ELECTRICAL SYMBOL LEGEND GENERAL NOTES

6

5

4

3

2

1

ELECTRICAL SYMBOL LEGEND

GENERAL NOTES:

Dewberry Architects Inc.

BASIC MATERIALS

BASIC MATERIALS CONT.

FIRE ALARM/DETECTION SYSTEM

1. LIGHT SWITCHES SHALL BE MOUNTED 48 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF

DEVICE, UNLESS OTHERWISE NOTED.

SYMBOL

DESCRIPTION

SYMBOL

DESCRIPTION

SYMBOL

DESCRIPTION

2. RECEPTACLES SHALL BE LOCATED 18 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE,

F

Sa

SINGLE POLE SWITCH

(SUBSCRIPT INDICATES ITEM CONTROLLED)

S3

THREE-WAY SWITCH

S4

FOUR-WAY SWITCH

T

TRANSFORMER

AUTOMATIC TRANSFER SWITCH

30AR

NON-FUSED DISCONNECT SWITCH, SIZE AS NOTED

NF

NF DENOTES NON-FUSED

F

MANUAL PULL STATION

CEILING SMOKE DETECTOR, PHOTO-ELECTRIC TYPE UNLESS OTHERWISE NOTED

E = ELEVATOR WITH RECALL CONTACTS I = IONIZATION

UNLESS OTHERWISE NOTED. ABOVE COUNTER RECEPTACLES SHALL BE MOUNTED 6" ABOVE BACK SPLASH TO CENTERLINE OF DEVICE.

3. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND RATED FOR THE ENVIRONMENT IN WHICH THEY ARE TO BE INSTALLED.

A. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH NEC 110.

SP S WP S WPL

SINGLE POLE SWITCH WITH PILOT LIGHT

SINGLE POLE SWITCH WITH WEATHERPROOF COVER

SINGLE POLE SWITCH WITH WEATHERPROOF LOCKING COVER

30AR FUSED DISCONNECT 20AF

AR DENOTES AMP RATING OF SWITCH

AF DENOTES AMP FUSE SIZE MCP

SIZE

# OF POLES

30/3 0 3R

COMBINATION MAGNETIC MOTOR STARTER, SIZE AS NOTED 3 POLE UNLESS OTHERWISE NOTED

DUCT SMOKE DETECTOR

R = RETURN S = SUPPLY

R

SUPERVISED CONTROL RELAY

I

INPUT MONITORING MODULE

R

DUCT SMOKE REMOTE ALARM INDICATING LAMP,

W/ TEST SWITCH, WALL MOUNTED 72" AFF

B. THE EXCLUSIVELY DEDICATED SPACE EXTENDING FROM FLOOR TO STRUCTURAL CEILING WITH A WIDTH AND DEPTH OF THE PANELBOARD OR SWITCHBOARD MUST BE CLEAR OF ALL PIPING, DUCTS, EQUIPMENT FOREIGN TO THE ELECTRICAL EQUIPMENT OR ARCHITECTURAL APPURTENANCES IN ACCORDANCE WITH NEC 408.

4. WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE-RESISTIVE ASSEMBLIES, (CLASSIFIED AS FIRE/SMOKE AND SMOKE PARTITIONS), THEY SHALL BE INSTALLED WITHOUT AFFECTING THE FIRE CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS SHALL BE MET:

A. ALL ELECTRICAL BOXES SHALL BE METALLIC.

401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax

SK

SINGLE POLE KEY SWITCH

WALL MOUNTED OCCUPANCY SENSOR

CEILING MOUNTED OCCUPACY SENSOR

SL

SINGLE POLE SWITCH WITH SECURITY LOCKING KEY

S LV

LOW VOLTAGE SWITCH

SF

FAN SWITCH

SM

MANUAL MOTOR STARTER WITH OVERLOAD HEATERS

ENCLOSURE NEMA 1 UNLESS NOTED NEMA STARTER SIZE

BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, SURFACE MOUNTED

BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, FLUSH MOUNTED

BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS, SURFACE MOUNTED

BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS, FLUSH MOUNTED

RT

REMOTE FIRE ALARM WITH TEST SWITCH

F XXCD

COMBINATION AUDIBLE/VISUAL NOTIFICATION DEVICE CHIME/FLASHING "FIRE" LIGHT

CD = CANDELA RATING

F XXCD

COMBINATION AUDIBLE/VISUAL

NOTIFICATION DEVICE CD = CANDELA RATING

C = CEILING-MOUNTED

F

FIRE ALARM SPEAKER WITH STROBE

CD = CANDELA RATING

B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE.

C. BOX OPENING SHALL NOT EXCEED 16 SQUARE INCHES.

D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE COMPLETELY FILLED WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL).

E. PROVIDE A WALL AROUND OUTLETS LARGER THAN 16 SQUARE INCHES. THE INTEGRITY OF THE WALL RATING SHALL BE MAINTAINED.

F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 100 SQUARE INCHES PER 100 SQUARE FEET.

G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE RESISTIVE ASSEMBLIES SHALL BE SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES.

Pinellas County

Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings

114400 North 49th Street Clearwater, FL.

E

S MP

MANUAL MOTOR STARTER WITH OVERLOAD HEATERS AND PILOT LIGHT

SD

DIMMER SWITCH

(1500 WATTS UNLESS OTHERWISE INDICATED)

BRANCH CIRCUIT CONDUIT CONCEALED ABOVE CEILING OR IN WALL. CONDUIT SHALL INCLUDE PHASE, NEUTRAL AND GROUND CONDUCTORS AS REQUIRED FOR CIRCUITS (UNLESS OTHERWISE NOTED).

