RE: Eden Isle WWTP Inspection (Cleburne Co) AFIN: 12-00022 ...

May 9, 2014

Jerry Shuler, Maintenance Supervisor Eden Isle Corporation 335 Sugar Maple Drive Heber Springs, AR 72543

RE: Eden Isle WWTP Inspection (Cleburne Co)

AFIN: 12-00022

NPDES Permit No.: AR0024066

Dear Mr. Shuler:

On April 9, 2014, I performed a routine compliance inspection and Sanitary Sewer Overflow inspection of the above referenced facility in accordance with the provisions of the Federal Clean Water Act, the Arkansas Water and Air Pollution Control Act, and the regulations promulgated thereunder. A copy of the inspection report is enclosed for your records.

Please refer to the "Summary of Findings" section of the attached inspection report and provide a written response for each violation that was noted. This response should be mailed to the attention of the Water Division Inspection Branch at the address at the bottom of this letter or emailed to Water-Inspection-Report@adeq.state.ar.us. This response should contain documentation describing the course of action taken to correct each item noted. This corrective action should be completed as soon as possible, and the written response with all necessary documentation (i.e. photos) is due by May 23, 2014.

If I can be of any assistance, please contact me at saunders@adeq.state.ar.us or (870) 424-3322 ext. 3.

Sincerely,

Sean Saunders District 11 Field Inspector Water Division

Page 1 of 10

Inspection Report: Eden Isle WWTP, AFIN: 12-00022, Permit #: AR0024066

WATER DIVISION INSPECTION REPORT

AFIN: 12-00022 PERMIT #: AR0024066

DATE: 4/9/2014

COUNTY: 12 Cleburne

PDS #: 077695

MEDIA: WN

GPS LAT: 35.511471 LONG: -92.100645 LOCATION: Entrance

FACILITY INFORMATION

NAME:

Eden Isle WWTP

LOCATION:

Overlook Lane

CITY:

Eden Isle, AR

RESPONSIBLE OFFICIAL

NAME: / TITLE

Jim Shuler / Maintenance Supervisor

COMPANY:

Eden Isle WWTP

MAILING ADDRESS:

335 Sugar Maple Dr. Address 2

CITY, STATE, ZIP:

Heber Springs AR 72543

PHONE & EXT: / FAX:

5013626823

/

EMAIL:

INSPECTION INFORMATION

FACILITY TYPE:

1 - Municipal

INSPECTOR ID#:

71153 S - State

FACILITY EVALUATION RATING:

2 - Marginal

DATE(S):

4/9/2014

ENTRY TIME:

11:30

INSPECTION TYPE:

Compliance Evaluation

EXIT TIME:

14:30

PERMIT EFFECTIVE DATE:

2/1/2009

PERMIT EXPIRATION DATE:

1/31/2014

FAYETTEVILLE SHALE RELATED: N

FAYETTEVILLE SHALE VIOLATIONS: N INSPECTION PARTICIPANTS

NAME/TITLE/PHONE/FAX/EMAIL/ETC.:

Steve Upton, Operator, 501-691-9242

CONTACTED DURING INSPECTION: No

AREA EVALUATIONS

(S=Satisfactory, M=Marginal, U=Unsatisfactory, N=Not Applicable/Evaluated)

S PERMIT

U FLOW MEASUREMENT

N STORMWATER

S RECORDS/REPORTS

N LABORATORY

S FACILITY SITE REVIEW

M OPERATION & MAINTENANCE S EFFLUENT/RECEIVING WATER N SELF-MONITORING PROGRAM

S SAMPLING

S SLUDGE HANDLING/DISPOSAL N PRETREATMENT

N OTHER: SUMMARY OF FINDINGS

1. Violations of Part II.B.1 of your permit (see Photos 1-4):

a. The clarifier sweeper arm is not working and needs repaired.

b. There is an extreme amount of paint peeling from the insides of the equalization basin.

c. There was an excessive amount of trash and debris in the aeration basin.

2. Violations of Part III.C.2 of your permit (see Attachment 1):

a. The facility's inline flow meter has not been calibrated since installed on 10/11/2012.

GENERAL COMMENTS On March 16, 2014, there was an overflow of the equalization basin at the facility due to large amounts of inflow and infiltration (I/I) from a large rain event. Please continue to upgrade your system to eliminate these conditions.

