Standard for the Inspection, Testing, and Maintenance of ...
Errata
NFPA 25
Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems
2017 Edition
Reference: Various Errata No: 25-17-1
The Technical Committee on Inspection, Testing, and Maintenance of Water-Based Protection Systems notes the following errors in the 2017 edition of NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems.
1. In Table 5.1.1.2, correct the cross references to read as follows:
Table 5.1.1.2 Summary of Sprinkler System Inspection, Testing, and Maintenance
Item
Frequency
Inspection
Control valves
Fire department connections
Gauges (wet and deluge systems) Quarterly
Gauges (dry and preaction systems)
Monthly/quarterly
Hanger/braces/supports
Annually
Heat tracing
Per manufacturer's requirements
Hydraulic design information sign Annually
Information signs
Annually
Internal piping condition
Pipe and fittings
Annually
Sprinklers
Annually
Sprinklers (spare)
Annually
Reference
Chapter 13 Chapter 13 Chapter 13 Chapter 13
5.2.3 5.2.76 5.2.65 5.2.7, 5.2.8, 5.2.9 Chapter 14 5.2.2 5.2.1 5.2.1.4
Supervisory signal devices (except Quarterly valve supervisory switches)
System valves
Valve supervisory signal devices Quarterly
Waterflow alarm devices
Quarterly
Test
Antifreeze solution
Annually
Control valves
Gauges
5 years
Main drain
Sprinklers
At 50 years and every 10 years thereafter
Sprinklers
At 75 years and every 5 years thereafter
Sprinklers (dry)
10 years and every 10 years thereafter
Sprinklers (extra high or greater 5 years temperature solder type)
Sprinklers (fast-response)
At 20 years and every 10 years thereafter
Sprinklers (harsh environments) 5 years
Supervisory signal devices (except valve supervisory switches)
System valves
Valve supervisory signal devices
Waterflow alarm devices (Mechanical)
Quarterly
Waterflow alarm devices (vane and pressure switch type)
Semiannually
Maintenance
Low-point drains (dry pipe and preaction systems)
Sprinklers and automatic spray Annually nozzles protecting commercial cooking equipment and ventilation systems
Valves (all types)
Investigation
Obstruction
5.2.54 Chapter 13 5.2.54 5.2.54
5.3.43 Chapter 13 Chapter 13 Chapter 13 5.3.1.1.1, 5.3.1.1.1.1, 5.3.1.1.1.2 5.3.1.1.1.5 5.3.1.1.1.6 5.3.1.1.1.4 5.3.1.1.1.3 5.3.1.1.2 Chapter 13 Chapter 13 Chapter 13 5.3.32.1 5.3.32.2
Chapter 13 5.4.1.7
Chapter 13
Chapter 14
2. In Table 6.1.1.2, correct the cross references to read as follows:
Table 6.1.1.2 Summary of Standpipe and Hose Systems Inspection, Testing, and Maintenance
Item
Frequency
Inspection
Cabinet
Annually
Control valves
Gauges
Weekly/quarterly
Hose
Annually
Hose connection
Annually
Hose nozzle
Annually and after each use
Hose storage device
Annually
Hydraulic design information sign Annually
Hose valves
Hose connection
Annually
Piping
Annually
Pressure-regulating devices
Test
Flow test
5 years
Hose
5 years/3 years
Hose connections
Annually
Hose valves
Hydrostatic test
5 years
Main drain test
Pressure control valve
Pressure-reducing valve
Supervisory signal devices (except valve supervisory switches)
Valve status test
Valve supervisory devices
Waterflow alarm devices
Maintenance
Hose connections
Annually
Hose valves
Valves (all types)
Annually/as needed
Reference
6.2.18 Chapter 13 Chapter 13 NFPA 19626.2.5 6.2.13 NFPA 19626.2.6 6.2.17 6.2.32 Chapter 13 6.2.1 6.2.14 Chapter 13
6.3.1 NFPA 1962 6.2.1 Chapter 13 6.3.2 Chapter 13 Chapter 13 Chapter 13 Chapter 13
Chapter 13 Chapter 13 Chapter 13
Table 6.1.2 Chapter 13 Chapter 13
3. Correct the cross references in 8.3.3.6.3.3 and 8.3.3.6.3.4 to read as follows:
8.3.3.6.3.3 If the test results are not consistent with the previous annual test, the test shall be repeated using the test arrangement described in 8.3.3.6.3.1. 8.3.3.6.3.4 If testing in accordance with 8.3.3.6.3.1 is not possible, a flowmeter calibration shall be performed and the test shall be repeated.
