ASPEED AST1300AST2300 graphic only support basic 2D ...



Advantech AE Technical Share Document

|Date |2015 / 04 / 07 |SR# | |

|Category |□ FAQ■ SOP |Related OS |Win7/ WinXP |

|Abstract |Connection Guide of Panel Express for S7-1500 Ethernet |

|Keyword |WOP/ WebOP/ Siemens/ S7-1500/ Panel Express |

|Related Product |Panel Express/ WOP-2000V Series/ WOP-2000T Series |

■ Problem Description:

This connection guide introduces how to connect Siemens S7-1500 with WebOP HMI. User can set the communication setup in TCP/IP and it can connect Siemens S7-1500 with WebOP HMI.

Note: this document could also be adapted with WOP-2000V/WOP-2000T Series.

System Architecture:

[pic]

Hardware:

HMI

[pic]

|Manufacturing Company |Order number |Description |

|Advantech |PE-TPC1251-01NA01K |COMPUTER SYSTEM, TPC-1251T w/PE 1500 Tag, CFast 32Gb, WES7Pro |

|Advantech |PE-TPC1551-01NA01K |COMPUTER SYSTEM, TPC-1551T w/PE 1500 Tag, CFast 32Gb, WES7Pro |

PLC

[pic]

|Manufacturing Company |Order number | |

|SIEMENS |S7-1500 CPU 1516-3 PN/DP | |

■ Brief Solution - Step by Step:

S7-1500 PLC setting

1. Create a new project:

[pic]

2. Add a new device: SIMATC S7-1500 CPU 1516-3 PN/DP

[pic]

3. In PLC_1 [CPU1516-3 PN/DP], choose properties.

Please confirm 2 points setting:

[pic]

[pic]

[pic]

4. Create a new data block:

a. chooses “Add new block”

[pic]

b. choose “Data block”:

[pic]

c. Set the “Name”: DBW0, and set “Data type”: Array [0..10] of Int.

[pic]

[pic]

d-1. Choose Data_block_1 [DB1] properties:

[pic]

d-2. Choose “Attributes”(optimized block access cancel [pic]

[pic]

[pic]

5. Extended download to device(Load

[pic]

Continue without synchronization

[pic]

“No action” change to “Re-initialize”.

[pic]

[pic]

Program is load to CPU

[pic]

6. Hardware setting: setting(Date & Time(General

(General remember change date data)

[pic] [pic] [pic]

WebOP Designer General setting:

Link Type: Direct Link (Ethernet)

Device/Server: Siemens AG/ SIMATIC S7 (Ethernet)

[pic]

Setting Parameter: IP Address(192.168.1.1(same the S7-1500 X2 port)

[pic]

Setting Numeric Entry: DB1.DBW0~DB1.DBW9

[pic]

Monitor Data_block_1 data & started Panel Express runtime:

[pic]

[pic]

[pic]

■ Reference:

N/A

................
................

In order to avoid copyright disputes, this page is only a partial summary.