INSPECTOR'S SIGNATURE:

Sean Saunders

DATE: 5/5/2014

SUPERVISOR'S SIGNATURE:

Kerri McCabe

DATE: 5/9/2014

Inspection Report Page 2 of 10

Inspection Report: Eden Isle WWTP, AFIN: 12-00022, Permit #: AR0024066

SECTION A: PERMIT VERIFICATION PERMIT SATISFACTORILY ADDRESSES OBSERVATIONS

S M U NA NE

DETAILS:

1. CORRECT NAME AND MAILING ADDRESS OF PERMITTEE: 2. NOTIFICATION GIVEN TO EPA/STATE OF NEW DIFFERENT OR INCREASED DISCHARGES: 3. NUMBER AND LOCATION OF DISCHARGE POINTS AS DESCRIBED IN PERMIT: 4. ALL DISCHARGES ARE PERMITTED:

Y N NA NE Y N NA NE Y N NA NE Y N NA NE

SECTION B: RECORDKEEPING AND REPORTING EVALUATION RECORDS AND REPORTS MAINTAINED AS REQUIRED BY PERMIT DETAILS:

1. ANALYTICAL RESULTS CONSISTENT WITH DATA REPORTED ON DMRS: 2. SAMPLING AND ANALYSES DATA ADEQUATE AND INCLUDE:

a. DATES AND TIME(S) OF SAMPLING: b. EXACT LOCATION(S) OF SAMPLING: c. NAME OF INDIVIDUAL PERFORMING SAMPLING: d. ANALYTICAL METHODS AND TECHNIQUES: e. RESULTS OF CALIBRATIONS: f. RESULTS OF ANALYSES: g. DATES AND TIMES OF ANALYSES: h. NAME OF PERSON(S) PERFORMING ANALYSES: 3. LABORATORY EQUIPMENT CALIBRATION AND MAINTENANCE RECORDS ADEQUATE: 4. PLANT RECORDS INCLUDE SCHEDULES, DATES OF EQUIPMENT MAINTENANCE AND REPAIR: 5. EFFLUENT LOADINGS CALCULATED USING DAILY EFFLUENT FLOW AND DAILY ANALYTICAL DATA:

S M U NA NE

Y N NA NE S M U NA NE

Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE S M U NA NE S M U NA NE Y N NA NE

SECTION C: OPERATIONS AND MAINTENANCE TREATMENT FACILITY PROPERLY OPERATED AND MAINTAINED DETAILS:

1. TREATMENT UNITS PROPERLY OPERATED: 2. TREATMENT UNITS PROPERLY MAINTAINED: Clarifier arm needs replaced or repaired 3. STANDBY POWER OR OTHER EQUIVALENT PROVIDED: 4. ADEQUATE ALARM SYSTEM FOR POWER OR EQUIPMENT FAILURES AVAILABLE: 5. ALL NEEDED TREATMENT UNITS IN SERVICE: 6. ADEQUATE NUMBER OF QUALIFIED OPERATORS PROVIDED: 7. SPARE PARTS AND SUPPLIES INVENTORY MAINTAINED: 8. OPERATION AND MAINTENANCE MANUAL AVAILABLE: 9. STANDARD OPERATING PROCEDURES AND SCHEDULES ESTABLISHED: 10. PROCEDURES FOR EMERGENCY TREATMENT CONTROL ESTABLISHED: 11. HAVE BYPASSES/OVERFLOWS OCCURRED AT THE PLANT OR IN THE COLLECTION SYSTEM IN THE LAST YEAR: 12. IF SO, HAS THE REGULATORY AGENCY BEEN NOTIFIED: 13. HAS CORRECTIVE ACTION BEEN TAKEN TO PREVENT ADDITIONAL BYPASSES/OVERFLOWS: 14. HAVE ANY HYDRAULIC OVERLOADS OCCURRED AT THE TREATMENT PLANT: 15. IF SO, DID PERMIT VIOLATIONS OCCUR AS A RESULT:

S M U NA NE

S M U NA NE S M U NA NE S M U NA NE S M U NA NE S M U NA NE S M U NA NE S M U NA NE

Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE

Inspection Report Page 3 of 10

Inspection Report: Eden Isle WWTP, AFIN: 12-00022, Permit #: AR0024066

SECTION D: SAMPLING PERMITTEE SAMPLING MEETS PERMIT REQUIREMENTS

S M U NA NE

DETAILS:

1. SAMPLES TAKEN AT SITE(S) SPECIFIED IN PERMIT: 2. LOCATIONS ADEQUATE FOR REPRESENTATIVE SAMPLES: 3. FLOW PROPORTIONED SAMPLES OBTAINED WHEN REQUIRED BY PERMIT: 4. SAMPLING AND ANALYSES COMPLETED ON PARAMETERS SPECIFIED IN PERMIT: 5. SAMPLING AND ANALYSES PERFORMED AT FREQUENCY SPECIFIED IN PERMIT: 6. SAMPLE COLLECTION PROCEDURES ADEQUATE:

a. SAMPLES REFRIGERATED DURING COMPOSITING: b. PROPER PRESERVATION TECHNIQUES USED: c. CONTAINERS AND SAMPLE HOLDING TIMES CONFORM TO 40 CFR 136: 7. IF MONITORING IS PERFORMED MORE OFTEN THAN REQUIRED ARE RESULTS REPORTED ON THE DMR:

Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE

SECTION E: FLOW MEASUREMENT

PERMITTEE FLOW MEASUREMENT MEETS PERMIT REQUIREMENTS

S M U NA NE

DETAILS:

1. PRIMARY FLOW MEASUREMENT DEVICE PROPERLY INSTALLED AND MAINTAINED: TYPE OF DEVICE: McCrometer inline flow gauge

2. FLOW MEASURED AT EACH OUTFALL AS REQUIRED:

Y N NA NE Y N NA NE

3. SECONDARY INSTRUMENTS (TOTALIZERS, RECORDERS, ETC.) PROPERLY OPERATED AND MAINTAINED:

Y N NA NE

4. CALIBRATION FREQUENCY ADEQUATE:

Y N NA NE

5. RECORDS MAINTAINED OF CALIBRATION PROCEDURES:

Y N NA NE

6. CALIBRATION CHECKS DONE TO ASSURE CONTINUED COMPLIANCE:

Y N NA NE

7. FLOW ENTERING DEVICE WELL DISTRIBUTED ACROSS THE CHANNEL AND FREE OF TURBULENCE:

Y N NA NE

8. FLOW MEASUREMENT EQUIPMENT ADEQUATE TO HANDLE EXPECTED RANGE OF FLOW RATES:

Y N NA NE

9. HEAD MEASURED AT PROPER LOCATION:

Y N NA NE

SECTION F: LABORATORY PERMITTEE LABORATORY PROCEDURES MEET PERMIT REQUIREMENTS DETAILS:

1. EPA APPROVED ANALYTICAL PROCEDURES USED (40 CFR 136.3 FOR LIQUIDS, 503.8(B) FOR SLUDGES) : 2. IF ALTERNATIVE ANALYTICAL PROCEDURES ARE USED, PROPER APPROVAL HAS BEEN OBTAINED: 3. SATISFACTORY CALIBRATION AND MAINTENANCE OF INSTRUMENTS AND EQUIPMENT: 4. QUALITY CONTROL PROCEDURES ADEQUATE: 5. DUPLICATE SAMPLES ARE ANALYZED >10% OF THE TIME: 6. SPIKED SAMPLES ARE ANALYZED >10% OF THE TIME: 7. COMMERCIAL LABORATORY USED:

S M U NA NE

Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE

a. LAB NAME: Sorrells Research

b. LAB ADDRESS: 8100 National Drive, Little Rock, AR 72209 Phone: 501-562-8139 Fax: 501-562-7025

c. PARAMETERS PERFORMED: CBOD5, TSS, , Oil & Grease, DO, Total Phosphorus, Residual Chlorine, Ammonia Nitrogen (NH3-N) & pH, Fecal Coliform

8. BIOMONITORING PROCEDURES ADEQUATE:

Y N NA NE

a. PROPER ORGANISMS USED:

Y N NA NE

b. PROPER DILUTION SERIES FOLLOWED:

Y N NA NE

c. PROPER TEST METHODS AND DURATION:

Y N NA NE

d. RETESTS AND/OR TRE PERFORMED AS REQUIRED:

Y N NA NE

Inspection Report Page 4 of 10

Inspection Report: Eden Isle WWTP, AFIN: 12-00022, Permit #: AR0024066

SECTION G: EFFLUENT/RECEIVING WATERS OBSERVATIONS BASED ON VISUAL OBSERVATIONS ONLY

S M U NA NE

DETAILS:

OUTFALL #:

OIL SHEEN

GREASE

TURBIDITY

VISIBLE FOAM

FLOATING SOLIDS

COLOR

OTHER

001

None

None

Slight

None

None

Light gray/green

--

SECTION H: SLUDGE DISPOSAL SLUDGE DISPOSAL MEETS PERMIT REQUIREMENTS DETAILS:

1. SLUDGE MANAGEMENT ADEQUATE TO MAINTAIN EFFLUENT QUALITY:

2. SLUDGE RECORDS MAINTAINED AS REQUIRED BY 40 CFR 503:

3. FOR LAND APPLIED SLUDGE, TYPE OF LAND APPLIED TO: (E.G., FOREST, AGRICULTURAL, PUBLIC CONTACT SITE):

SECTION I: SAMPLING INSPECTION PROCEDURES SAMPLE RESULTS WITHIN PERMIT REQUIREMENTS DETAILS:

1. SAMPLES OBTAINED THIS INSPECTION:

2. TYPE OF SAMPLE: GRAB: COMPOSITE:

METHOD:

FREQUENCY:

3. SAMPLES PRESERVED:

4. FLOW PROPORTIONED SAMPLES OBTAINED:

5. SAMPLE OBTAINED FROM FACILITY'S SAMPLING DEVICE:

6. SAMPLE REPRESENTATIVE OF VOLUME AND NATURE OF DISCHARGE:

7. SAMPLE SPLIT WITH PERMITTEE:

8. CHAIN-OF-CUSTODY PROCEDURES EMPLOYED:

9. SAMPLES COLLECTED IN ACCORDANCE WITH PERMIT:

SECTION J: STORM WATER POLLUTION PREVENTION PLAN STORM WATER MANAGEMENT MEETS PERMIT REQUIREMENTS DETAILS:

1. SWPPP UPDATED AS NEEDED: DATE OF LAST UPDATE: 2. SITE MAP INCLUDING ALL DISCHARGES AND SURFACE WATERS: 3. POLLUTION PREVENTION TEAM IDENTIFIED: 4. POLLUTION PREVENTION TEAM PROPERLY TRAINED: 5. LIST OF POTENTIAL POLLUTANT SOURCES: 6. LIST OF POTENTIAL SOURCES AND PAST SPILLS AND LEAKS: 7. ALL NON-STORM WATER DISCHARGES ARE AUTHORIZED: 8. LIST OF STRUCTURAL BMPS: 9. LIST OF NON-STRUCTURAL BMPS: 10. BMPS PROPERLY OPERATED AND MAINTAINED: 11. INSPECTIONS CONDUCTED AS REQUIRED:

S M U NA NE

S M U NA NE S M U NA NE

S M U NA NE

Y N NA NE

Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE

S M U NA NE

Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE Y N NA NE

Inspection Report Page 5 of 10

Inspection Report: Eden Isle WWTP, AFIN: 12-00022, Permit #: AR0024066

DMR Calculation Check

Reporting Period: From 2013

7

1 To 2013

7

31

Year

Month

Day

Year

Month

Day

Parameter Checked:

pH

Reported Value: Calculated Value: Permit Value:

Loading Mass

Mo. Avg. - lbs/day

N/A

N/A

N/A

Concentration

Monthly

Min. S.U.

Max. S.U.

7.08

7.26

7.08

7.26

6

9

If calculated value does not equal reported value, explain:

Inspection Report Page 6 of 10

Inspection Report: Eden Isle WWTP, AFIN: 12-00022, Permit #: AR0024066

DMR Calculation Check

Reporting Period: From 2013

12

1 To 2013

12

31

Year

Month

Day

Year

Month

Day

Parameter Checked:

pH

Reported Value: Calculated Value: Permit Value:

Loading Mass

Mo. Avg. - lbs/day

N/A

N/A

N/A

Concentration

Monthly

Min. S.U.

Max. S.U.

6.60

6.64

6.60

6.64

6

9

If calculated value does not equal reported value, explain:

Inspection Report Page 7 of 10

Inspection Report: Eden Isle WWTP, AFIN: 12-00022, Permit #: AR0024066

Water Division Photographic Evidence Sheet

Location: Eden Isle WWTP

Photographer: Sean Saunders

Date: 4/9/2014

Witness: Steve Upton

Description: Paint peeling from inside the equalization basin.

Time: 11:39 Photo #: 1

Photographer: Sean Saunders Witness: Steve Upton Description: Broken clarifier sweeper arm.

Date: 4/9/2014

Time: 11:50 Photo #: 2

Inspection Report Page 8 of 10

................
................