SECTION 26 32 00 - DOA Home

Provide audio/visual alarm indication to generator control panel and to remote annunciator panel if the generator output circuit breaker(s) or OCPD serving the emergency side of each automatic transfer switch is in the “Tripped or “Open” position. Provide monitoring micro-switches. Provide wiring diagram at equipment submittal. ................
................