SECTION 01100 - SUMMARY



Hyannis Golf Club,

First Floor Toilet Refurbishment

Rt. 132 1280 Iyannough Rd.

Hyannis, MA 02601

TECHNICAL SPECIFICATIONS

GENERAL

1. SUMMARY OF WORK

A. Project: Hyannis Golf Club, 1680 Iyannough Rd, Rt 132, Hyannis, MA 02601

B. Owner: Town of Barnstable, 367 Main St, Hyannis MA 02601

C. The Work consists of the refurbishment and renovation of the existing first floor rest rooms at the Hyannis Golf Club originally built in the mid 80's. The work includes enlarging the toilet rooms to include handicapped accessible rest rooms. New partitions and doors, new vanities with granite counter tops, flooring and painting throughout. The toilet count will increase with the installation of new toilets, urinals and plumbing modifications. Repaired ceiling and lighting with supply and exhaust HVAC system changes.

D. The work will be carried out in two phases, Phase 1 maintain the existing Female Toilet and build the new Female Toilet; Phase 2 to then build the Male Toilet.

2. WORK RESTRICTIONS

A. Contractor's Use of Premises: During construction, Contractor will have limited use of site and building. Contractor's use of premises is limited only by Owner's right to perform work or employ other contractors on portions of Project.

Subparagraph below contains an example of limitations on Contractor's use of premises; delete if not applicable. Insert other descriptions of areas or types of limited use, requirements for cooperation with Owner's personnel, noninterference with Owner's or public use, and other necessary restrictions if required.

1.

B. The Building must remain able to operate as a Golf Club and Function facility at all times throughout construction. Signage will be required directing guests to the Basement locker room toilet facilities during construction.

END OF SECTION 01100

Copyright 2003 by The American Institute of Architects (AIA)

GENERAL

3. ALTERNATES

A. An alternate is an amount proposed by bidder for certain work that may be added to or deducted from the Base Bid amount if Owner accepts the Alternate. The cost or credit for each alternate is the net addition to or deduction from the Contract Sum to incorporate the Alternate into the Work. No other adjustments are made to the Contract Sum.

B. Indicate on the Bid Form amounts to be deducted from or added to the Contract Sum for the following alternates:

1. Add: Alternate Number 1: Remove Existing door and replace with New 3' x 6'8" half glazed wood panel door to Function Room

2. Add: Alternate Number 2: Add 2# Awning Windows to match existing,

3. Add: Alternate Number 3: Baby changing station to wall in female disabled stall.

PRODUCTS (Not Applicable)

EXECUTION (Not Applicable)

END OF SECTION 01200

Copyright 2003 by The American Institute of Architects (AIA)

GENERAL

1. SECTION REQUIREMENTS

A. Use Charges: Cost or use charges for temporary facilities shall be included in the Contract Sum. Any special connections required by the contractor will be at the contractors expense and must be removed at the end of the project.

First paragraph below assume services are available and Owner will permit tapping into existing system without charge.

B.

C. Temporary Electrical Service: Comply with NEMA, NECA, and UL standards and regulations for temporary electric service. Install service to comply with NFPA 70.

PRODUCTS

1. EQUIPMENT

A. Heating Equipment: The use of the permanent heating system, will be allowed.

Usually retain first subparagraph below. Gasoline-burning and salamander-type heating units are usually prohibited.

1. TEMPORARY UTILITIES

A. General: Arrange with utility company, Owner, and existing users for time when service can be interrupted, if necessary, to make connections for services.

Select paragraph above or first paragraph below.

B.

C. Provide temporary lighting with local switching that provides adequate illumination for construction operations, observations, inspections, and traffic conditions.

2. TEMPORARY SUPPORT FACILITIES

A. Provide field offices, storage and fabrication sheds, and other support facilities as necessary for construction operations. Any use of Owners facilities must be left in the condition in which it was found.

B. Provide waste-collection containers in sizes adequate to handle waste from construction operations. Collect waste daily and, when containers are full, legally dispose of waste off-site. Comply with requirements of authorities having jurisdiction.

C. Install project identification and Directional signs in locations approved by owner to inform the public and persons seeking entrance to Project or to other rooms.

3. TEMPORARY SECURITY AND PROTECTION FACILITIES

A. Provide temporary environmental protection, operate temporary facilities, and conduct construction in ways and by methods that comply with environmental regulations and that minimize possible air, waterway, and subsoil contamination or pollution or other undesirable effects. Exclusive use of a section of the Golf Club Parking Lot will be provided for the contractor.

B. Provide temporary enclosures for protection of construction and workers from inclement weather and for containment of heat.

C. Provide floor-to-ceiling dustproof partitions to limit dust and dirt migration and to separate areas occupied by neighbors and stored materials from fumes and noise.

D. Comply with requirements of authorities having jurisdiction for erecting structurally adequate barricades, including warning signs and lighting.

E. Furnish and install site enclosure fence in a manner that will prevent people and animals from easily entering site except by entrance gates, around any stored materials or facilities in an approved area of the parking lot.

F. Install and maintain temporary fire-protection facilities. Comply with NFPA 241.

END OF SECTION 01500

Copyright 2003 by The American Institute of Architects (AIA)

GENERAL

1. SECTION REQUIREMENTS

A. The term "product" includes the terms "material," "equipment," "system," and terms of similar intent.

B. Product Substitutions: Substitutions include changes in products, materials, equipment, and methods of construction from those required by the Contract Documents and proposed by Contractor after award of the Contract.

1. Submit 3 copies of each request for product substitution.

2. Submit requests within 7 days after the Notice to Proceed.

3. Do not submit unapproved substitutions on Shop Drawings or other submittals.

4. Identify product to be replaced and show compliance with requirements for substitutions. Include a detailed comparison of significant qualities of proposed substitution with those of the Work specified, a list of changes needed to other parts of the Work required to accommodate proposed substitution, and any proposed changes in the Contract Sum or the Contract Time should the substitution be accepted.

5. The Owners Project Manager will review the proposed substitution and notify Contractor of its acceptance or rejection by Change Order.

C. Comparable Product Requests:

1. Submit 3 copies of each request for comparable product. Do not submit unapproved products on Shop Drawings or other submittals.

2. Identify product to be replaced and show compliance with requirements for comparable product requests. Include a detailed comparison of significant qualities of proposed substitution with those of the Work specified.

3. The Owners Project Manager will review the proposed product and notify Contractor of its acceptance or rejection.

D. Deliver, store, and handle products using means and methods that will prevent damage, deterioration, and loss, including theft. Comply with manufacturer's written instructions.

1. Schedule delivery to minimize long-term storage at Project site and to prevent overcrowding of construction spaces.

2. Deliver products to Project site in manufacturer's original sealed container or packaging, complete with labels and instructions for handling, storing, unpacking, protecting, and installing.

3. Inspect products on delivery to ensure compliance with the Contract Documents and to ensure that products are undamaged and properly protected.

4. Store materials in a manner that will not endanger Project structure.

5. Store products that are subject to damage by the elements, under cover in a weathertight enclosure above ground, with ventilation adequate to prevent condensation.

E. Warranties specified in other Sections shall be in addition to, and run concurrent with, other warranties required by the Contract Documents. Manufacturer's disclaimers and limitations on product warranties do not relieve Contractor of obligations under requirements of the Contract Documents.

PRODUCTS

1. PRODUCT OPTIONS

Revise first paragraph below if any salvaged items or materials are used.

A.

1. Provide products complete with accessories, trim, finish, and other devices and components needed for a complete installation and the intended use and effect.

2. Descriptive, performance, and reference standard requirements in the Specifications establish "salient characteristics" of products.

B. Product Selection Procedures:

1. Where Specifications name a single product or manufacturer, provide the item indicated that complies with requirements.

2. Where Specifications include a list of names of products or manufacturers, provide one of the items indicated that complies with requirements.

3. Where Specifications include a list of names of products or manufacturers, accompanied by the term "available products" or "available manufacturers," provide one of the named items that complies with requirements. Comply with provisions for "comparable product requests" for consideration of an unnamed product.

4. Where Specifications name a product as the "basis-of-design" and include a list of manufacturers, provide the named product. Comply with provisions for "comparable product requests" for consideration of an unnamed product by the other named manufacturers.

Select subparagraph above or subparagraph below if "basis of design" products are specified.

5.

C. Unless otherwise indicated, the Owners Project Manager will select color, pattern, and texture of each product from manufacturer's full range of options that includes both standard and premium items.

EXECUTION (Not Applicable)

END OF SECTION 01600

Copyright 2003 by The American Institute of Architects (AIA)

GENERAL

1. CLOSEOUT SUBMITTALS

A. Record Drawings: Maintain a set of prints of the Contract Drawings as Record Drawings. Mark to show, on a weekly basis, actual installation where installation varies from that shown originally and forward any changes to the Owners Project Manager.

1. Identify and date each Record Drawing; include the designation "PROJECT RECORD DRAWING" in a prominent location. Record drawings to be submitted to the owner in both AutoCAD and PDF electronic formats

Delete paragraph and subparagraphs below if Specifications are on Drawings.

B.

1. Manufacturer's operation and maintenance documentation.

2. Maintenance and service schedules.

3. Maintenance service contracts.

4. Emergency instructions.

5. Spare parts list.

6. Wiring diagrams.

7. Copies of warranties.

PRODUCTS (Not Applicable)

EXECUTION

1. EXAMINATION AND PREPARATION

A. Examine substrates and conditions for compliance with manufacturer's written requirements including, but not limited to, surfaces that are sound, level, plumb, smooth, clean, and free of deleterious substances; substrates within installation tolerances; and application conditions within environmental limits. Proceed with installation only after unsatisfactory conditions have been corrected.