F

VISUAL SIGNALING UNIT, WALL MOUNTED

(NO AUDIO DEVICE)

P

FIREMAN'S PHONE JACK

H. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS.

I. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 1/8 INCH BETWEEN THE EDGES OF THE OUTLET BOX AND THE EDGES OF THE OPENING.

DUPLEX RECEPTACLE

BRANCH CIRCUIT CONDUIT CONCEALED IN SLAB, UNDERGROUND OR UNDER FLOOR.

TS

SPRINKLER TAMPER

SWITCH CONNECTION

5. ALL DEVICES SHALL BE MOUNTED VERTICAL, UNLESS OTHERWISE NOTED.

TWIST LOCK RECEPTACLE T

SURGE PROTECTION TYPE (TVSS)

SP

DUPLEX RECEPTACLE

PEDESTAL MOUNTED RECEPTACLE

FLOOR OUTLET BOX AND DUPLEX RECEPTACLE WITH APPROPRIATE FLANGE.

FLOOR OUTLET BOX WITH TWO DUPLEX RECEPTACLES AND ONE COMBINATION W/ VOICE/DATA OUTLET

DUPLEX RECEPTACLE WITH EACH HALF ON SEPARATE CIRCUIT (BREAKER SHALL BE TWO POLE WITH COMMON TRIP)

C L EQ

UP DN

BRANCH CIRCUIT CONDUIT EXPOSED GROUND OR GROUND ROD AS NOTED CRITICAL BRANCH CONDUIT LIFE SAFETY BRANCH CONDUIT EQUIPMENT BRANCH CONDUIT CONDUIT TURNING UP CONDUIT TURNING DOWN CONDUIT STUB

DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER

CONDUIT CONTINUED

DUPLEX SAFETY RECEPTACLE MOUNT COVERPLATES WITH SPANNER HEAD SCREWS

DUPLEX RECEPTACLE WITH TOP HALF SWITCHED

D

SIMPLEX RECEPTACLE (EWC DENOTES

ELECTRIC WATER COOLER. COORDINATE WITH EWC

EWC

INSTALLER FOR MOUNTING HEIGHT)

GFI RECEPTACLE. WP DENOTES WEATHERPROOF COVER. WP

GFI RECEPTACLE MOUNTED ABOVE COUNTER

FLEXIBLE CONDUIT EXISTING TO BE REMOVED EXISTING TO REMAIN EXISTING AFFECTED BY THIS PROJECT FUTURE NEW

TWO DUPLEX RECEPTACLES WITH COMMON COVER

TWO DUPLEX RECEPTACLES WITH COMMON COVER MOUNTED ABOVE COUNTER

ISOLATED GROUND DUPLEX RECEPTACLE,

IG

(ORANGE DEVICE)

LIGHTING

FLUORESCENT STRIP FIXTURE

A

FIXTURE DESIGNATION

FLUORESCENT FIXTURE

FS

H H H FACP FATC

SPRINKLER WATERFLOW SWITCH CONNECTION

ELECTROMAGNETIC DOOR HOLD OPEN DEVICE ELECTROMAGNETIC DOOR HOLD OPEN DEVICE CONNECTION TO CLOSURE/ HOLDER ELECTROMAGNETIC DOOR HOLD OPEN DEVICE CONNECTION TO CLOSURE/ HOLDER INCLUDES DETECTOR CEILING HEAT DETECTOR 135? UNLESS OTHERWISE INDICATED.

FIRE ALARM CONTROL PANEL

FIRE ALARM TERMINAL CABINET

FAAP

FIRE ALARM ANNUNCIATOR PANEL - FLUSH MOUNTED

F

FIRE ALARM SYSTEM CONDUIT AND WIRING

E

FIREMAN'S ELEVATOR WARNING LIGHT

LIGHTNING PROTECTION SYSTEM

CI

CLASS I MAIN CONDUCTOR CABLE

6. ALL RECEPTACLES SHALL BE MOUNTED SUCH THAT THE GROUND PIN IS MOUNTED UP. 7. THE NUMBER OF ARROWHEADS ON THE HOMERUNS DENOTES THE NUMBER OF CIRCUITS. 8. ALL PANELS IN THIS PROJECT SHALL BE PROVIDED WITH A TYPE WRITTEN DIRECTORY.

LIGHTING FIXTURE SCHEDULE

TYPE

A1 A1E A2E B1 B1E B2E CE

D1E D3 D3E F FE G

DESCRIPTION

2x4 LED LAY-IN SECURTIY LIGHTING FIXTURE 2x4 LED LAY-IN SECURTIY LIGHTING FIXTURE WITH EMERGENCY BATTERY BACK-UP DRIVER 2x4 LED LAY-IN LIGHTING FIXTURE WITH EMERGENCY BATTERY BACK-UP DRIVER 2x2 LED LAY-IN SECURTIY LIGHTING FIXTURE 2x2 LED LAY-IN SECURTIY LIGHTING FIXTURE WITH EMERGENCY BATTERY BACK-UP DRIVER 2x2 LED LAY-IN LIGHTING FIXTURE WITH EMERGENCY BATTERY BACK-UP DRIVER 4' LONG LED UP/DOWN WALL MOUNTED SECURITY LIGHTING FIXTURE WITH EMERGENCY BATTERY BACK-UP DRIVER

