer model 560
- september 29 2020 purdue university
- advanced subsidiary gce physics a g482 oxford cambridge and rsa
- chapter 16 problem 1 university of nevada las vegas
- national electrical code allowable ampacities of insulated conductors
- 18 06 problem set 3 solution massachusetts institute of technology
- multimeter 560cvd03 abb
- cisco ncs 560 series routers interface modules data sheet
- series 560 9xxxx and 5400 6xxxx swr autotesters operation and
- technical brief ind560 mettler toledo