B. Before proceeding to lay out the Work, verify layout information shown on Drawings, in relation to property survey and existing benchmarks.

C. Take field measurements as required to fit the Work properly. Where fabricated products are to be fitted to other construction, verify dimensions by field measurement before fabrication and, when possible, allow for fitting and trimming during installation.

2. CUTTING AND PATCHING

A. Do not cut structural members without prior written approval of the Engineer.

Retain first paragraph below if Owner continues to occupy other portions of an existing facility.

B.

3. INSTALLATION

A. Comply with manufacturer's written instructions for installation. Anchor each product securely in place, accurately located and aligned with other portions of the Work. Clean exposed surfaces and protect from damage.

B. Clean Project site and work areas daily, including common areas.

4. FINAL CLEANING

A. Complete the following cleaning operations before requesting inspection for certification of Substantial Completion:

1. Remove labels that are not permanent.

2. Clean transparent materials, including mirrors. Remove excess glazing compounds. Replace chipped or broken glass.

3. Clean exposed finishes to a dust-free condition, free of stains, films, and foreign substances. Sweep concrete floors broom clean.

4. Vacuum carpeted surfaces and wax resilient flooring.

5. Wipe surfaces of mechanical and electrical equipment. Remove excess lubrication. Clean plumbing fixtures. Clean light fixtures, lamps, globes, and reflectors.

6. Clean Project site, yard, and grounds, in areas disturbed by construction activities. Sweep paved areas; remove stains, spills, and foreign deposits. Rake grounds to a smooth, even-textured surface.

5. CLOSEOUT PROCEDURES

A. Substantial Completion: Before requesting Substantial Completion inspection, complete the following:

1. Prepare a monetized list of items to be completed and corrected (punch list), the value of items on the list, and reasons why the Work is not complete.

2. Advise Owner of pending insurance changeover requirements.

3. Submit specific warranties, maintenance service agreements, and similar documents.

4. Obtain and submit releases permitting Owner unrestricted use of the Work and access to services and utilities. Include occupancy permits, operating certificates, and similar releases.

5. Submit Record operation and maintenance manuals and similar final record information. Record drawings to be submitted to the owner in both AutoCAD and PDF electronic formats.

6. Deliver tools, spare parts, extra materials, and similar items.

7. Make final changeover of permanent locks and deliver keys to Owner.

8. Complete startup testing of systems.

9. Remove temporary facilities and controls.

10. Submit changeover information related to Owner's occupancy, use, operation, and maintenance.

11. Complete final cleaning requirements, including touchup painting.

12. Touch up and otherwise repair and restore marred exposed finishes to eliminate visual defects.

B. Submit a written request for inspection for Substantial Completion. On receipt of request, Owners Project Manager will proceed with inspection or advise Contractor of unfulfilled requirements. Owners Project Manager will prepare the Certificate of Substantial Completion after inspection or will advise Contractor of items that must be completed or corrected before certificate will be issued.

C. Request inspection for Final Completion, once the following are complete:

1. Submit a copy of Substantial Completion inspection list stating that each item has been completed or otherwise resolved for acceptance.

2. Instruct Owner's personnel in operation, adjustment, and maintenance of products, equipment, and systems.

D. Request reinspection when the Work identified in previous inspections as incomplete is completed or corrected.

E. Submit a written request for final inspection for acceptance. On receipt of request, Architect will proceed with inspection or advise Contractor of unfulfilled requirements. Architect will prepare final Certificate for Payment after inspection or will advise Contractor of items that must be completed or corrected before certificate will be issued.

6. DEMONSTRATION AND TRAINING

A. Engage qualified instructors to instruct Owner's personnel to adjust, operate, and maintain systems, subsystems, and equipment not part of a system. Include a detailed review of the following:

1. Include instruction for basis of system design and operational requirements, review of documentation, emergency procedures, operations, adjustments, troubleshooting, maintenance, and repairs.

END OF SECTION 01701

Copyright 2003 by The American Institute of Architects (AIA)

GENERAL

7. SECTION REQUIREMENTS

A. Items indicated to be removed and salvaged remain Owner's property. Remove, clean, and deliver to Owner's designated storage area.

B. Comply with EPA regulations and hauling and disposal regulations of authorities having jurisdiction.

C. Owner will occupy portions of building immediately adjacent to selective demolition area. Conduct selective demolition so Owner's operations will not be disrupted.

D. It is not expected that hazardous materials will be encountered in the Work. If materials suspected of containing hazardous materials are encountered, do not disturb; immediately notify the Owner. Owner will remove hazardous materials under a separate contract.

PRODUCTS (Not Applicable)

EXECUTION

1. DEMOLITION

A. Maintain services/systems indicated to remain and protect them against damage during selective demolition operations. Before proceeding with demolition, provide temporary services/systems that bypass area of selective demolition and that maintain continuity of services/systems to other parts of the building.

B. Locate, identify, shut off, disconnect, and cap off utility services and mechanical/electrical systems serving areas to be selectively demolished.

C. Provide temporary barricades and other protection required to prevent injury to people and damage to adjacent buildings and facilities to remain.

D. Provide and maintain shoring, bracing, and structural supports as required to preserve stability and prevent movement, settlement, or collapse of construction and finishes to remain or construction being demolished.

E. Provide temporary weather protection to prevent water leakage and damage to structure and interior areas.

F. Protect walls, ceilings, floors, and other existing finish work that are to remain. Erect and maintain dustproof partitions. Cover and protect furniture, furnishings, and equipment that have not been removed.

G. Neatly cut openings and holes plumb, square, and true to dimensions required. Use cutting methods least likely to damage construction to remain or adjoining construction.

H. Promptly remove demolished materials from Owner's property and legally dispose of them. Do not burn demolished materials. All existing landscaping, roads, trees and pavement are to be protected and restored to original condition at the end of the project.

END OF SECTION 01732

Copyright 2005 by The American Institute of Architects (AIA)

GENERAL

2. SECTION REQUIREMENTS

A. Submittals: Model code evaluation reports for wood-preservative treated wood engineered wood products, and metal framing anchors.

PRODUCTS

1. WOOD PRODUCTS, GENERAL

A. Lumber: Provide dressed lumber, S4S, marked with grade stamp of inspection agency.

B. Engineered Wood Products: Acceptable to authorities having jurisdiction and for which current model code research or evaluation reports exist that show compliance with building code in effect for Project.

2. TREATED MATERIALS

A. Preservative-Treated Materials: AWPA C2, except that lumber not in ground contact and not exposed to the weather may be treated according to AWPA C31 with inorganic boron (SBX).

1. Use treatment containing no arsenic or chromium.

2. Kiln-dry lumber after treatment to a maximum moisture content of 19 percent.

3. Mark lumber with treatment quality mark of an inspection agency approved by the ALSC Board of Review.

B. Provide preservative-treated materials for items indicated on Drawings,

1. Wood members in connection with roofing, flashing, vapor barriers, and waterproofing, must be resistant to Pressure Treated chemicals if used in a location where they may become exposed.

2. Concealed members in contact with masonry or concrete.

3. Wood floor plates that are installed over concrete slabs-on-grade.

3. LUMBER

A. Dimension Lumber:

1. Maximum Moisture Content: 15 percent for 2-inch nominal (38-mm actual) thickness or less, 19 percent for more than 2-inch nominal (38-mm actual) thickness.

Select one grade requirement and one or more species group in first two subparagraphs below depending on availability and suitability for Project. Designate load-bearing walls on Drawings.

2.

Retain subparagraph below for better appearance for exposed work.

3.

a. Species: As specified for framing other than non-load bearing partitions.

Select one or more species in first two paragraphs below depending on availability and suitability for Project.

B.

4. ENGINEERED WOOD PRODUCTS

A. Engineered wood products with allowable design stresses, as published by manufacturer, that meet or exceed those indicated. Manufacturer's published values shall be demonstrated by comprehensive testing.

Retain paragraph and subparagraphs below if required for use with wood I-joists. I-joist blocking can also be used, but rim board is stronger and requires less labor.

5.

A. Fasteners: Size and type indicated. Where rough carpentry is exposed to weather, in ground contact, or in area of high relative humidity, provide fasteners of Type 304 stainless steel.

1. Power-Driven Fasteners: ESR 1539.

2. Bolts: Galvanized Steel bolts complying with ASTM A 307, Grade A (ASTM F 568, Property Class 4.6); with ASTM A 563 (ASTM A 563M) hex nuts and, where indicated, flat washers.

B. Metal Framing Anchors: Structural capacity, type, and size indicated.

1. Use anchors made from stainless steel complying with ASTM A 666, Type 304 for exterior locations and where indicated and must be resistant to Pressure Treated chemicals if used in a location where they may become exposed.

EXECUTION

1. INSTALLATION

A. Set rough carpentry to required levels and lines, with members plumb, true to line, cut, and fitted. Locate nailers, blocking, and similar supports to comply with requirements for attaching other construction.

B. Securely attach rough carpentry to substrates, complying with the following:

1. ESR 1539 for power-driven fasteners.

2. Published requirements of metal framing anchor manufacturer.

3. Table R602.3(1), "Fastener Schedule for Structural Members," and Table R602.3(2), "Alternate Attachments," in ICC's International Residential Code for One- and Two-Family Dwellings.

