Kidde Fire Systems System Component Datasheet

Kidde Fire Systems System Component Datasheet

Pressure Operated Switch

FEATURES ? For Approvals, see the "COMPATIBILITY" table on page 2. P/N: 81-486536-000

Effective: December 2018 K-85-0524 Rev AB

OPERATED SET

OPERATED SET

STEM SHOWN IN SET POSITIONPULL UP ON STEM TO MANUALLY OPERATE SWITCH

4.00"

WIRING SCREW TERMINALS

PRESSURE OPERATED SWITCH 3P.D.T.

TO RESET PUSH STEM TO SET POSITION 15 AMP.-- 125 V.AC UL 10 AMP.--250 V.AC

3/4HP--250 VAC PT. NO. 486536

FM

KIDDE-FENWAL, INC. 400 MAIN STREET ASHLAND, MA 01721

0.375" 8 COVER SCREWS

TO RESET PUSH STEM TO SET POSITION

4.00" FRONT VIEW COVER REMOVED

SWITCH 3PDT COVER

15 AMP 125 VAC 10 AMP 250 VAC 3/4 HP 1-2-3 PH 125-480 VAC

FRONT VIEW

BOX 3 EACH SIDE 1/2" CONDUIT KNOCKOUTS

1/2" SUPPLY PIPE WITH UNION

OPERATED

SET

NC

NC

NC

C

C

C

NO

NO

NO

GASKET SIDE SECTION

?" NPT FEMALE, CONNECT TO SYSTEM PIPING

PRESSURE INLET WIRING DIAGRAM

Notes:

? The switch may be mounted in any position, however, the preferred installation is upright, as shown. ? Any load connection to the switch must not exceed the switch rating, and shall utilize a suitable protection device

(i.e., circuit breaker, fuse) ? Contact Ratings (3 PDT)

? 15 Amp @ 125 Vac ? 10 Amp @ 250 Vac ? 3/4 HP @ 250 Vac ? 1, 2, or 3 Phase

1

COMPATIBILITY Series

Kidde? ECS-500TM System Kidde? ECS-500TM Marine System Kidde? ECSTM with 3MTM NovecTM 1230 Fire Protection Fluid Kidde? ADSTM with 3MTM NovecTM 1230 Fire Protection Fluid Kidde? ECSTM Marine with 3MTM NovecTM 1230 Fire Protection Fluid Kidde? ADSTM Marine with 3MTM NovecTM 1230 Fire Protection Fluid Kidde? ECSTM with HFC-227ea Agent Kidde? Modular ECSTM with HFC-227ea Agent Kidde? ECSTM Marine with HFC-227ea Agent Kidde? ADSTM Marine with HFC-227ea Agent Kidde? ADSTM with HFC-227ea Agent Kidde? FE-13TM Engineered Suppression System Kidde Fire Systems Marine Carbon Dioxide Version 2.4 DIOM Kidde? High Pressure CO2

DIOM P/N 06-237585-001 06-237589-001 06-236553-001 06-237256-001 06-236559-001 06-237257-001 06-236115-001 06-236116-001 06-236225-001 06-236595-001 06-236068-001 06-236169-002

220610 81-CO2MAN-001

Approvals UL, ULC, FM UL, ULC, USCG UL, ULC, FM UL, ULC, FM UL, ULC, USCG UL, ULC, USCG UL, ULC, FM UL, ULC, FM

UL, USCG UL, ULC, USCG

UL, ULC, FM UL

UL, USCG UL, ULC, FM

KIDDE is a registered trademark of Kidde-Fenwal, Inc., or its parents, subsidiaries or affiliates.

EXPORT INFORMATION (USA) Jurisdiction: EAR

Classification: EAR99 This document contains technical data subject to the EAR.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. believes this data to be accurate, but it is published and presented without any guarantee or warranty whatsoever. KIDDE-FENWAL, INC. assumes no responsibility for the product's suitability for a particular application. Product features specified are only applicable when the fire suppression system is correctly designed, installed, maintained and serviced by trained, authorized Kidde Fire Systems distributors as per the applicable design, installation, operation, and maintenance manuals. If you need more information on this product, or if you have a particular problem or question, contact: KIDDE-FENWAL, INC., Ashland, MA 01721 USA, Telephone: (508) 881-2000.

2

K-85-0524 Rev AB ?2018 Kidde-Fenwal, Inc.

Kidde Fire Systems 400 Main Street

Ashland, MA 01721 Ph: 508.881.2000 Fax: 508.881.8920



................
................