4' LONG LED WALL MOUNTED VAPORTITE LIGHTING FIXTURE WITH EMERGENCY BATTERY BACK-UP DRIVER 4' LONG LED CHAIN HUNG VAPORTITE LIGHTING FIXTURE

4' LONG LED CHAIN HUNG VAPORTITE LIGHTING FIXTURE WITH EMERGENCY BATTERY BACK-UP DRIVER 1x4 LED SURFACE MOUNTED SECURITY FIXTURE 1x4 LED SURFACE MOUNTED SECURITY FIXTURE WITH EMERGENCY BATTERY BACK-UP DRIVER LED WET LOCATION HIGH BAY FIXTURE

MANUFACTURER

FAIL-SAFE FAIL-SAFE METALUX FAIL-SAFE FAIL-SAFE METALUX FAIL-SAFE

METALUX METALUX METALUX FAIL-SAFE FAIL-SAFE FAIL-SAFE

MODEL

FSR-SC-X-24-4-LD3-3-STD-40-UNV-80/97-ED1C FSR-SC-X-24-4-LD3-3-STD-40-UNV-80/97-ED1C-EBP

VOLTAGE

277 V 277 V

24EN-LD1-6700-UNV-EL14-L840-CD-1

277 V

FSR-SC-X-24-2-LD3-3-STD-40-UNV-80/97-ED1C FSR-SC-X-24-2-LD3-3-STD-40-UNV-80/97-ED1C-EBP

277 V 277 V

22EN-LD1-34-UNV-EL14-L840-CD-1

277 V

FMB-X-4-5000/2500-7-40-UNV-80/97-ED-EBP

277 V

VT-LD2-55-DR-W-EL400-UNV-L840-CD2-WL-VT2

VT-LD2-55-DR-W-UNV-L840-CD2-WL-VT2-CHAIN/SETU

VT-LD2-55-DR-W-EL400-UNV-L840-CD2-WL-VT2-CHAI N/SET-U

FMSLP-X-12-4-7500-7-40-UNV-80/97-ED FMSLP-X-12-4-7500-7-40-UNV-80/97-ED-EBP

FHL-7L-50-3A-UNV-TL

277 V 277 V 277 V 277 V 277 V 277 V

GE LED WET LOCATION HIGH BAY FIXTURE WITH EMERGENCY BATTERY BACK-UP DRIVER

FAIL-SAFE

FHL-7L-50-3A-UNV-TL-EBP

277 V

REQUIRED LAMPS

TYPE

LAMP QUANTITY

7900 LUMEN LED 7900 LUMEN LED

WITH UNIT WITH UNIT

6700 LUMEN LED

WITH UNIT

5000 LUMEN LED 5000 LUMEN LED

WITH UNIT WITH UNIT

3400 LUMEN LED

WITH UNIT

5000 LUMEN DOWN/2500 LUMEN UP

WITH UNIT

5500 LUMEN LED

WITH UNIT

5500 LUMEN LED

WITH UNIT

5500 LUMEN LED

WITH UNIT

7500 LUMEN LED 7500 LUMEN LED

WITH UNIT WITH UNIT

7400 LUMEN LED

WITH UNIT

7400 LUMEN LED

WITH UNIT

LOAD

122 VA 122 VA

70 VA

77 VA 77 VA

35 VA

105 VA

COMMENTS

WALL MOUNT @+8'-0" A.F.F.

81 VA 81 VA 81 VA 105 VA 105 VA 36 VA 94 VA

WALL MOUNT IN ELEVATOR PIT

MOUNT FIXTURE @ +8'-0" A.F.F.

MOUNT FIXTURE @ +8'-0" A.F.F. IN NON SECURE AREAS, MOUNT FIXTURE @ +12'-0" A.F.F. IN SECURE AREAS

MOUNT FIXTURE @ +18'-0" A.F.F. OR FLUSH WITH BOTTOM OF BEAM, WHICH EVER IS LOWER MOUNT FIXTURE @ +18'-0" A.F.F. OR FLUSH WITH BOTTOM OF BEAM, WHICH EVER IS LOWER

DUPLEX RECEPTACLE

NOTE: TICK MARKS SHOWN ON ANY DEVICE REPRESENTS RECEPTACLE CONNECTED TO THE EMERGENCY CIRCUIT

2

a

LOWER CASE LETTER INDICATES CONTROL CIRCUIT SWITCH LEG

CIRCUIT NUMBER

CII

CLASS II MAIN CONDUCTOR CABLE

TEE SPLICE

S1

BUILIDING MOUNTED LED WALLPACK FIXTURE WITH WIRE

GUARD

X

INSTITUTIONAL GRADE LED EXIT SIGN, CEILING

MOUNTED, RED LETTERS, WHITE BACKGROUND AND

SINGLE OR DOUBLE FACE

LUMARK FAIL-SAFE

XTORA9A-WG-XTORMX EXL-7-*-RW-*-*

277 V 277 V

7200 LUMEN LED LED

WITH UNIT

PROVIDED WITH FIXTURE

86 VA

VERIFY FINISH WITH ARCHITECT, MOUNT FIXTURE AT 20'-0" TO TOP OF FIXTURE

VERIFY COLOR/FINISH WITH ARCHITECT. SINGLE FACE, DOUBLE FACE, AND DIRECTIONAL INDICATOR OPTIONS SHALL BE IN ACCORDANCE WITH FLOOR PLANS.