END OF SECTION 06100

Copyright 2005 by The American Institute of Architects (AIA)

GENERAL

2. SECTION REQUIREMENTS

A. Submittals: Model code evaluation reports for treated wood.

PRODUCTS

1. WOOD PRODUCTS, GENERAL

A. Lumber: Provide dressed lumber, S4S, marked with grade stamp of inspection agency.

2. TREATED MATERIALS

A. Preservative-Treated Materials: AWPA C2, except that lumber not in ground contact and not exposed to the weather may be treated according to AWPA C31 with inorganic boron (SBX)].

1. Use treatment containing no arsenic or chromium.

2. Kiln-dry lumber after treatment to a maximum moisture content of 19 percent.

3. Mark lumber with treatment quality mark of an inspection agency approved by the ALSC Board of Review.

B. Provide preservative-treated materials for items indicated on Drawings.

1. Wood members in connection with roofing, flashing, vapor barriers, and waterproofing.

2. Concealed members in contact with masonry or concrete.

3. Wood floor plates that are installed over concrete slabs-on-grade.

3. LUMBER

A. Dimension Lumber:

1. Maximum Moisture Content15 percent.

Select one grade requirement and one or more species group in first two subparagraphs below depending on availability and suitability for Project.

2.

3. Other Framing: Construction, Stud, or No. 2

Select one or more species in first two paragraphs below depending on availability and suitability for Project.

B.

C. Provide for nailers, blocking, and similar members.

4. PLYWOOD BACKING PANELS

A. Telephone and Electrical Equipment Backing Panels: Plywood, Exposure 1, C-D Plugged, fire-retardant treated, not less than 1/2 inch (12.7 mm) thick.

5. FASTENERS

A. Fasteners: Size and type indicated. Where rough carpentry is exposed to weather, in ground contact, or in area of high relative humidity, provide fasteners of Type 304 stainless steel.

1. Power-Driven Fasteners: CABO NER-272.

EXECUTION

1. INSTALLATION

A. Set miscellaneous rough carpentry to required levels and lines, with members plumb, true to line, cut, and fitted. Locate nailers, blocking, and similar supports to comply with requirements for attaching other construction.

B. Securely attach miscellaneous rough carpentry to substrates, complying with the following:

1. CABO NER-272 for power-driven fasteners.

2. Table R602.3(1), "Fastener Schedule for Structural Members," and Table R602.3(2), "Alternate Attachments," in ICC's International Residential Code for One- and Two-Family Dwellings and Table 23-II-B-2, "Wood Structural Panel Roof Sheathing Nailing Schedule," in ICBO's Uniform Building Code.

END OF SECTION 06105

Copyright 2005 by The American Institute of Architects (AIA)

GENERAL

1. SECTION REQUIREMENTS

A. Submittals: Model code evaluation reports for building wrap.

PRODUCTS

1. WOOD PANEL PRODUCTS, GENERAL

A. Plywood: DOC PS 1.

2. WALL SHEATHING

A. Plywood Wall Sheathing: Exterior, Structural I sheathing.

3. SUBFLOORING AND UNDERLAYMENT

A. Combination Subfloor-Underlayment:

1. Plywood Combination Subfloor-Underlayment: DOC PS 1, Exterior, Structural I, C-C Plugged single-floor panels.

2. Oriented-Stand-Board Combination Subfloor-Underlayment: Exposure 1 single-floor panels.

B. Subflooring:

1. Plywood Subflooring: Exterior, Structural I single-floor panels or sheathing.

2. Oriented-Strand-Board Subflooring: Exposure 1single-floor panels or sheathing.

C. Underlayment:

1. Plywood Underlayment for Resilient Flooring: DOC PS 1, Exterior A-C Underlayment with fully sanded face.

2. Plywood Underlayment for Carpet: DOC PS 1, Exterior, C-C Plugged

4. MISCELLANEOUS PRODUCTS

A. Fasteners: Size and type indicated.

1. CABO NER-272 for power-driven fasteners.

2. Table R602.3(1), "Fastener Schedule for Structural Members," and Table R602.3(2), "Alternate Attachments," in ICC's International Residential Code for One- and Two-Family Dwellings and Table 23-II-B-2, "Wood Structural Panel Roof Sheathing Nailing Schedule," in ICBO's Uniform Building Code.

B. Weather-Resistant Sheathing Paper:

1. Building Paper: ASTM D 226, Type 1 (No. 15 asphalt-saturated organic felt), unperforated.

2. Building Wrap: ASTM E 1677, Type I air retarder; with flame-spread and smoke-developed indexes of less than 25 and 450, respectively, when tested according to ASTM E 84; UV stabilized; and acceptable to authorities having jurisdiction.

a. Products:

1) Certainteed 15lb paper or similar approved

C. Sheathing Joint-and-Penetration Treatment Materials:

1. Sealant for Gypsum Sheathing Board: Joint sealant recommended by sheathing manufacturer for application indicated.

D. Adhesives for Field Gluing Panels to Framing: APA AFG-01.

E. Flexible Flashing: Adhesive rubberized-asphalt compound, bonded to polyethylene film, with an overall thickness of 0.030 inch (0.8 mm).

EXECUTION

1. INSTALLATION

A. Securely attach to substrates, complying with the following:

1. CABO NER-272 for power-driven fasteners.

2. Table R602.3(1), "Fastener Schedule for Structural Members," and Table R602.3(2), "Alternate Attachments," in ICC's International Residential Code for One- and Two-Family Dwellings and Table 23-II-B-2, "Wood Structural Panel Roof Sheathing Nailing Schedule," in ICBO's Uniform Building Code.

B. Fastening Methods:

1. Combination Subfloor-Underlayment:

a. Glue and nail to wood framing.

b. Screw to cold-formed metal framing.

2. Subflooring:

a. Glue and nail to wood framing.

b. Screw to cold-formed metal framing.

3. Wall and Roof Sheathing:

a. Nail to wood framing.

b. Screw to cold-formed metal framing.

4. Underlayment:

a. Nail to subflooring.

Retain first paragraph below if joints are sealed in lieu of using a weather-resistant barrier; verify requirements of authorities having jurisdiction.

C.

D. Building Wrap Installation:

1. Apply building wrap immediately after sheathing is installed.

2. Seal seams, edges, fasteners, and penetrations with tape.

3. Extend into jambs of openings and seal corners with tape.

END OF SECTION 06100

SECTION 06200 - FINISH CARPENTRY

GENERAL

2. SECTION REQUIREMENTS

A. Submittals: Samples for wall cap detail, window trim and door casing

PRODUCTS

1. MATERIALS, GENERAL

A. Lumber: DOC PS 20 and grading rules of inspection agencies certified by American Lumber Standards Committee Board of Review.

2. EXTERIOR FINISH CARPENTRY

If retaining first paragraph below, select one texture, grade, and species.

A.

1. Maximum Moisture Content: 15 percent.

B. Lumber Siding: Kiln-dried, Primed Grade B, western red cedar

C. Bodyguard Soffits: 3/4"-inch- thick, Exterior-type, and touch sanded

3. INTERIOR STANDING AND RUNNING TRIM

A. Interior Softwood Lumber Trim: C Select (Choice), eastern white, Idaho white, lodgepole, ponderosa, or sugar pine

1. Maximum Moisture Content: 15 percent.

B. Wood Moldings: WMMPA WM 4 made to patterns in WMMPA WM 12 from kiln-dried stock.

1. to match existing

4. MISCELLANEOUS MATERIALS

A. Fasteners for Exterior Finish Carpentry: Stainless-steel

B. Glue: Aliphatic-resin, polyurethane, or resorcinol wood glue recommended by manufacturer.

1. Use waterproof resorcinol glue for exterior applications.

C. Insect Screening for Soffit Vents: Aluminum

EXECUTION

1. INSTALLATION

A. Condition finish carpentry in installation areas for 24 hours before installing.

B. Prime and back prime lumber for painted finish exposed on the exterior.

C. Install finish carpentry level, plumb, true, and aligned with adjacent materials. Scribe and cut to fit adjoining work. Refinish and seal cuts.

D. Install standing and running trim with minimum number of joints practical, using full-length pieces from maximum lengths of lumber available. Stagger joints in adjacent and related trim. Cope at returns and miter at corners.

E. Nail siding at each stud. Do not allow nails to penetrate more than one thickness of siding, unless otherwise recommended by siding manufacturer. Seal joints at inside and outside corners and at trim locations.

F. Select and arrange paneling for best match of adjacent units. Install with uniform tight joints.

END OF SECTION 06200

Copyright 2005 by The American Institute of Architects (AIA)

GENERAL

2. SECTION REQUIREMENTS

A. Submittals: Shop Drawings & Stone Samples at least 12 inches (300 mm) square.

B. Verify dimensions of stone countertops by field measurements and indicate on Shop Drawings.

PRODUCTS

1. STONE

Some varieties of granite that are suitable for countertops do not comply with ASTM C 615; verify that granite selected will comply before retaining option in first paragraph below.

A.

1. Kashmir Gold, polished with pencil round edges to top and bottom edges or similar approved granite

2. COUNTERTOP FABRICATION

A. Comply with recommendations in MIA's "Dimensional Stone - Design Manual IV."

1. Thickness: 1-1/4 inches (30 mm).

2. Edge Detail: Straight, slightly eased at top 3/8-inch (10-mm) bevel

B. Splashes: 3/4-inch (20-mm) nominal thickness [backsplashes] [and] [end splashes].

1. Height: 4 inches (100 mm).

2. Top-Edge Detail: Straight, slightly eased at corner3/8-inch (10-mm) bevel.

C. Fabricate molded edges with machines having abrasive shaping wheels made to reverse contour of edge profile. Form corners of molded edges as indicated with outside corners slightly eased.