4. In Table 9.1.1.2, correct the cross references to read as follows:
Table 9.1.1.2 Summary of Water Storage Tank Inspection, Testing, and Maintenance
Item
Inspection
Air pressure--tanks that have their air pressure source supervised
Air pressure--tanks without their air pressure source supervised
Catwalks and ladders
Check valves
Control valves
Expansion joints
Heating system -- tanks with supervised low temperature alarms connected to constantly attended location
Heating system -- tanks without supervised low temperature alarms connected to constantly attended location
Hoops and grillage
Interior -- all other tanks
Interior -- steel tanks without corrosion protection
Painted/coated surfaces
Support structure
Surrounding area
Tank -- exterior
Temperature alarms -- connected to constantly attended location
Temperature alarms -- not connected to constantly attended location
Water level -- tanks equipped with supervised water level alarms connected to constantly attended location
Frequency
Quarterly Monthly Quarterly
Annually Weekly*
Daily*
Annually 5 years 3 years Annually Quarterly Quarterly Quarterly Monthly* Weekly* Quarterly
Reference
9.2.2.1
9.2.2.2
9.2.54.1 Chapter 13 Chapter 13 9.2.54.3 9.2.32.1
9.2.32.2
9.2.54.4 9.2.65.1.2 9.2.65.1.1
9.2.54.5 9.2. 54.1 9.2. 54.2 9.2. 54.1 9.2.43.2
9.2.4.3
9.2.1.1
Water level -- tanks without supervised water level alarms connected to constantly attended location
Monthly
Water temperature -- low temperature alarms connected to constantly attended location
Monthly
Water temperature -- low temperature alarms not Weekly connected to constantly attended location
Test
High temperature limit switches
Monthly*
Level indicators
5 years
Low water temperature alarms
Monthly*
Pressure gauges
5 years
Tank heating system
Prior to heating season
Valve status test
Water level alarms
Semiannually
Maintenance
Check valves
--
Control valves
--
Embankment-supported coated fabric (ESCF) --
Water level
--
*Cold weather/heating season only.
9.2.1.2
9.2.4.2
9.2.4.3
9.3.4 9.3.1 9.3.3 Chapter 13 9.3.2 Chapter 13 9.3.5
Chapter 13 Chapter 13 9.4.6.2 9.4.2
5. In Table 9.5.1.1, correct the cross references to read as follows:
Table 9.5.1.1 Summary of Automatic Tank Fill Valve Inspection and Testing
Item Inspection Strainers, filters, orifices (inspect/clean) Enclosure (during cold weather) Exterior Interior Test Automatic tank fill valve
Frequency
5 years Daily/weekly Monthly Annually/5 years
Annually
Reference
13.4.1.2 13.4.3.1.1 13.4.3.1.63 13.4.3.1.74
9.5.3
................
................
In order to avoid copyright disputes, this page is only a partial summary.
To fulfill the demand for quickly locating and searching documents.
It is intelligent file search solution for home and business.
Related download
- scoring rubric for oral presentations example 1
- standard for the inspection testing and maintenance of
- rv trailer towing guide ford
- national fire alarm and signaling code
- memorandum for record
- remittance advice details rad codes and messages 001
- application for kentucky certificate of title or registration
- fltmps access and reporting procedures
- assignedprotectionfactors
- department of the air force headquarters air force
Related searches
- find the sample variance and standard deviation
- caterpillar operation and maintenance manual
- the causes and consequences of the holocaust
- of by and for the people
- pros and cons of animal testing peta
- purpose of testing and assessment
- happiness is the meaning and the purpose of life the whole aim and end of human
- nfpa 72 inspection testing form
- nj inspection locations and hours
- operations and maintenance funding rules
- commercial inspection forms and checklists
- advantage and disadvantage of testing animals