SEAL

(RED DEVICE) TYPICAL FOR ANY DEVICE IN LEGEND

C

CLOCK RECEPTACLE

FLUORESCENT FIXTURE DIAGONAL SHADING DENOTES TO LIGHT FIXTURE CONNECTED TO CRITICAL BRANCH.

BONDING PLATE PIPE CLAMP FOR PLUMBING VENT THRU ROOF.

LIGHTING FIXTURE SCHEDULE NOTES: 1. SHADED FIXTURES IN PLAN VIEW ARE EMERGENCY LIGHTING FIXTURES PROVIDED WITH AN EMERGENCY BATTERY BACK-UP SOURCE.

PRELIMINARY DOCUMENTS

NOT FOR CONSTRUCTION

SPECIAL PURPOSE RECEPTACLE, RATING AS NOTED

FLUORESCENT FIXTURE DIAGONAL SHADING DENOTES HALF OF LAMPS

AIR TERMINATION DEVICE

2. VERIFY COLOR/FINISH OF ALL FIXTURES WITH THE ARCHITECT. 3. SINGLE FIXTURE LISTED IN SCHEDULE. ALL EQUIVALENT FIXTURES SHALL MEET OR EXCEED THE PERFORMANCE OF FIXTURES LISTED IN LIGHTING FIXTURE SCHEDULE.

LIGHTING CONTROL TIME CLOCK

CONNECTED TO CRITICAL BRANCH, OTHER HALF

GROUND TERMINAL

TO NORMAL BRANCH. (3 LAMP FIXTURES SHALL

C

PHOTOCELL, MOUNTED ON ROOF FACING NORTH

HAVE 2 LAMPS CONNECTED TO CRITICAL, 1 LAMP CONNECTED TO NORMAL).

BONDING CONDUCTOR

KEY PLAN

GND

GROUND BAR

FLUORESCENT FIXTURE

DN DOWN CONDUCTOR

PLUG-IN STRIP WITH RECEPTACLES, 18" O.C. UNLESS OTHERWISE INDICATED

COMPLETELY SHADED DENOTES LIGHT FIXTURE CONNECTED TO LIFE SAFETY BRANCH

G

COUNTERPOISE CONDUCTOR

CABLE TRAY

CIRCUIT.

PARAPET MOUNTED AIR TERMINAL P

J

JUNCTION BOX

FLUORESCENT FIXTURE HALF SHADING DENOTES HALF OF LAMPS CONNECTED

FLAT ROOF MOUNTED OR MECHANICAL F

CONDUIT SEAL-OFF FITTINGS

TO LIFE SAFETY BRANCH, OTHER HALF TO NORMAL BRANCH. (3 LAMP FIXTURES SHALL HAVE 2 LAMPS CONNECTED TO LIFE SAFETY, 1 LAMP

THRU-ROOF CONDUCTOR DN

SS C3

SURGE SUPRESSOR C3 = SERVICE ENTRANCE DEVICE

CONNECTED TO NORMAL).

SCALE

B3 = DISTRIBUTION BOARD DEVICE

FLUORESCENT WALL MOUNTED FIXTURE WITH

A3 = PANELBOARD DEVICE

WALL OUTLET BOX

ST

SHUNT-TRIP BUTTON - FLUSH MOUNTED UNLESS

OTHERWISE NOTED NEMA 3R FOR EXTERIOR LOCATIONS

HID, FLUORESCENT, OR INCANDESCENT FIXTURE

NOT TO SCALE

C

POWER CONNECTION TO EQUIPMENT

FLUORESCENT, OR INCANDESCENT WALL WASHER.

EXIT LIGHT FIXTURE

MAGNETIC MOTOR STARTER OR CONTACTOR

DIRECTION ARROWS AS SHOWN

SIZE AS NOTED

(SHADED QUADRANT INDICATES FACE(S) OF FIXTURE)

EDH-X

ELECTRIC DUCT HEATER

WALL MOUNTED EXIT LIGHT FIXTURE

5

MOTOR CONNECTION, NUMBER DENOTES HORSEPOWER

B

VFD

VARIABLE FREQUENCY DRIVE

DDC

DIRECT DIGITAL CONTROL PANEL

EXTERIOR LIGHT FIXTURE WITH ARMS AS SHOWN ON DRAWINGS

TRACK WITH TRACK LIGHT FIXTURE (TRIANGLES INDICATE QUANTITY OF LIGHT FIXTURES)

BATTERY PACK WITH TWIN HEADS

NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.

No.

Description

Date

REVISIONS

DRAWN BY APPROVED BY CHECKED BY DATE

JMB GAC GAC 03/19/2014

TITLE

ELECTRICAL SYMBOL LEGEND

A

PROJECT NO.

50057109

E-000

SHEET NO.

6 F

E

5

4

PROPOSED NEW DUKE ENERGY PRIMARY SERVICE

3

2

1

ELECTRICAL KEY NOTES

#

KEYNOTE TEXT

1 PROPOSED LOCATION FOR DUKE ENERGY PRIMARY SERVICE CONDUCTORS

2 NEW PRIMARY SERVICE TO REFEED EXISTING DUKE ENERGY TRANSFORMERS SERVING "A", "B", AND "C" BARRACKS

3 EXISTING DUKE ENERGY PAD-MOUNTED SWITCHGEAR TO REMAIN.

4 EXISTING DUKE ENERGY TRANSFORMER TO REMAIN.

5 DEMOLISH EXISTING "FSG" SECONDARY SERVICE BACK TO EXISTING TRANSFORMER.

6 DEMOLISH ALL ELECTRICAL ASSOCIATED WITH VISITOR CENTER, FOOD SERVICE, AND LAUNDRY FACILITY. EXISTING EMERGENCY GENERATOR SERVES "A" AND "B" BARRACKS.