D. Seams: Fabricate countertops without seams.

E. Cutouts and Holes:

1. Undercounter Fixtures: Make cutouts for undercounter fixtures in shop using template or pattern furnished by fixture manufacturer. Form cutouts to smooth, even curves.

a. Edge Detail: Vertical, slightly eased at top and bottom surfaces and projecting 3/16 inch (5 mm) into fixture opening

2. Counter-Mounted Fixtures: Prepare countertops in shop for field cutting openings for counter-mounted fixtures. Mark tops for cutouts and drill holes at corners of cutout locations. Make corner holes of largest radius practical.

3. Fittings: Drill countertops in shop for plumbing fittings, undercounter soap dispensers, and similar items.

EXECUTION

1. INSTALLING COUNTERTOPS

Retain one of two options in first paragraph below. For best work, retain first and show subtops on Drawings. Second option is generally suitable only for residential work and only if countertops are adequately supported. Second option may also be used with lavatory tops supported by steel angle framing if framing is adequately spaced for stone strength and thickness and has flush top surface.

A.

B. Space seams with 1/16-inch (1.5-mm) gap for filling with sealant. Use temporary shims to ensure uniform spacing and use clamps to eliminate lipping.

C. Complete cutouts not finished in shop. Mask areas of countertops adjacent to cutouts while cutting.

D. Install backsplash and end splashes by adhering to wall with water-cleanable epoxy adhesive. Leave 1/16-inch (1.5-mm) gap between countertop and splash for filling with sealant. Use temporary shims to ensure uniform spacing.

Delete first paragraph below if grouted seams are not used.

E.

2. CLEANING

A. Clean countertops as work progresses. Remove adhesive, grout, mortar, and sealant smears immediately.

B. Clean stone countertops not less than six days after completion of sealant installation, using clean water and soft rags. Do not use materials or methods that could damage stone.

Delete paragraph below if not required or recommended for stone type.

C.

END OF SECTION 06415

Copyright 2005 by The American Institute of Architects (AIA)

GENERAL

3. SECTION REQUIREMENTS

A. Surface-Burning Characteristics: ASTM E 84, and as follows:

Revise first subparagraph below to suit requirements of authorities having jurisdiction. The International Building Code also requires a flame-spread index of 25 or less for concealed insulation in Types I and II construction.

1.

2. Smoked-Developed Index: 450 or less.

PRODUCTS

1. INSULATION PRODUCTS

Usually select Type IV in first paragraph below if extruded polystyrene is used.

A.

2. ACCESSORIES

If retaining first paragraph below, select first water-vapor transmission requirement if sheet radiant barrier also serves as vapor barrier, second requirement if not.

A.

EXECUTION

1. INSTALLATION

A. Install insulation in areas and in thicknesses indicated or required to produce R-values indicated. Cut and fit tightly around obstructions and fill voids with insulation.

B. Except for loose-fill insulation and insulation that is friction fitted in stud cavities, bond units to substrate with adhesive or use mechanical anchorage to provide permanent placement and support of units.

C. Extend vapor retarder to extremities of areas to be protected from vapor transmission. Secure in place with adhesives or other anchorage. Locate seams at framing members, overlap, and seal with tape.

END OF SECTION 07210

Copyright 2005 by The American Institute of Architects (AIA)

GENERAL

2. SECTION REQUIREMENTS

A. Submittals: Gray prestained Shingles to match existing gray prestained shingle.

Retain paragraph below if fire-retardant-treated shingles are required.

1. SHINGLES,

Coordinate lengths of shingles and shakes with roof slopes.

A.

2. ACCESSORIES

A. Felt Underlayment: ASTM D 226, Type I, No. 15.

B. Self-Adhering Sheet Underlayment: ASTM D 1970, SBS-modified asphalt; mineral-granule or slip-resisting-polyethylene surfaced; with release paper backing; cold applied.

C. Nails: Type 316 stainless-steel nails of sufficient length to penetrate 3/4 inch into solid wood decking or extend at least 1/8 inch plywood sheathing.

1. Use stainless steel shingle-type staples to attach wood shingles.

D. Sheet Metal Flashing and Trim: Comply with requirements in Division 7 Section "Sheet Metal Flashing and Trim."

1. Sheet Metal: 16 oz min. Lead coated Copper.

2. Fabricate sheet metal flashing and trim to comply with recommendations in SMACNA's "Architectural Sheet Metal Manual."

EXECUTION

1. INSTALLATION

A. Comply with CSSB's "Design and Application Manual for Exterior and Interior Walls" for wall installations.

B. Layout shingle coursing prior to start of shingle installation.

C. Install shingles to match existing weather. Weather exposure to match existing exposure.

D. When white cedar shingles are installed against the lower corner of windows or openings, the joint must align with the edge of the opening. Apply glue to the back of shingles below opening and nail.

E. Install metal flashing above window heads allowing underlayment to overlap flashing.

F. Allow a 1/4 inch gap between the top of wood casing and white cedar shingles installed above window and door headers.

G. At wood trim at jambs of doors and windows, apply line of caulk along edge of trim prior to installing shingles.

H. Begin white cedar shingle installation from the bottom, working toward the top. Double first row of shingles. Do not allow joints between shingles to align.

I. Leave gap of 1/8" between neighboring shingles

J. Joints of successive courses to be offset by a minimum of 1-1/2 inches.

K. Joints of 3 consecutive shingle courses shall not line up.

L. Use 2 fasteners per shingle at 3/4 inch from each edge and 1 inch above the butt-line of the overlapping shingle. If shingles are wider than 8 inches use additional fasteners.

END OF SECTION 07317

Copyright 2003 by The American Institute of Architects (AIA)

GENERAL

1. SECTION REQUIREMENTS

A. Submittals: Product Data, including details of construction and factory-finishing specifications.

B. Quality Standard: AWI's "Architectural Woodwork Quality Standards."

Select second or third option in first paragraph below if positive-pressure testing is required.

C.

Verify availability of certification in paragraph below with manufacturers selected before retaining.

D.

PRODUCTS

1. STILE AND RAIL DOORS

Retain one or more of first three paragraphs and associated subparagraphs below if WDMA standard is selected in "Quality Standard" Paragraph in Part 1.

A.

1. Half Glazed Red Oak Door: by Simpson Doors or similar approved

Retain one grade in paragraph below. Premium or Select grade is for transparent finish; Standard grade is for opaque finish. Also retain one species or insert another.

2.

A. Factory fit doors to suit frame-opening sizes and to comply with referenced quality standard.

1. Provide 1/8-inch (3.2-mm) clearance at jambs, heads, and meeting stiles and 1/2 inch (12.7 mm) at bottom. At thresholds, provide 3/8-inch (9.5-mm) clearance.

2. Comply with NFPA 80 for fire-resistance-rated doors.

B. Factory machine doors for hardware that is not surface applied.

C. Glaze doors at factory.

D. Factory treat exterior doors after fabrication with water repellent to comply with WDMA I.S.4.

Retaining paragraph below will help improve indoor air quality by lowering the use of VOC's at the Project site.

E.

EXECUTION

1. INSTALLATION

A. Install fire-rated wood door frames level, plumb, true, and aligned with adjacent materials. Countersink fasteners, fill surface flush, and sand smooth.

B. Install fire-rated doors to comply with NFPA 80.

Delete first paragraph and subparagraph below if factory fitting was retained in Part 2.

C.

1. Provide 1/8-inch (3.2-mm) clearance at jambs, heads, and meeting stiles and 1/8 inch (3.2 mm) at bottom. At thresholds, provide 1/4-inch (6.4-mm) clearance from bottom of door.

D. Align factory-fitted doors in frames for uniform clearances.

E. Repair, refinish, or replace factory-finished doors damaged during installation as directed by Architect.

END OF SECTION 08212

Copyright 2005 by The American Institute of Architects (AIA)

GENERAL

1. SECTION REQUIREMENTS

A. Submittals: Product Data, Shop Drawings, and color Samples.

B. Quality Standard: Comply with AAMA/NWWDA 101/I.S.2/NAFS.

Retain requirements for AAMA or WDMA certification and labeling if required.

1.

PRODUCTS

1. ALUMINUM WINDOWS

A. Products:

1. Andersen Windows, 100 Series Awning Windows

B. Window Types:

1. Awning.

C. Performance Class: C.

Determine Project location's basic wind speed and design pressures for window locations before selecting performance grade in first paragraph below. Verify availability of class and grade specified with manufacturers selected.

D.

First option in first paragraph below is suitable for most of the U.S. at 25 percent relative humidity where outdoor design temperature is below 0 deg F (minus 18 deg C); second option is suitable for same relative humidity at minus 10 deg F (minus 23.3 deg C). In northern states where winter outdoor design temperature is lower, increase factor.

E.

Retain first paragraph below if needed. First, second, and fourth options in paragraph are recommended by the Efficient Window Collaborative for the northern, central, and southern zones of the U.S., respectively. Third option is U-factor requirement per ASHRAE/IESNA 90.1-1999 for window-to-wall ratios of less than 0.2 for large buildings and 0.15 for small buildings. Select test option complying with energy code applicable to Project.

F.

