FAAST A/E Specifications - Honeywell
The sample port spacing shall not exceed 200 sq. ft. (18.5 sq. m) and shall initiate an alarm/alert in less than 60 seconds from the furthest sample port. The detector shall be programmed to pre-alarm at .2% obscuration per foot and alarm at 1% obscuration per foot at the sample port. ................
................