7 REFEED EXISTING "A" AND "B" BARRACKS' EMERGENCY FEEDS FROM NEW INFRASTRUCTURE BUILDING. VERIFY ALL EXISTING REQUIREMENTS.

8 DEMOLISH EXISTING DUKE ENERGY PRIMARY FEEDER, ASSOCIATED TRANSFORMERS BACK TO SOURCE.

Dewberry Architects Inc.

401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax

SAFE HARBOR

GENERAL NOTES:

1. TRANSFORMER, SWITCHGEAR, AND PULL BOX LOCATIONS ARE BASED UPON CIVIL DRAWINGS, ELECTRICAL UTILITY DRAWINGS, AND SATELLITE IMAGERY. FIELD VERIFY EXACT LOCATIONS.

2. UNDERGROUND FEEDER ROUTING IS DIAGRAMMATIC AND BASED UPON CIVIL DRAWINGS AND ELECTRICAL UTILITY DRAWINGS. REFER TO CIVIL AND ELECTRICAL UTILITY DRAWINGS FOR FURTHER INFORMATION.

3. TRANSFORMER DATA IS BASED UPON ELECTRICAL UTILITY DRAWINGS AND AN EXISTING FACILITY ELECTRICAL ASSESSMENT REPORT DATED JULY 19, 2006.

4. ALL WORK REQUIRED BY THE UTILITY COMPANY SHALL BE PERFORMED BY THE UTILITY COMPANY AND ALL ASSOCIATED COSTS SHALL BE INCLUDED BY THE DESIGN BUILDER.

5. DESIGN BUILDER TO SEQUENCE ALL DEMOLITION WITH OWNER TO MINIMIZE SHUTDOWNS TO ALL EXISTING OPERATIONS TO REMAIN.

6. PROVIDE EMERGENCY POWER TO ALL NEW SECURITY WORK IN EXISTING BUILDINGS. COORDINATEREQUIREMENTS WITH SECURITY DRAWINGS.

CROSS BAYOU MH

2' V ALLEY GU TTER

49TH ST N Pinellas County Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings 114400 North 49th Street Clearwater, FL.

EXISTING 208/120V, 3 PHASE, 4W, 75KVA, PAD-MOUNTED ELECTRICAL UTILITY TRANSFORMER (UNLABELED BLDG. ADJACENT TO HEALTH)

EXISTING 480/277V, 3 PHASE, 4W,

VT

150KVA, PAD-MOUNTED ELECTRICAL

UTILITY TRANSFORMER (MINI 1)

D

PROPOSED NEW DUKE ENERGY PRIMARY SERVICE

MH

2

VT

2

VT

T T

4

7

"B" PB

("A" AND "B")

7

T

"A"

4

(HEALTH)

HEALTTH CARE FACILITY

"M1"

2

T

8

SHERIFF ADMIN.

VT

MH

145TH AVE N

4

PB

("C" AND "FSC")

"C"

2

8

"M2"

SEAL

5

6

T

T

VT

1

6

PRELIMINARY DOCUMENTS

NOT FOR CONSTRUCTION

T

VT

EXISTING 480/277V, 3 PHASE, 4W,

T

150KVA, PAD-MOUNTED ELECTRICAL

1

T

UTILITY TRANSFORMER (MINI 2)

VT

C

1

PB

KEY PLAN

3

142ND AVE N

4

T

OCPD OCPD OCPD

(CENTRAL)

CENTRAL DIVISION

3

POND

PB PB PB

PB

POND

T TT

EXISTING PRIMARY-SIDE, MEDIUM VOLTAGE, UNDERGROUND FEEDERS. TYPICAL.

SCALE

T

4 SOUTH DIVISION

("A" SOUTH)

PINELLAS COUNTY

4 CRIMINAL COURT

(CJC)

COMPLEX

1" = 100'-0"

"G"

4

POND

POND

VT

(SA)

B

"F"

"E"

"D"

"C"

T

MAINTENANCE

A

1

ELECTRICAL SITE PLAN

Scale: 1" = 100'-0"

T

4

("F" SOUTH)

VT

JURISDICT IONAL WET LAND LINE

OHE

SIR LB021 (FI R 1/2" LB1344 0.30' S., 0.50' W.)

OHE

OHE

VT

VT

No.

Description

Date

REVISIONS

DRAWN BY APPROVED BY CHECKED BY DATE

JMB GAC GAC 03/19/2014

TITLE

ELECTRICAL SITE PLAN

PROJECT NO.

50057109

E-001

SHEET NO.