Retain first paragraph below if needed. First option in paragraph is the maximum SHGC per IECC 2003 requirements for the area-weighted average SHGC of all fenestration installed in climates up to 3500 HDD (cooling climates). Second and third options are recommended by the Efficient Window Collaborative for the northern and central zones of the U.S., respectively, for spaces where cooling is a concern.

G.

H. Construction: Provide units with a concealed, thermal break.

I. Provide gear-type rotary operators with folding handles for awning windows.

J. Equip units with aluminum mesh insect screens at operable sashes.

K. Glaze units with clear sealed insulating glass, complying with Division 8 Section "Glazing."

L. Finish: Class II, clear anodic finish; AA-M12C22A31;

EXECUTION

1. INSTALLATION

A. Set units level, plumb, and true to line, without warp or rack of frames and panels. Provide proper support and anchor securely in place.

B. Set sill members in bed of sealant or with gaskets, as indicated, to provide weathertight construction.

C. Adjust operating panels, screens, and hardware to provide a tight fit at contact points and weather stripping for smooth operation and weathertight closure. Lubricate hardware and moving parts.

D. Clean aluminum surfaces and glass immediately after installing windows. Remove nonpermanent labels from glass surfaces.

END OF SECTION 08520

Copyright 2005 by The American Institute of Architects (AIA)

GENERAL

2. SECTION REQUIREMENTS

Retain first paragraph below if an allowance is used.

A.

B. Deliver keys to Owner.

PRODUCTS

1. HARDWARE

A. Manufacturers:

1. Schlage or Town of Barnstable Standard

B. Hinges:

Select from options in five subparagraphs below.

1.

2. 2 hinges for 1-3/8-inch- (35-mm-) thick wood doors.

C. Locksets and Latchsets: ( all to be compatible with Schlage removable core key system)

1. Schlage B571 Commercial Restroom Indicator Deadbolt in Satin Chrome (Note: Base bid is for plastic toilet partitionas and Alternate 5 if for stile and rail partitions)

2. Separate fixed lever handle to inside Schlage Elan Lever Handle in Satin Chrome

3. Provide trim on exit devices matching locksets.

D. Closers:

Select from options in two subparagraphs below.

1.

2. Mount closers on interior side (room side) of door opening. Provide regular-arm, parallel-arm, or top-jamb-mounted closers as necessary.

3. Adjustable delayed opening (accessible to people with disabilities) feature on closers.

E. Provide wall stops or floor stops for doors without closers.

F. Provide hardware finishes as follows:

1. Hinges: Satin Chrome

2. Locksets, Latchsets, and Exit Devices: Satin Chrome

EXECUTION

1. INSTALLATION

A. Mount hardware in locations recommended by the Door and Hardware Institute and as required by Americans with Disabilities Act (ADA) and the Mass. Architectural Access Board unless otherwise indicated.

END OF SECTION 08710

Copyright 2003 by The American Institute of Architects (AIA)

GENERAL

2. SECTION REQUIREMENTS

A. Submittals: Product Data.

B. STC-Rated Assemblies: For gypsum plaster assemblies with STC ratings, provide materials and construction identical to assemblies whose STC ratings were determined according to ASTM E 90 and classified according to ASTM E 413 by a qualified independent testing agency.

C. Fire-Resistance-Rated Assemblies: For gypsum plaster assemblies with fire-resistance ratings, provide materials and construction identical to assemblies tested according to ASTM E 119 by an independent testing and inspecting agency acceptable to authorities having jurisdiction.

PRODUCTS

1. ACCESSORIES

A. Comply with material provisions of ASTM C 841 and requirements indicated below; coordinate depth of accessories with thicknesses and number of plaster coats required.

1. Aluminum Components: ASTM B 221 (ASTM B 221M) for Alloy and Temper 6063-T5 or aluminum extrusions with similar properties.

2. Plastic Components: ASTM D 3678, rigid PVC.

3. Galvanized Steel Components: Fabricated from zinc-coated (galvanized) steel sheet complying with ASTM A 653/A 653M, G40 (Z90) minimum coating designation.

B. Bonding Compound: ASTM C 631.

C. Sound Attenuation Blankets: ASTM C 665, Type I (unfaced mineral fiber).

2. GYPSUM PLASTER

A. Base-Coat Plasters: ASTM C 28/C 28M, gypsum neat plaster with job-mixed sand aggregate.

B. Finish-Coat Plasters: Gypsum ready-mixed finish plaster; manufacturer's standard mill-mixed gauged interior finish.

C. Plaster Mixes: Comply with ASTM C 842 and manufacturer's written instructions for applications indicated.

EXECUTION

1. INSTALLATION

A. Install strapping for ceiling to comply with ASTM C 841.

Retain subparagraph below for partitions, framed soffits, and vertical furring.

1.

B. STC-Rated Assemblies: Comply with ASTM C 919 for location of edge trim and closing off sound-flanking paths around or through assemblies.

C. Install supplementary framing, blocking, and bracing at terminations in Work and for support of fixtures, equipment services, heavy trim, grab bars, toilet accessories, furnishings, and similar work.

D. Apply and cure plaster materials and finishes to comply with ASTM C 842. Apply two coats. Apply float finish coat.

END OF SECTION 09210

Copyright 2005 by The American Institute of Architects (AIA)

GENERAL

2. SECTION REQUIREMENTS

A. Submittals: Product Data.

B. Fire-Resistance-Rated Assemblies: Provide materials and construction identical to those tested in assemblies per ASTM E 119 by an independent testing and inspecting agency acceptable to authorities having jurisdiction.

C. STC-Rated Assemblies: Provide materials and construction identical to those tested in assemblies per ASTM E 90 and classified per ASTM E 413 by a qualified independent testing and inspecting agency.

PRODUCTS

1. PANEL PRODUCTS

A. Provide in maximum lengths available to minimize end-to-end butt joints.

B. Interior Gypsum Board: ASTM C 36/C 36M or ASTM C 1396/C 1396M, in thickness indicated, with manufacturer's standard edges. Greenboard to repairs and Blueboard below new plastered areas unless otherwise indicated.

2. ACCESSORIES

A. Trim Accessories: ASTM C 1047, formed from galvanized or aluminum-coated steel sheet, rolled zinc, plastic, or paper-faced galvanized-steel sheet. For exterior trim, use accessories formed from hot-dip galvanized-steel sheet, plastic, or rolled zinc.

1. Provide cornerbead at outside corners unless otherwise indicated.

2. Provide LC-bead (J-bead) at exposed panel edges.

3. Provide control joints where indicated.

B. Aluminum Accessories: Extruded-aluminum accessories indicated with manufacturer's standard corrosion-resistant primer

C. Joint-Treatment Materials: ASTM C 475/C 475M.

1. Joint Tape: Paper unless otherwise recommended by panel manufacturer.

2. Joint Compounds: Setting-type compounds

3. Skim Coat: For final coat of Level 5 finish, use setting-type.

EXECUTION

1. INSTALLATION

A. Install gypsum board to comply with ASTM C 840.

1. Isolate gypsum board assemblies from abutting structural and masonry work. Provide edge trim and acoustical sealant.

2. Single-Layer Fastening Methods: Fasten gypsum panels to supports with screws.

3. Multilayer Fastening Methods: Fasten base layers and face layer separately to supports with screws.

B. Finishing Gypsum Board: ASTM C 840.

1. At concealed areas, unless a higher level of finish is required for fire-resistance-rated assemblies, provide Level 1 finish: Embed tape at joints.

2. At substrates for tile, provide Level 1 finish: Embed tape and apply separate first coat of joint compound to tape, fasteners, and trim flanges.

END OF SECTION 09250

Copyright 2005 by The American Institute of Architects (AIA)

GENERAL

1. SECTION REQUIREMENTS

A. Submittals: Product Data and Samples.

The International Building Code and NFPA 101, "Life Safety Code," require that floors in corridors and exits meet critical radiant flux limitations. Delete first paragraph below if not applicable.

B.

C. Extra Materials: Deliver to Owner at least 10 linear feet in roll form and in full roll width, for each type and color of resilient sheet flooring installed.

PRODUCTS

1. SHEET VINYL FLOOR COVERING (Dwg A2)

A. Products:

1. Johnsonite Acczent Heterogeneous Sheet or similar approved

B. Color and Pattern: Acczent Light Cherry, 6007 or similar approved

For proprietary or semiproprietary specification, delete descriptive requirements in remaining paragraphs below that are determined by product designations inserted above.

C.

D. Sheet Vinyl Floor Covering With Backing: ASTM F 1303, Type I, minimum binder content of 90 percent Grade 1.

1. Overall Thickness: 2mm

2. Interlayer Material: None.

3. Backing Class: Class A (fibrous).

E. Wearing Surface: Embossed

F. Sheet Width: As standard with manufacturer 6.6 feet (2.0 m).

G. Seaming Method: Heat welded.

2. INSTALLATION ACCESSORIES

A. Trowelable Leveling and Patching Compounds: Latex-modified, portland cement- or blended hydraulic cement-based formulation provided or approved by flooring manufacturer for applications indicated.

B. Adhesives: Water-resistant type recommended by manufacturer to suit sheet vinyl floor covering and substrate conditions indicated.

C. Heat-Welding Bead: Solid-strand product of floor covering manufacturer.

1. Color: Match floor covering .

D. Integral-Flash-Cove-Base Accessories: 1-inch- radius cove strip and square metal, vinyl, or rubber cap, both provided or approved by floor covering manufacturer.

Not all manufacturers require metal corners and end stops. Delete subparagraph below if not required.

1.

