MOBILE HOME POLES - TVEC

MOBILE HOME POLES

TVEC WILL SPOT ALL MOBILE HOME POLES

MINIMUM CLEARANCE REQUIREMENTS

MINIMUM OF 12' HEIGHTH TO WEATHERHEAD

AND MUST BE WITHIN 24" OF EYEBOLT

18' MINIMUM CLEARANCE IS REQUIRED

OVER PUBLIC ROADWAYS

MINIMUM 18" TAILS FOR CONNECTION

16' MINIMUM CLEARANCE IS REQUIRED

OVER DRIVEWAYS

200 AMP: USE 2/0 THW HOTLEGS, WITH

#1 NEUTRAL STRANDED COPPER

CONDUCTORS OR EQUIVALENT

NON-CORROSIVE STRAPS WITH LAG BOLTS

OR ADEQUATE SCREWS PLACED EVERY 4'

12' MINIMUM CLEARANCE IS REQUIRED

OVER PEDESTRIAN AREAS

MINIMUM 16', TREATED, ROUND POLE

WITH 5" MINIMUM TOP DIAMETER

2" RIGID OR SCHEDULE 80 PVC CONDUIT

#4 SOLID COPPER FOR 200 AMP SERVICE

#6 SOLID COPPER FOR 100 AMP SERVICE

200

200 AMP WEATHERPROOF MAIN SERVICE

RATED FOR SERVICE EQUIPMENT WITH

PROVISIONS FOR ADDITIONAL BREAKERS

2" FLEXIBLE

A 120V GFCI WITH IN-USE COVER MAY BE

INSTALLED BUT IS NOT REQUIRED

MULTIPLE POINT GROUNDING BLOCK

GROUND WIRE TO GO FROM GROUND TO

METER BASE, UNBROKEN FOR CONNECTION,

ATTACHED EVERY 18" WITH MINIMUM 1"

CLAMPS.

OR RIGID

GALVANIZED STEEPLES OR WIRE HOLDING

5 1/2' FROM GROUND TO CENTER OF METER

FLEXIBLE CONDUIT INSTALLATIONS MAY BE NO

MORE THAN 12" FROM THE POLE TO THE HOME

CONDUIT

APPROVED GROUND ROD CLAMP

5/8 X 8' GALVANIZED GROUND ROD

IF MORE THAN 50' FROM SERVICE POLE

CONCRETE OR GUYING REQUIRED

IF GUYING IS REQUIRED A MINIMUM 1/2"

ROD SCREW ANCHOR SHALL BE USED.

CUSTOMER IS RESPONSIBLE FOR GUYING

CONCRETE AROUND

POLE IF MORE THAN 50'

FROM SERVICE POLE

GROUND LEVEL



USE 2/0 THW HOTLEGS, WITH A #1 NEUTRAL

AND #6 BOND STRANDED COPPER CONDUCTOR

OR EQUIVALENT IN 2" FLEX OR RIGID CONDUIT

4' BURIED DEPTH

All wiring must meet State of Tennessee wiring

code and the National Electric Code (NEC).

TVEC will not connect to a meter pole until

approved by Tennessee deputy state inspector

JANUARY 2016

................
................