JJ J

H

Pinellas County

Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings

114400 North 49th Street Clearwater, FL.

6

5

F

A A.1

J

7 4

1 1.1

E

B

D

C

4

7 WP

J

10

SECURITY ELECTRONICS

101

6 6

6

6

10

5

DOCK FAN COILSUTONRITAGE

102

STAIR A

SA1

WP

WP

SALLYPORT SERVICE DRIVE

103

D

C

4 7 WP

PARKING AREA

E.9 F

B

1 1.1

1

FIRST FLOOR POWER PLAN

Scale: 1/8" = 1'-0"

4

3

2

3

5

6.9 7

WP

WP

WP

9

LOADING

DOCK

105

WP

9

5

BULK DRY

STORAGE

108

TV

WALK-IN REF. FAN COIL

5

UNIT

PROGRAM MEETING ROOM

110

COILING DOOR #2

5

3

4

TV DOCK STAGING 107

5

5 VAV BOX 5

JANITOR 142

BULK REFIG 2 STORAGE

109

J

STORAGE 112

PROGRAM MEETING ROOM

111

VAV BOX

5

JANITOR 114

INMATE TOILET

113

VAV BOX

OFFICE 115

PROGRAM MEETING ROOM

116

TV

INMATE TOILET

121

66

AV CLOSET 117

VAV BOX

STAFF

5

118

INMATE TOILET

119

STORAGE VAV BOX

5

WORKER

STAGING 122

WP

SEARCH 123

8

COILING DOOR #1

4

ELEVATOR A EA

1

WP

WP

6

TRASH COMPACTOR 5

WP

GARBAGE/ RECYCLE DOCK

106

WP

UTILITY WASH 136

OFFICE/ CONTROL

137 VAV BOX 5

FEC

C

5 CORRIDOR

141

CART WASH 139 4

4

J

L104

ELECTRICAL 140

ELEVBAT1OR

1

EEB-141

5

WP 5

5 WP

ELEVATOR

1

6

C EC

WP WP

6 L101

5 L109B

L109A L108B L108A

FEC

WATER HEATER

124

STAIR B

WP

SB1

STAFF

TOILET

5

1L21156

AIR COMPRESSOR

126 4

FAN COIL UNIT

L115

TRASH COMPACTOR WP

CLEAN LAUNDRY STORAGE 135

WATER TANK STORAGE 104

BEDDING STORAGE

134

MAINTENANCE SUPPLY 133

RISER ROOM 132

WP

UNIFORM STORAGE

131

VAV BOX 5

VAV BOX 5 BREAK ROOM 130

C

CENTRAL LAUNDRY

138

INMATE TOILET

129

CHEMICAL STORAGE

128

2448

2448

L114A 4

4 4

4

4 DRYERS 127

4

4

4

4 4

DRYER BOOSTER FAN L114B

4 4

L111A L111B L111C L111D L111E L111F L111G L111H

3

5

6.9 7

A

A A.1

B

1

ELECTRICAL KEY NOTES

#

KEYNOTE TEXT

1 DEDICATED RECEPTACLE FOR SUMP PUMP

2 J-BOX FOR WALK-IN REFRIGERATOR LIGHTING, DOOR HEATER (IF PROVIDED), AND CONTROLS. COORDINATE LOCATION, MOUNTING HEIGHT, AND REQUIREMENTS WITH FOOD SERVICE CONSULTANT AND SHOP DRAWINGS PRIOR TO ROUGH-IN. SEAL ALL CONDUIT PENETRATIONS AND MAKE CONNECTIONS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.

3 COORDINATE LOCATION, MOUNTING HEIGHT, AND REQUIREMENTS WITH FOOD SERVICE CONSULTANT AND SHOP DRAWINGS PRIOR TO ROUGH-IN. SEAL ALL CONDUIT PENETRATIONS AND MAKE CONNECTIONS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.

4 PROVIDE DEDICATED BRANCH CIRCUIT IN 208/120V PANELBOARD. COORDINATE VOLTAGE, CIRCUIT BREAKER/CONDUCTOR AMPERE RATING, PHASE, AND CONNECTION REQUIREMENTS WITH EQUIPMENT SELECTIONS. ADJUST CONDUCTOR AND CONDUIT SIZES FOR VOLTAGE DROP (AS REQUIRED).

5 PROVIDE DEDICATED BRANCH CIRCUIT IN 480/277V PANELBOARD. COORDINATE VOLTAGE, CIRCUIT BREAKER/CONDUCTOR AMPERE RATING, PHASE, AND CONNECTION REQUIREMENTS WITH EQUIPMENT SELECTIONS. ADJUST CONDUCTOR AND CONDUIT SIZES FOR VOLTAGE DROP (AS REQUIRED).

6 PROVIDE DEDICATED BRANCH CIRCUIT IN 208/120V PANELBOARD. ADJUST CONDUCTOR AND CONDUIT SIZES FOR VOLTAGE DROP (AS REQUIRED).

7 J-BOX FOR SECURITY GATE OPERATOR. COORDINATE LOCATION, MOUNTING HEIGHT, AND REQUIREMENTS WITH ARCHITECT AND SECURITY GATE SHOP DRAWINGS PRIOR TO INSTALLATION.

8 DISCONNECT SWITCH FOR DOCK LIFT. COORDINATE LOCATION, MOUNTING HEIGHT, AND REQUIREMENTS WITH ARCHITECT AND SECURITY GATE SHOP DRAWINGS PRIOR TO INSTALLATION.

9 DISCONNECT SWITCH FOR DOCK LEVELER. COORDINATE LOCATION, MOUNTING HEIGHT, AND REQUIREMENTS WITH ARCHITECT AND SECURITY GATE SHOP DRAWINGS PRIOR TO INSTALLATION.

10 J-BOX FOR SECURITY ELECTRONICS. COORDINATE LOCATION, MOUNTING HEIGHT, AND REQUIREMENTS WITH OWNER AND SECURITY CONTRACTOR PRIOR TO INSTALLATION.