E. Metal Edge Strips: Extruded aluminum in maximum available lengths to minimize joints.

EXECUTION

1. INSTALLATION

A. Prepare concrete substrates according to ASTM F 710. Verify that substrates are dry and free of curing compounds, sealers, and hardeners.

B. Unroll sheet floor coverings and allow them to stabilize before cutting and fitting.

C. Maintain uniformity of resilient sheet flooring direction, and match edges for color shading at seams.

D. Minimize number of seams; place seams in inconspicuous and low-traffic areas, at least 6 inches (152 mm) away from parallel joints in substrates.

E. Integral Flash Cove Base: Cove floor coverings 6 inches (152 mm) up vertical surfaces. Support on cove strip and butt against cap strip.

1. Install metal corners and end stops.

END OF SECTION 09652

Copyright 2005 by The American Institute of Architects (AIA)

GENERAL

1. SECTION REQUIREMENTS

A. Submittals: Product Data and Samples.

B. Extra Materials: Deliver to Owner full-width carpet equal to 5 percent of each type and color carpet installed, packaged with protective covering for storage.

PRODUCTS

1. CARPET

Copy and re-edit this article for each carpet required.

A.

1. Shaw Floors, Volare 00726 Artisan Tan or similar approved

For a proprietary or semiproprietary specification, delete descriptive carpet requirements in remaining paragraphs below that are determined by product designations inserted above.

B.

C. Pile Characteristic: Level-loop pile.

D. Width: 12 feet (3.7 m.

The International Building Code and NFPA 101, "Life Safety Code," require that floors in corridors and exits meet critical radiant flux limitations. Delete first paragraph below if not applicable.

2.

Copy and re-edit this article for each carpet cushion required.

A.

B. Rubber Cushion: Rippled waffle.

1. Weight: Heavy Traffic.>

Retain paragraph below if required. Verify requirements of authorities having jurisdiction.

1. INSTALLATION

A. Comply with CRI 104.

B. Installation Method: Double glue-down to bathrooms and stretch in place to hallway and lobby

C. Maintain uniformity of carpet direction and lay of pile. At doorways, center seams under door in closed position. Bind or seal cut edges as recommended by carpet manufacturer.

D. Install pattern parallel to walls and borders.

END OF SECTION 09680

Copyright 2005 by The American Institute of Architects (AIA)

PLASTIQUE SP COMPARTMENTS

PART 1 - GENERAL

1.1 SECTION INCLUDES

A. Floor to ceiling pilasters (Gramercy style).

B. Urinal screens.

1.2 QUALITY ASSURANCE

A. Source: Provide partitions and screens which are the products of one manufacturer.

B. Coordination: Coordinate related work such as concealed blocking to ensure proper location and quantity.

1.3 SUBMITTALS

A. Product Data: Submit manufacturer’s product data, installation details, and catalog cuts for partitions, hardware and accessories.

B. Shop Drawings: Provide shop drawings for field measurements, fabrication, installation and erection of all parts of the work.

C. Manufacturer’s Installation Instructions: Provide details of hardware locations and drilling dimensions.

1.4 FIELD MEASUREMENTS

A. Verify that field measurements are as indicated on shop drawings. Advise manufacturer of any changes.

1.5 DELIVERY, STORAGE AND HANDLING

A. Deliver materials and products in unopened factory labeled packages. Store and handle in strict compliance with manufacturer’s instructions and recommendations. Protect from all possible damage. Inspect cartons at the time of delivery and advise carrier of any damage immediately.

PART 2 - PRODUCTS

2.01 ACCEPTABLE MANUFACTURERS

A. Knickerbocker Partition Corporation or approved equal

2.02 MATERIALS AND PRODUCTS

A. All material shall be constructed of high density solid polyethylene plastic (HDPE) which is non-absorbent, waterproof, with a self lubricating surface which resists graffiti.

1. Panels, Urinal Screens and Doors: Shall be 1” thick, in colors that extend from the surface through the entire core. Doors and panels shall be a minimum of 55” high and extend 14” off the floor. All edges are to be machined and all sharp corners to be removed. Bottom edges shall have an aluminum heat-sinc strip.

2. Gramercy Pilasters: Shall be 1” thick, constructed the same as the panels, doors and urinal screens. Both the top and the bottom of the pilasters shall have adjustable anchors and leveling devices. Anchor studs and locking nuts are designed to firmly secure the pilaster to the floor and ceiling. Both assemblies to be concealed with 4” high stainless steel plinths, secured in place with one-way thru bolts.

3. Hardware and Fittings: Panels and pilasters shall be attached to one another and/or to walls with Zamac chrome plated brackets. Doors shall be equipped with Knickerbocker Ever Life Spring Activated Non-Rising Hinges. Top hinge pivot door bracket to be recessed and inset into edge of door, approximately 2” below the top with a steel pivot pin, operating on a self-lubricating bushing, mounted within the door structure, supported both above and below the pivot bracket. Operation of door shall be controlled by opposing cams under spring tension, mounted on a fixed vertical pintle. Hinges to be adjustable to permit door to rest at any angle, or to hold door open or closed when not latched. Hinges shall operate without raising or lowering the door on a fixed horizontal plane. Each door shall be equipped with stop and keeper, combination coat hook and bumper and concealed latch, featuring a latch cover which permits access to the compartment in case of emergency. Handicap door to be equipped with Knickerbocker Partition Corporation Lever Handle. Design to comply with ADA requirements. Hinge bracket and stops shall have clamp flanges to transmit the strain of door closing to the pilaster. All hardware shall be heavy one-piece, non-ferrous “Zamac” casting, heavily chrome plated. Hinges, stop and keeper, pilaster and panel brackets shall be thru bolted with sex bolts having theft-resistant heads.

B. FINISH: Mocha SP 550K or similar approved.

PART 3 - EXECUTION

3.01 INSTALLATION

A. Install partitions secure, rigid, plumb and level in accordance with manufacturer’s instructions.

B. Maintain manufacturer’s recommended spacing between wall and panels, and between wall and pilasters.

C. Attach panels and pilasters to brackets with theft-resistant one-way thru bolted screws.

D. Equip each door with hinges, concealed lock, coat hook and bumper, door strike and keepers. Outswing doors shall have a door pull and wall bumper.

3.02 ADJUSTMENT

A. Adjust operating parts to work easily, smoothly and correctly.

B. Adjust and align hardware to uniform clearance at vertical edge of doors, not exceeding 3/16 inch.

C. Adjust hinges to position inswing doors at a 30 degree angle to pilasters and outswing doors to a fully closed position.

END OF SECTION 10155

Copyright 2005 by The American Institute of Architects (AIA)

GENERAL

2. SECTION REQUIREMENTS

A. Submittals: Product Data.

PRODUCTS

1. MATERIALS

For a proprietary or semiproprietary specification, delete material descriptions below that are determined by manufacturers' product designations.

A.

B. Brass: ASTM B 19, ASTM B 16, or ASTM B 30.

C. Aluminum: ASTM B 221, Alloy 6063-T6 or 6463-T6.

D. Sheet Steel: ASTM A 1008/A 1008M, 0.0359-inch minimum nominal thickness.

E. Galvanized-Steel Sheet: ASTM A 653/A 653M, G60.

F. Chromium Plating: ASTM B 456, Service Condition Number SC 2 (moderate service).

G. Baked-Enamel Finish: Factory-applied, gloss-white, baked-acrylic-enamel coating.

H. Tempered Glass: ASTM C 1048, Kind FT (fully tempered).

I. Mirrors: ASTM C 1503, Mirror Glazing Quality, clear-glass mirrors, nominal 6.0 mm thick.

J. Galvanized-Steel Mounting Devices: ASTM A 153/A 153M, hot-dip galvanized after fabrication.

K. Fasteners: Screws, bolts, and other devices of same material as accessory unit, tamper and theft resistant when exposed, and of galvanized steel when concealed.

L. Keys: Provide universal keys for internal access to accessories for servicing and resupplying. Provide minimum of 6 keys to Owner's representative.

2. TOILET AND BATH ACCESSORIES

A. Toilet Tissue Dispenser

1. Basis-of-Design Product: BoBrick, B-2892 Classic Series, Surface Moiunted, Twin jumbo Roll Toilet Tissue Dispenser.

2. Type: Roll-in-reserve dispenser with hinged front secured with tumbler lockset

3. Mounting: Surface mounted with concealed anchorage

4. Material: Satin Finished Stainless Steel

Controlled-delivery units cannot be used at accessible toilets.

5.

6. Capacity: 2 Jumbo rolls

B. Mirror Unit for bathroom:

1. Basis-of-Design Product: Custom sized framed, glass mirror,

C. Baby Changing Station: (Add: Alternate 3)

1. Basis-of-Design Product: Rubbermaid 7819-88 Vertical Baby Changing Station

2 Type: Manual.

3 Mounting: Surface.

4 Material: Plastic

EXECUTION

1. INSTALLATION

A. Install accessories using fasteners appropriate to substrate indicated and recommended by unit manufacturer. Install units level, plumb, and firmly anchored in locations and at heights indicated.

B. Adjust accessories for unencumbered, smooth operation and verify that mechanisms function properly. Replace damaged or defective items. Remove temporary labels and protective coatings.

