Factsheet Energy Breakdown - Environment

PEOPLE PRACTICES SYSTEMS

Factsheet HVAC Energy Breakdown

Heating Ventilation and Air Conditioning (HVAC) is generally responsible for a significant proportion of total building energy consumption. A typical system accounts for approximately 40% of total building consumption and 70% of base building (i.e. landlord) consumption. The pie graph in Figure 1 shows the typical energy consumption breakdown of an office building, being 39% HVAC, 25% lighting, 22% equipment, 4% lifts, 1% domestic hot water and 9% other.

Figure 1: Typical energy consumption breakdown in an office building1

9%

1% 4%

39%

HVAC

Lighting

Equipment 22%

Lifts

Domestic Hot Water

Other

25%

There are a number of key end uses in HVAC systems. The bar graph in Figure 2 shows the typical end use breakdown, including:

` Fans for air circulation and ventilation account for 34% of HVAC energy consumption

` Cooling, most frequently the energy use of chillers for the production of cooling via chilled water, but also the use of direct expansion cooling systems such as packaged airconditioners, accounts for 27% of consumption

` Heating, most frequently the energy use of boilers for the production of hot water for heating, but also the use of electric heaters for zonal reheat, accounts for 17% of consumption

` Pumps for the circulation of hot water, chilled water and condenser water, account for 16% of consumption

` Cooling towers for heat rejection, being primarily the cooling tower fan energy, account for 6% of consumption.

MJ/m2

Figure 2: Typical HVAC end use breakdown1

160 34%

140

120

27%

100

80

17%

16%

60

40

20

0 Fans

Cooling Heating Pumps

6%

Cooling Towers

The above breakdown of HVAC energy use is a national average. In practice there is a great deal of variation amongst buildings. This variation is due to a number of factors, including the following:

` Equipment Efficiency ? differences in efficiency can have a radical impact on energy consumption. For some buildings the before-and-after consumption of an individual end use following an efficiency upgrade can vary by a factor of five or more. This is particularly true of fans, which are highly non-linear, and gas, which is often very inefficiently used.

` Building design, orientation and location ? the physical characteristics of a building have a significant impact on building loads and particularly the balance between heating and cooling. For instance, a building with very limited north and west glazing will generally have lower than average cooling loads, while a building with a large unshaded west facade will have high cooling loads, particularly in the afternoons.

` Type of HVAC system ? this can significantly alter the distribution of energy between different end uses. The energy use shown in Figure 2 is typical of the more common airbased air conditioning systems such as variable air volume systems with water cooled chillers. Changes in system type can produce significant changes in end use distribution, examples include:

` Constant volume air-conditioning systems or variable volume systems with poor air-volume controls ? require

1 Guide to Best Practice Maintenance and Operation of HVAC Systems for Energy Efficiency (January 2012), Pages 36?37

HVAC HESS Heating, Ventilation & Air-Conditioning High Efficiency Systems Strategy

September 2013

1

Energy Breakdown

far higher fan energy, upwards of three times that of an equivalent well-tuned variable volume system `

`

`

HVAC HESS

The Heating, Ventilation and Air-Conditioning High Efficiency Systems Strategy (HVAC HESS) is a ten year strategy under the National Strategy on Energy Efficiency that aims to drive long term improvements in energy efficiency of HVAC systems Australia wide. Under The Energy Efficiency Working Group, the Buildings Committee manages the implementation of the HVAC Strategy. This committee is comprised of representatives from Australian, State and Territory Governments.

The Strategy takes a whole of life perspective in targeting HVAC efficiency improvement, encompassing the design, manufacture, installation, operation and maintenance stages of the HVAC lifecycle. The Strategy consists of a number of complementary measures that fall under three broad initiatives ? People, Practices and Systems. This HVAC Energy Breakdown factsheet specifically relates to People. It is one of a suite of factsheets developed to provide a quick overview and reference to inform, educate, and encourage energy efficiency in the HVAC industry.

A series of HVAC HESS factsheets can be found at:

`

` Climate ? while it is true that climate has an impact on the air conditioning requirements of office buildings, the scale of effect is generally far less than commonly believed. This is due to the fact that climate only really impacts on the perimeter of the building, the centre zone being largely buffered from outside influence by the perimeter zone. Nonetheless, it is reasonable to assume that only the colder capitals have significant genuine heating loads in office buildings (the heating loads in Sydney are minimal and essentially non-existent in Brisbane) and that cooling will increase on average from cooler climates to warmer climates.

HVAC HESS Heating, Ventilation & Air-Conditioning High Efficiency Systems Strategy

September 2013

2

................
................