GENERAL NOTES:

1. PROVIDE ELECTRICAL CONNECTIONS FOR ALL EQUIPMENT INDICATED ON ARCHITECTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION, OR OTHER EQUIPMENT PLANS AS REQUIRED. CONNECTION INFORMATION TO BE COORDINATED WITH FINAL CONSTRUCTION DOCUMENTS.

2. COORDINATE ALL LAUNDRY EQUIPMENT WITH LAUNDRY SERVICE DRAWINGS.

3. ALL FINAL LAUNDRY EQUIPMENT CONNECTIONS WILL BE PROVIDED AS REQUIRED BY FINAL LAUNDRY CONSTRUCTION DOCUMENTS INCLUDING ALL ELECTRICAL STUB-UP LOCATIONS, OVERCURRENT PROTECTION, CONDUIT AND WIRE REQUIREMENTS.

4. REFER TO TECHNOLOGY DRAWINGS FOR ALL SECURITY AND DATA INFRASTRUCTURE CONNECTION REQUIREMENTS. ALL EQUIPMENT COORDINATION SHALL BE IN ACCORDANCE WITH FINAL TECHNOLOGY CONSTRUCTION DOCUMENTS.

Dewberry Architects Inc.

401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax

C

SEAL

PRELIMINARY DOCUMENTS

NOT FOR CONSTRUCTION

D

KEY PLAN

SCALE

1/8" = 1'-0"

E.9 F

No.

Description

Date

REVISIONS

DRAWN BY APPROVED BY CHECKED BY DATE

JMB GAC GAC 03/19/2014

TITLE

FIRST FLOOR POWER PLAN

PROJECT NO.

50057109

E-110

SHEET NO.

6

5

4

3

2

F

A A.1

E

B

D

C

1 1.1

S1 GE

S1

G GE

GE

GE

G

S1

G

GE

GE

X S1

GE

D3E

FE

SECURITY ELECTRONICS

S1

101

DOCK STORAGE

102

STCAEIR

G

A

SA1

CE GE

S1

X

CE

G

S1 GE

GE

G

G

GE

GE

G

G

GE

SALLYPORT SERVICE DRIVE

103

GE

G

G

GE

GE

G

G

GE

D

C

G S1

GE

G

GE

G

G

GE

PARKING AREA

GE

G

E.9 F

B

GE S1

G

GE

X S1

1 1.1

1

FIRST FLOOR LIGHTING PLAN

Scale: 1/8" = 1'-0"

3

5

6.9 7

S1

GE

G

X

G

GE

GE

G

G

GE

GE

G

G

GE

GE

G

G

GE

TRASH COMPACTOR

GE

G

G

GE

GE

WATER TANK

G

STORAGE

104

G

GE

FE

F

F

FE

S1

S1

G

G

GE

BULK DRY

STORAGE

108

X

A1

A1E

X

A1E

A1

A1E

A1

A1E

A1

A1E

PROGRAM MEETING ROOM

110

PROGRAM MEETING ROOM

116

A1

A1E

A1

A1E

A1

A1

A1E

A1

A1E

A1E

WORKER X

S1

STAGING

12A12

GE

G

G

LOADING DOCK 105

FE

F

F

FE

FE

F

G DOCK STAGING 107 GE

G

GE

G

A1

G

G

A1E

G FE

GE

BULK REFIG STORAGE 109

FE

STORAGE 112 F

A1E 111

A1

A1E A1

A1 A1E

FE

JANITOR 114B1

A2E

FE

115

A2E B1E

A1

A1E

A1

INMFAETE

121

A1E

A1

A1E

STOFREAGE

A1E

B1

AV CFLEOSET

FE

FE

INMATE TOILET

A1

B1E

STAFF TOILET

1F19

118

A1E B1

SEARCH

B1 123

A1

A1

A1E

A1E

A1

X

A1E

A1

A1E

X

A1E

A1

ELEVATOR

D1E

A

D1E

EA

A1

A2E

A2E

OFFICE/ CONTROL A2E 137 A2E

X

X

A1E

A1

A1E

A1

A1E

CORRIDOR 141

FEC

A1E

C

A1E

D3E

F

FE

CART

ELEVATOR

ELEVATOR

WASH

ELECTRICAL D1E

B

D1E

D1E

C D1E

139

1D430E

EB

X

EC B1

A1

FEC HWEAAFTETEERR

X A1E

X X

CE

STAIR

B

SB1

X

S1

X

F

A1E

A1

A1E

X

GE

G

GE

G

GE

G

GE

GE

CE

X

STAFF

TOILET

125

X

F

FE X

FE

AIR

CE

COMPRESSOR

GARBAGE/ RECYCLE DOCK

F

F

G

GE

G

GE

G

GE

126

G

GE

106

F

UTILITY

WASH

FE

136

F

D3E

FE

F

CF LEAN LAUNDFREY

GE

G

GE

G

GE

G

GE

STORAGE

135

CENTRAL

D3

LAUNDRY

138

S1

FE

F

F

FE

G

GE

G

GE

G

GE

G

D3E

BEDDING STORAGE

134

DRYERS 127

D3

FE

F

F

FE

MAINTENANCE

GE

G

GE

G

GE

G

GE

SUPPLY

133

D3

D3E RISER ROOM 132 D3E

a

S1

FE

F

F

FE

UNIFORM

STORAGE

131

F

FE

F

BREAK ROOM 130

S1

ITNOMFIELAETTE

F CHEMICAL FE STORAGE

G

128

2448

2448

C

G S1

G

D3E

3

5

6.9 7

A

H

Pinellas County

Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings

114400 North 49th Street Clearwater, FL.

1

GENERAL NOTES: 1. REFER TO REFLECTED CEILING PLANS FOR EXACT LOCATIONS

OF FIXTURES. 2. ALL LIGHTING FIXTURES SHALL BE CONTROLLED VIA RELAY

CONTROL PANELS FROM THE MAIN BUILDING CONTROL/SECURITY ROOM. 3. PROVIDE UNSWITCHED CONDUCTORS TO ALL EMERGENCY LIGHTING POWER SUPPLIES IN DESIGNATED FIXTURES. 4. REFER TO SHEET E-000 FOR FIXTURE SCHEDULE.