END OF SECTION 10801

Copyright 2005 by The American Institute of Architects (AIA)

GENERAL

1. SECTION REQUIREMENTS

A. System Description: removal and relocation of existing Fire Alarm sounder and switch

PRODUCTS

A. Existing to be relocated

1. ALARM-INITIATING DEVICES

A. Existing to be relocated

END OF SECTION 13851

Copyright 2005 by The American Institute of Architects (AIA)

GENERAL

2. SECTION REQUIREMENTS

A. Submittals: Product Data for each type of plumbing insulation material.

B. Quality Assurance: Labeled with maximum flame-spread index of 25 and maximum smoke-developed index of 50 according to ASTM E 84.

PRODUCTS

1. INSULATION MATERIALS

A. Flexible Elastomeric: Closed-cell, sponge- or expanded-rubber materials. Comply with ASTM C 534, Type I for tubular materials and Type II for sheet materials.

B. Factory-Applied Jackets: When factory-applied jackets are indicated, comply with the following:

1. ASJ: White, kraft-paper, fiberglass-reinforced scrim with aluminum-foil backing; complying with ASTM C 1136, Type I.

2. FSK Jacket: Aluminum-foil, fiberglass-reinforced scrim with kraft-paper backing; complying with ASTM C 1136, Type II.

C. ASJ Tape: White vapor-retarder tape matching factory-applied jacket with acrylic adhesive, complying with ASTM C 1136.

D. FSK Tape: Foil-face, vapor-retarder tape matching factory-applied jacket with acrylic adhesive; complying with ASTM C 1136.

EXECUTION

1. PIPE INSULATION INSTALLATION

A. Comply with requirements of the Midwest Insulation Contractors Association's "National Commercial & Industrial Insulation Standards" for insulation installation on pipes and equipment.

B. Insulation Installation at Interior Wall and Partition Penetrations (That Are Not Fire Rated): Install insulation continuously through walls and partitions.

C. Flexible Elastomeric Insulation Installation:

1. Seal longitudinal seams and end joints with adhesive to eliminate openings in insulation that allow passage of air to surface being insulated.

2. Insulation Installation on Pipe Fittings and Elbows: Install mitered sections of pipe insulation. Secure insulation materials and seal seams with adhesive to eliminate openings in insulation that allow passage of air to surface being insulated.

D. Interior Piping System Applications: Insulate the following piping systems:

1. Domestic hot water.

2. Recirculated domestic hot water.

3. Roof drain bodies and horizontal rainwater leaders of storm water piping.

4. Exposed water supplies and sanitary drains of fixtures for people with disabilities.

E. Do not apply insulation to the following systems, materials, and equipment:

1. Flexible connectors.

2. Sanitary drainage and vent piping.

3. Drainage piping located in crawlspaces unless otherwise indicated.

4. Chrome-plated pipes and fittings, except for plumbing fixtures for people with disabilities.

5. Piping specialties, including air chambers, unions, strainers, check valves, plug valves, and flow regulators.

2. INDOOR PIPING INSULATION SCHEDULE

A. Unless otherwise indicated, do not install insulation on the following:

1. Drainage piping located in crawlspaces.

2. Underground piping.

3. Chrome-plated pipes and fittings unless there is a potential for personnel injury.

END OF SECTION 15082

Copyright 2005 by The American Institute of Architects (AIA)

GENERAL

3. SECTION REQUIREMENTS

A. Submittals: Product Data for each type of HVAC insulation material.

B. Quality Assurance: Labeled with maximum flame-spread index of 25 and maximum smoke-developed index of 50 according to ASTM E 84.

PRODUCTS

1. INSULATION MATERIALS

A. Flexible Elastomeric: Closed-cell, sponge- or expanded-rubber materials. Comply with ASTM C 534, Type I for tubular materials and Type II for sheet materials.

B. Flexible Elastomeric and Polyolefin Adhesive: Comply with MIL-A-24179A, Type II, Class I.

C. Mineral-Fiber Adhesive: Comply with MIL-A-3316C, Class 2, Grade A.

D. Vapor-Barrier Mastic: Water based; suitable for indoor and outdoor use on below ambient services.

E. ASJ Tape: White vapor-retarder tape matching factory-applied jacket with acrylic adhesive, complying with ASTM C 1136.

F. FSK Tape: Foil-face, vapor-retarder tape matching factory-applied jacket with acrylic adhesive; complying with ASTM C 1136.

EXECUTION

1. INSULATION INSTALLATION

A. Comply with requirements of the Midwest Insulation Contractors Association's "National Commercial & Industrial Insulation Standards" for insulation installation on pipes and equipment.

B. Insulation Installation at Interior Wall and Partition Penetrations (That Are Not Fire Rated): Install insulation continuously through walls and partitions.

C. Insulation Installation at Fire-Rated Wall, Partition, and Floor Penetrations: Install insulation continuously through penetrations. Seal penetrations. Comply with requirements in Division 7 Section "Through-Penetration Firestop Systems."

D. Flexible Elastomeric Insulation Installation:

1. Seal longitudinal seams and end joints with adhesive to eliminate openings in insulation that allow passage of air to surface being insulated.

2. Insulation Installation on Pipe Fittings and Elbows: Install mitered sections of pipe insulation. Secure insulation materials and seal seams with adhesive to eliminate openings in insulation that allow passage of air to surface being insulated.

E. Plenums and Ducts Requiring Insulation:

1. Concealed and exposed supply and outdoor air.

2. Concealed and exposed return air located in nonconditioned space.

3. Concealed and exposed exhaust between isolation damper and penetration of building exterior.

F. Plenums and Ducts Not Insulated:

1. Metal ducts with duct liner.

2. Factory-insulated plenums and casings.

3. Flexible connectors.

4. Vibration-control devices.

5. Factory-insulated access panels and doors.

G. Piping Not Insulated: Unless otherwise indicated, do not install insulation on the following:

1. Drainage piping located in crawlspaces.

2. Underground piping.

3. Chrome-plated pipes and fittings unless there is a potential for personnel injury.

2. HVAC PIPING INSULATION SCHEDULE

A. Chilled Water: Insulation shall be[ one of] the following:

1. Flexible Elastomeric: 1 inch > 1/2"thick.

B. Refrigerant Suction and Hot-Gas Piping: Insulation shall be the following:

1. Flexible Elastomeric: 1 inch thick.

END OF SECTION 15083

Copyright 2005 by The American Institute of Architects (AIA)

GENERAL

3. SECTION REQUIREMENTS

A. Submittals: Product Data for each type of plumbing fixture, including trim, fittings, accessories, appliances, appurtenances, equipment, and supports.

B. Regulatory Requirements: Comply with requirements in ICC A117.1, "Accessible and Usable Buildings and Facilities Regulatory Requirements: Comply with requirements in Public Law 102-486, "Energy Policy Act," about water flow and consumption rates for plumbing fixtures.

C. NSF Standard: Comply with NSF 61, "Drinking Water System Components - Health Effects," for fixture materials that will be in contact with potable water.

PRODUCTS

Copy and edit Part 2 articles below for fixture types required. Insert specific requirements for reinforcements if applicable.

1.

A. Vitreous-China Water Closet:

1. Basis-of-Design Product: American Standard, Madeira 1.6gpf Less Everclean> or approved equal:

a. American Standard

2. Design Consumption: 1.6 gal./flush (6 L/flush

B. Toilet Seat: open front class.

1. Basis-of-Design Product: American Standard 5905.110 or approved equal:

a. American Standard

C. Flushometer Valve: Brass body, brass or copper pipe or tubing inlet with wall flange and tailpiece with spud, screwdriver check stop, and vacuum breaker. Polished, chrome-plated, exposed metal parts. Consumption: 1.6 gal./flush (6.0 L/flush).

1. Basis-of-Design Product: American Standard Chrome Plated Flushometer or approved equal:

a. American Standard

2. URINAL

A. Vitreous-China Urinal: Accessible, wall mounting, back-outlet, siphon-jet type or approved equal:.

1. Basis-of-Design Product: American Standard Trimbrook Urinal, color white, 6561.017 Top Spud or comparable product by one of the following:

a. American Standard

2. Design Consumption: 0.5 gal./flush (1.9 L/flush).

B. Flushometer Valve: Cast-brass body, brass or copper pipe or tubing inlet with wall flange and tailpiece with spud, screwdriver check stop, and vacuum breaker. Polished, chrome-plated, exposed metal parts. Consumption: 0.5 gal./flush (1.9 L/flush) or approved equal:.

C. Fixture Support: Type II, with hanger and bearing plates

3. LAVATORY

A. Enameled, Cast-Iron undermounted

1. Basis-of-Design Product: Kohler Ledges or approved equal:

a. Kohler

B. Faucets: ASME A112.18.1; solid-brass underbody and brass cover plate

C. Basis-of-Design Product: American Standard Selectronic DC powered single inlet 6055.102 Selectronic Electronic Proximity lavatory faucet with American Standard 605XTMV Mixing Valve or approved equal:

a. American Standard

1. Finish: Polished chrome-plate.

2. Flow Rate: 0.5 gpm (1.5 L/min

D. Trap: Chrome-plated with slip-joint inlet and wall flange.

2.4 VANITY

F. A. 1. New Salem Woodworking, Short Apron Open Style Vanity without Drawer, Country Sheraton Legs and finished in Cherry to match Mirror Surround Trim. Vanity to receive separate granite top and back and side splashes or approved equal:.

EXECUTION

1. INSTALLATIONS

A. Install fitting insulation kits on fixtures for people with disabilities.

B. Install fixtures with flanges and gasket seals.

C. Install flushometer valves for accessible water closets and urinals with handle mounted on wide side of compartment. Install other actuators in locations that are easy for people with disabilities to reach.

