SECTION 263213 - PACKAGED ENGINE GENERATOR

Provide harmonic filters on the input to the regulator. Generator output voltage shall be maintained within the limits specified below: 0.8 percent RMS no load, to full load (0.8 to 1.0 PF) with a 5 percent speed change and a 20 deg C (68 deg F) ambient temperature change; transient dip not to exceed 15 percent upon application of full load ... ................
................