A A.1

Dewberry Architects Inc.

401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax

B

C

SEAL

PRELIMINARY DOCUMENTS

NOT FOR CONSTRUCTION

D

KEY PLAN

SCALE

1/8" = 1'-0"

E.9 F

No.

Description

Date

REVISIONS

DRAWN BY APPROVED BY CHECKED BY DATE

JMB GAC GAC 03/19/2014

TITLE

FIRST FLOOR LIGHTING PLAN

PROJECT NO.

50057109

E-111

SHEET NO.

6

5

4

3

2

F

A A.1

E

B

D

C

D

C

E.9 F

B

1 1.1

3

5

6.9 7

F

F F

C

F F

F

F F

WP F

SECURITY ELECTRONICS

101

DOCK STORAGE

WP

102

1

FS TS

STAIR A

SA1

WP 5

F

WP

WP

SALLYPORT SERVICE DRIVE

103

PARKING AREA WP

F F F

BULK DRY STORAGE

108

PROGRAM MEETING ROOM

110

PROGRAM MEETING ROOM

116

WORKER STAGING

122

LOADING DOCK 105 WP/110cd

F

14 TS

WP H 3

ELEVATOR A EA

DOCK STAGING

107

WP F

PROGRAM MEETING ROOM

111

JANITOR 142

BULK REFIG STORAGE 109

F STORAGE

112

INMATE TOILET

113

JANITOR 114

OFFICE 115

INMATE TOILET

121

STORAGE 120

F AV CLOSET

117

STAFF TOILET

118

INMATE TOILET

119

SEARCH 123

F F

F

F

OFFICE/ CONTROL

137

FEC

C

CORRIDOR 141

14 TS

CART

ELEVATOR

WASH 139

WP

ELECTRICAL H 140

B EB

2

14 E

TS

ELEVATOR

H

C

EC

2

FEC

WATER HEATER

124

STAIR B SB1

F F

F

TRASH COMPACTOR

WP F

F

GARBAGE/ RECYCLE DOCK

106

UTILITY WASH 136

F WP

CLEAN LAUNDRY STORAGE 135

E STAFF TOILET 125

AIR COMPRESSOR

126

110cd

110cd

CENTRAL LAUNDRY

138

BEDDING STORAGE

134

DRYERS 127

WATER TANK STORAGE 104

MAINTENANCE SUPPLY 133

F

H

RISER ROOM 132

1

FS

TS

UNIFORM STORAGE

131

BREAK ROOM 130

INMATE TOILET

129

CHEMICAL STORAGE

128

2448

2448

F

1 1.1

3

5

1

FIRST FLOOR FIRE ALARM & MISC. SYSTEMS PLAN

Scale: 1/8" = 1'-0"

6.9 7

A

F F

A A.1

1

ELECTRICAL KEY NOTES

#

KEYNOTE TEXT

1 COORDINATE LOCATION WITH DIVISION 21 CONTRACTOR PRIOR TO INSTALLATION. PROVIDE ADDRESSABLE INPUT MONITORING MODULE(S) LOCATED WITHIN A CONDITIONED, ACCESSIBLE SPACE OR IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.

2 MOUNT HEAT DETECTOR TO ELEVATOR PIT WALL AS INDICATED. LOCATE WITHIN 2'-0" OF SIDEWALL FIRE SPRINKLER PENDENT. COORDINATE LOCATION AND REQUIREMENTS WITH DIVISION 21 CONTRACTOR AND A.H.J. PRIOR TO INSTALLATION.

3 MOUNT SMOKE DETECTOR ABOVE ELEVATOR DOOR AS INDICATED.

4 TAMPER SWITCH FOR CONTROL VALVE SERVING ELEVATOR PIT SIDEWALL FIRE SPRINKLER PENDENT

5 COORDINATE LOCATION WITH A.H.J. PRIOR TO INSTALLATION.

GENERAL NOTES:

1. ALL NOTIFICATION DEVICES SHALL HAVE A LUMINOUS INTENSITY OF 75 CANDELA UNLESS OTHERWISE NOTED.

Dewberry Architects Inc.

401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax

B

Pinellas County

Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings

114400 North 49th Street Clearwater, FL.

C

SEAL

PRELIMINARY DOCUMENTS

NOT FOR CONSTRUCTION

D

KEY PLAN

SCALE

1/8" = 1'-0"

E.9 F

No.

Description

Date

REVISIONS

DRAWN BY APPROVED BY CHECKED BY DATE

JMB GAC GAC 03/19/2014

TITLE

FIRST FLOOR FIRE ALARM & MISC. SYSTEMS

PLAN

PROJECT NO.

50057109

E-112

SHEET NO.

................
................