D. Install tanks for accessible, tank-type water closets with lever handle mounted on wide side of compartment.

E. Fasten wall-hanging plumbing fixtures securely to supports attached to building substrate when supports are specified, and to building wall construction where no support is indicated.

F. Fasten floor-mounted fixtures to substrate. Fasten fixtures having holes for securing fixture to wall construction, to reinforcement built into walls.

G. Fasten wall-mounted fittings to reinforcement built into walls.

H. Fasten counter-mounting plumbing fixtures to casework.

I. Secure supplies to supports or substrate within pipe space behind fixture.

J. Set shower receptors and mop basins in leveling bed of cement grout.

K. Install individual supply inlets, supply stops, supply risers, and tubular brass traps with cleanouts at fixture.

L. Install water-supply stop valves in accessible locations.

M. Install traps on fixture outlets. Omit traps on fixtures having integral traps. Omit traps on indirect wastes unless otherwise indicated.

N. Install disposers in sink outlets. Install switch where indicated, or in wall adjacent to sink if location is not indicated.

O. Install hot-water dispensers in back top surface of sink or in counter with spout over sink.

P. Install escutcheons at wall, floor, and ceiling penetrations in exposed, finished locations and within cabinets and millwork. Use deep-pattern escutcheons where required to conceal protruding pipe fittings.

Q. Seal joints between fixtures and walls, floors, and counters using sanitary-type, one-part, mildew-resistant, silicone sealant. Match sealant color to fixture color.

R. Install piping connections between plumbing fixtures and piping systems and plumbing equipment. Install insulation on supplies and drains of fixtures for people with disabilities.

S. Ground equipment.

END OF SECTION 15410

Copyright 2005 by The American Institute of Architects (AIA)

GENERAL

2. SECTION REQUIREMENTS

A. Submittals: Product Data for each luminaire, including lamps.

B. Fixtures, Emergency Lighting Units, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

C. Coordinate ceiling-mounted luminaires with ceiling construction, mechanical work, and security and fire-prevention features mounted in ceiling space and on ceiling.

PRODUCTS

1. BALLASTS

Select ballast type in first paragraph below to specify the default ballast type for linear fluorescent lamps. Note that most projects will have some applications for linear fixtures requiring ballasts other than the default type selected below. For such fixtures, indicate the ballast type in the Interior Lighting Fixture Schedule on Drawings.

A.

1. Lamp end-of-life detection and shutdown circuit.

2. Automatic lamp starting after lamp replacement.

3. Sound Rating: Amperes.

4. BF: 0.95 or higher unless otherwise indicated.

5. Power Factor: 0.95 or higher.

B. Internal-Type Emergency Fluorescent Power Unit: Self-contained, modular, battery-inverter unit, factory mounted within lighting fixture body and compatible with ballast. Comply with UL 924.

Retain first subparagraph below if night-light connections are used. If used, differentiate two connection modes on Drawings or in the Interior Lighting Fixture Schedule on Drawings.

1.

2. Battery: Sealed, maintenance-free, nickel-cadmium type.

3. Charger: Fully automatic, solid-state, constant-current type with sealed power transfer relay.

Retain first subparagraph below if Project includes pulse-start, metal-halide fixtures with electronic ballasts. See Evaluations for discussion.

4.

a. Lamp end-of-life detection and shutdown circuit.

b. Total Harmonic Distortion Rating: Less than 15 percent.

c. Transient Voltage Protection: IEEE C62.41, Category A or better.

2. EMERGENCY LIGHTING UNITS

A. Description: Self-contained units complying with UL 924.

1. Battery: Sealed, maintenance-free, lead-acid type.

2. Charger: Fully automatic, solid-state type with sealed transfer relay.

3. Test Push Button: Push-to-test type, in unit housing, simulates loss of normal power and demonstrates unit operability.

4. LED Indicator Light: Indicates normal power on. Normal glow indicates trickle charge; bright glow indicates charging at end of discharge cycle.

3. LAMPS

A. Compact Fluorescent Lamps: 4-Pin, CRI 80 (minimum), color temperature 3500 average rated life of 10,000 hours at 3 hours operation per start, and suitable for use with dimming ballasts unless otherwise indicated.

1. 13 W: T4, double or triple tube, rated 900 initial lumens (minimum).

2. 18 W: T4, double or triple tube, rated 1200 initial lumens (minimum).

3. 26 W: T4, double or triple tube, rated 1800 initial lumens (minimum).

Low-mercury products may not be available in higher-wattage products in three subparagraphs below. Consult manufacturers.

4.

5. 42 W: T4, triple tube, rated 3200 initial lumens (minimum).

6. 55 W: T4, triple tube, rated 4300 initial lumens (minimum).

4. REQUIREMENTS FOR INDIVIDUAL LIGHTING FIXTURES

Copy and revise this article for each fixture type. Delete if information is shown on Drawings.

G. |  Model #: H27RICAT or approved equal:.

A.

B. Basis-of-Design Product: Subject to compliance with requirements, provide 5" recessed ceiling fitting or comparable product by one of the following or approved equal:

a. Halo

1. Voltage: 120V ac.

2. Mounting: Recessed ceiling

3. Nominal Dimensions: 6" inches (150 mm).>

4. Lamps: Max 75W

EXECUTION

1. INSTALLATION

A. Set units level, plumb, and square with ceiling and walls, and secure.

Revise first two paragraphs below as required for seismic areas.

B.

1. Install ceiling support system wires at a minimum of 4 wires for each fixture, located not more than 6 inches (150 mm) from fixture corners.

2. Support Clips: Fasten to fixtures and to ceiling grid members at or near each fixture corner with clips that are UL listed for the application.

C. Suspended Lighting Fixture Support:

1. Pendants and Rods: Where longer than 48 inches (1200 mm), brace to limit swinging.

2. Stem-Mounted, Single-Unit Fixtures: Suspend with twin-stem hangers.

3. Continuous Rows: Use tubing or stem for wiring at one point and tubing or rod for suspension for each unit length of fixture chassis, including one at each end.

D. Air-Handling Fixtures: Install with dampers closed.

E. Adjust aimable lighting fixtures to provide required light intensities.

F. Lamping: Where specific lamp designations are not indicated, lamp units according to manufacturer's written instructions.

END OF SECTION 16500

Copyright 2005 by The American Institute of Architects (AIA)

GENERAL

2. SECTION REQUIREMENTS

A. Summary: Paint exposed surfaces, new and existing, unless otherwise indicated.

1. Paint the back side of access panels.

2. Color-code mechanical piping in accessible ceiling spaces.

3. Do not paint prefinished items, items with an integral finish, operating parts, and labels unless otherwise indicated.

B. Submittals:

1. Product Data. Include printout of "MPI Approved Products List" with product highlighted.

2. Samples.

C. MPI Standards:

1. Products: Complying with MPI standards indicated and listed in "MPI Approved Products List."

For renovation projects, consult "MPI Maintenance Repainting Manual" and revise subparagraph below and paint systems specified in Part 3.

2.

D. Extra Materials: Deliver to Owner 1 gal. of each color and type of finish coat paint used on Project, in containers, properly labeled and sealed.

PRODUCTS

1. PAINT

A. Products: Sherwin Williams or equal approved

Delete two paragraphs below if specific products are named for manufacturers inserted above. Coordinate products with types specified in application schedules in Part 3.

B.

1. For each coat in a paint system, provide products recommended in writing by manufacturers of topcoat for use in paint system and on substrate indicated.

C. Colors: as approved by the owner.

EXECUTION

1. PREPARATION

A. Remove hardware, lighting fixtures, and similar items that are not to be painted. Mask items that cannot be removed. Reinstall items in each area after painting is complete.

B. Clean and prepare surfaces in an area before beginning painting in that area. Schedule painting so cleaning operations will not damage newly painted surfaces.

C. All surfaces interior or exterior to be painted are to be thoroughly sanded prior to painting and between coats to ensure a smooth flat consistent finish to the final painted surface.

D. Where filling is required, a proprietary filler for the location must be used, it is to be allowed to dry prior to sanding to ensure a smooth invisible , crack free repair.

2. APPLICATION

A. Apply paints according to manufacturer's written instructions.

1. Use brushes only for exterior painting and where the use of other applicators is not practical.

2. Use rollers for finish coat on interior walls and ceilings.

B. Apply paints to produce surface films without cloudiness, spotting, holidays, laps, brush marks, roller tracking, runs, sags, ropiness, or other surface imperfections. Cut in sharp lines and color breaks.

1. If undercoats or other conditions show through topcoat, apply additional coats until cured film has a uniform paint finish, color, and appearance.

C. Apply stains and transparent finishes to produce surface films without color irregularity, cloudiness, holidays, lap marks, brush marks, runs, ropiness, or other imperfections. Use multiple coats to produce a smooth surface film of even luster.

3. EXTERIOR PAINT APPLICATION SCHEDULE

A. Dressed Lumber: Including architectural woodwork, and doors.

1. Trim, Semigloss Latex: Two coats over one primer coat: Top coats to be Duration paint or similar approved.

B. Wood Sidewall Shingles :

1. Siding and Painted Shingle: Flat Latex: Two coats over one primer coats:

4. INTERIOR PAINT APPLICATION SCHEDULE

A. Dressed Lumber: Including architectural woodwork, and doors

1. Semigloss Latex: Two coats over 1 primer coat:

B. Gypsum Board and Plaster:

1. Flat Latex: Two coats over primer/sealer:

END OF SECTION 09910

................
................

In order to avoid copyright disputes, this page is only a partial summary.

Google Online Preview   Download