Meter Pole Requirements - Central Alabama Electric Cooperative

[Pages:1]Meter Pole Requirements for Central Al. Electric Cooperative Pole Must be 20' Long, Treated, & 6"x6" Sq. or 6" Round

Weatherhead-Recommended but not Required

Materials Required

100 AMP

Service Entrance Cable Sizes Aluminum---#2 Copper--#4

Service Entrance Cable

100 AMP Meter Socket 100 AMP Main Breaker Panel

11/4" Pipe Nipple

16'

2" Conduit

Min.

Waterproof

Connector

#4 Solid Bare Copper Ground Wire

Meter Socket Furnished by CAEC

5/8"x8' Galvanized or Copper Ground Rod 200 AMP

Galvanized Pipe Nipple

Service Entrance Cable Sizes Aluminum---#4/0 Copper--#2/0

Main Breaker Panel

200 AMP Meter Socket 200 AMP Main Breaker Panel 2" Pipe Nipple

Ground Wire

2" Conduit

2' Min.

Conduit

#4 Solid Bare Copper Ground Wire

5/8"x8' Galvanized or Copper Ground Rod

18" Min.

4'

Ground Rod &

Clamp 8'

Schedule appointment with

Min.

staking engineer for location

of meter pole before installing

Entrance cable to Mobile Home

................
................