Voltage Regulator TAPCON® 230 expert

[Pages:20]Voltage Regulator TAPCON? 230 expert

Supplement

2664024/03 EN . Protocol Specification IEC 61850

? All rights reserved by Maschinenfabrik Reinhausen

Dissemination and reproduction of this document and use and disclosure of its content are strictly prohibited unless expressly permitted.

Infringements will result in liability for compensation. All rights reserved in the event of the granting of patents, utility models or designs.

The product may have been altered since this document was published.

We reserve the right to change the technical data, design and scope of supply.

Generally the information provided and agreements made when processing the individual quotations and orders are binding.

The original operating instructions were written in German.

Table of contents

Table of contents

1

Introduction ......................................................................................................................... 4

1.1 Subject to change without notice ......................................................................................................... 4

1.2 Completeness...................................................................................................................................... 4

1.3 Supporting documents......................................................................................................................... 4

1.4 Safekeeping......................................................................................................................................... 4

2

Physical interfaces.............................................................................................................. 5

3

Setting device parameters ................................................................................................. 7

4

Protocol specification......................................................................................................... 8

4.1 Downloading ICD file ........................................................................................................................... 8

5

Data points......................................................................................................................... 10

5.1 LLN0 class - Logical node ................................................................................................................. 10

5.2 LPHD class (LPHD1) - Physical device ............................................................................................. 10

5.3 AVR - Automatic tap changer controller (ATCC) ............................................................................... 11

5.4 GGIO ? Generic process I/O ............................................................................................................. 15

Glossary............................................................................................................................. 17

Maschinenfabrik Reinhausen 2014

2664024/03 EN

TAPCON? 230 expert

3

1 Introduction

1 Introduction

The technical file contains detailed descriptions for implementing the IEC 61850 interface protocol. This technical file is intended solely for specially trained and authorized personnel.

1.1 Subject to change without notice

The information contained in this technical file comprises the technical specifications approved at the time of printing. Significant modifications will be included in a new edition of the technical file. The document number and version number of this technical file are shown in the footer.

1.2 Completeness

This technical file is incomplete without the supporting documentation.

1.3 Supporting documents

The following documents apply to this technical file: Operating instructions for TAPCON? 230 expert Quick reference guide to TAPCON? 230 expert

1.4 Safekeeping

This technical file and all supporting documents must be kept ready at hand and accessible for future use at all times.

4

TAPCON? 230 expert

2664024/03 EN

Maschinenfabrik Reinhausen 2014

2 Physical interfaces

2 Physical interfaces

The device has been developed in accordance with applicable EMC standards. In regards to complying with EMC standards, please refer to the corresponding chapter on the topic of "Electromagnetic Compatibility" in the device's operating instructions.

You can find additional information on wiring and routing instructions for the fiber-optic cable in the operating instructions for this device.

The following physical interfaces are available on the device for data transmission using the control system protocol:

Network cable via the RJ45 bush

Fiber-optic cable via the LC bush

The device can be connected with plug connector RJ45 via 100BASE-TX or with the optical interface via 100BASE-FX. Only one connection can ever be active at any one time.

Ethernet variant

100BASE-TX

Transmission rate

10?Mbit/s

100?MBit/s (Fast Ethernet)

(Baud rate is established automatically by the device)

Range

100 m

Table 1: Plug connector RJ45 connection details

Ethernet variant

100BASE-FX

Transmission rate

100?MBit/s (Fast Ethernet)

Range

2 km

Optical transmitter

Bandwidth for wavelength: 1261 nm to 1360 nm, typically 1300 nm

Optical receiver

Bandwidth for wavelength: 1261 nm to 1580 nm

Plug type

Duplex LC plug or F-ST (adapter is included)

Cable type

Multimode cable 50/125 m (is recommended) or 62.5/125 m

Table 2: Optical interface connection details

Maschinenfabrik Reinhausen 2014

2664024/03 EN

TAPCON? 230 expert

5

2 Physical interfaces

Figure 1: Voltage regulator connections

1 RJ45 (terminal X12) 2 Fiber-optic cable, LC bush

(terminal X13) 3 RS232 (terminal X11)

4 CAN bus 5 Voltage supply

6

TAPCON? 230 expert

2664024/03 EN

Maschinenfabrik Reinhausen 2014

3 Setting device parameters

3 Setting device parameters

In order to use the control system protocol, you need to set the device parameters.

Please refer to the device's operating instructions for more information regarding setting the device parameters.

You must set the following parameters:

Parameter Network address Network mask Time server address 1 Time server address 2 Gateway IED name Transmission medium

Table 3: Device parameters

RJ45

OF

0.0.0.0...255.255.255.255

0.0.0.0...255.255.255.255

0.0.0.0...255.255.255.255

0.0.0.0...255.255.255.255

0.0.0.0...255.255.255.255

Freely definable

100BASE-TX

100BASE-FX

Maschinenfabrik Reinhausen 2014

2664024/03 EN

TAPCON? 230 expert

7

4 Protocol specification

4 Protocol specification

The device provides an extract of commands and messages from the interface protocol IEC 61850 for communication. Device-specific data points You can find the device-specific data points and presettings in the device's ICD file. You can request the following documents for the device or download from the device: MICS (Model Implementation Conformance Statement) [ 10] PICS (Protocol Implementation Conformance Statement) PIXIT (Protocol Implementation eXtra Information for Testing) TICS (Technical Issues Conformance Statement) Please note possible restrictions and comments regarding device specific data points and default settings listed in the documents above.

4.1 Downloading ICD file

You can download the ICD file via FTP from the device. You have to establish an ethernet connection between the device and your PC. For a smooth download with Windows Vista/7/8 operating systems, use Windows Explorer.

Proceed as follows to download the ICD file: 1. Enter in your browser (in the ex-

ample in the diagram below, the IP adress is 192.168.0.1) and select the directory home/gast.

8

TAPCON? 230 expert

2664024/03 EN

Maschinenfabrik Reinhausen 2014

................
................

In order to avoid copyright disputes, this page is only a partial summary.

Google Online Preview   Download