MOBILE HOME POLES - TVEC

MOBILE HOME POLES

TVEC WILL SPOT ALL MOBILE HOME POLES

MINIMUM CLEARANCE REQUIREMENTS 18' MINIMUM CLEARANCE IS REQUIRED OVER PUBLIC ROADWAYS 16' MINIMUM CLEARANCE IS REQUIRED OVER DRIVEWAYS 12' MINIMUM CLEARANCE IS REQUIRED OVER PEDESTRIAN AREAS

MINIMUM 16', TREATED, ROUND POLE WITH 5" MINIMUM TOP DIAMETER

MINIMUM OF 12' HEIGHTH TO WEATHERHEAD AND MUST BE WITHIN 24" OF EYEBOLT

MINIMUM 18" TAILS FOR CONNECTION

200 AMP: USE 2/0 THW HOTLEGS, WITH #1 NEUTRAL STRANDED COPPER CONDUCTORS OR EQUIVALENT NON-CORROSIVE STRAPS WITH LAG BOLTS OR ADEQUATE SCREWS PLACED EVERY 4'

2" RIGID OR SCHEDULE 80 PVC CONDUIT

#4 SOLID COPPER FOR 200 AMP SERVICE #6 SOLID COPPER FOR 100 AMP SERVICE

MULTIPLE POINT GROUNDING BLOCK

GROUND WIRE TO GO FROM GROUND TO METER BASE, UNBROKEN FOR CONNECTION, ATTACHED EVERY 18" WITH MINIMUM 1" GALVANIZED STEEPLES OR WIRE HOLDING CLAMPS.

GROUND LEVEL APPROVED GROUND ROD CLAMP 5/8 X 8' GALVANIZED GROUND ROD IF MORE THAN 50' FROM SERVICE POLE CONCRETE OR GUYING REQUIRED

2" FLEXIBLE OR RIGID

200

200 AMP WEATHERPROOF MAIN SERVICE

RATED FOR SERVICE EQUIPMENT WITH

PROVISIONS FOR ADDITIONAL BREAKERS

A 120V GFCI WITH IN-USE COVER MAY BE INSTALLED BUT IS NOT REQUIRED

5 1/2' FROM GROUND TO CENTER OF METER

FLEXIBLE CONDUIT INSTALLATIONS MAY BE NO MORE THAN 12" FROM THE POLE TO THE HOME CONDUIT

USE 2/0 THW HOTLEGS, WITH A #1 NEUTRAL AND #6 BOND STRANDED COPPER CONDUCTOR OR EQUIVALENT IN 2" FLEX OR RIGID CONDUIT

4' BURIED DEPTH

CONCRETE AROUND POLE IF MORE THAN 50'

FROM SERVICE POLE

IF GUYING IS REQUIRED A MINIMUM 1/2" CURSOTDOSMCERREWIS RAENSCPHOONRSISBHLAELFLOBREGUUSYEIDN.G



All wiring must meet State of Tennessee wiring code and the National Electric Code (NEC). TVEC will not connect to a meter pole until approved by Tennessee deputy state inspector

JANUARY 2016

................
................