ELECTRICAL SYMBOL LEGEND GENERAL NOTES
6
5
4
3
2
1
ELECTRICAL SYMBOL LEGEND
GENERAL NOTES:
Dewberry Architects Inc.
BASIC MATERIALS
BASIC MATERIALS CONT.
FIRE ALARM/DETECTION SYSTEM
1. LIGHT SWITCHES SHALL BE MOUNTED 48 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF
DEVICE, UNLESS OTHERWISE NOTED.
SYMBOL
DESCRIPTION
SYMBOL
DESCRIPTION
SYMBOL
DESCRIPTION
2. RECEPTACLES SHALL BE LOCATED 18 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE,
F
Sa
SINGLE POLE SWITCH
(SUBSCRIPT INDICATES ITEM CONTROLLED)
S3
THREE-WAY SWITCH
S4
FOUR-WAY SWITCH
T
TRANSFORMER
AUTOMATIC TRANSFER SWITCH
30AR
NON-FUSED DISCONNECT SWITCH, SIZE AS NOTED
NF
NF DENOTES NON-FUSED
F
MANUAL PULL STATION
CEILING SMOKE DETECTOR, PHOTO-ELECTRIC TYPE UNLESS OTHERWISE NOTED
E = ELEVATOR WITH RECALL CONTACTS I = IONIZATION
UNLESS OTHERWISE NOTED. ABOVE COUNTER RECEPTACLES SHALL BE MOUNTED 6" ABOVE BACK SPLASH TO CENTERLINE OF DEVICE.
3. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND RATED FOR THE ENVIRONMENT IN WHICH THEY ARE TO BE INSTALLED.
A. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH NEC 110.
SP S WP S WPL
SINGLE POLE SWITCH WITH PILOT LIGHT
SINGLE POLE SWITCH WITH WEATHERPROOF COVER
SINGLE POLE SWITCH WITH WEATHERPROOF LOCKING COVER
30AR FUSED DISCONNECT 20AF
AR DENOTES AMP RATING OF SWITCH
AF DENOTES AMP FUSE SIZE MCP
SIZE
# OF POLES
30/3 0 3R
COMBINATION MAGNETIC MOTOR STARTER, SIZE AS NOTED 3 POLE UNLESS OTHERWISE NOTED
DUCT SMOKE DETECTOR
R = RETURN S = SUPPLY
R
SUPERVISED CONTROL RELAY
I
INPUT MONITORING MODULE
R
DUCT SMOKE REMOTE ALARM INDICATING LAMP,
W/ TEST SWITCH, WALL MOUNTED 72" AFF
B. THE EXCLUSIVELY DEDICATED SPACE EXTENDING FROM FLOOR TO STRUCTURAL CEILING WITH A WIDTH AND DEPTH OF THE PANELBOARD OR SWITCHBOARD MUST BE CLEAR OF ALL PIPING, DUCTS, EQUIPMENT FOREIGN TO THE ELECTRICAL EQUIPMENT OR ARCHITECTURAL APPURTENANCES IN ACCORDANCE WITH NEC 408.
4. WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE-RESISTIVE ASSEMBLIES, (CLASSIFIED AS FIRE/SMOKE AND SMOKE PARTITIONS), THEY SHALL BE INSTALLED WITHOUT AFFECTING THE FIRE CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS SHALL BE MET:
A. ALL ELECTRICAL BOXES SHALL BE METALLIC.
401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax
SK
SINGLE POLE KEY SWITCH
WALL MOUNTED OCCUPANCY SENSOR
CEILING MOUNTED OCCUPACY SENSOR
SL
SINGLE POLE SWITCH WITH SECURITY LOCKING KEY
S LV
LOW VOLTAGE SWITCH
SF
FAN SWITCH
SM
MANUAL MOTOR STARTER WITH OVERLOAD HEATERS
ENCLOSURE NEMA 1 UNLESS NOTED NEMA STARTER SIZE
BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, SURFACE MOUNTED
BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS, FLUSH MOUNTED
BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS, SURFACE MOUNTED
BRANCH CIRCUIT PANELBOARD, OVER 250 VOLTS, FLUSH MOUNTED
RT
REMOTE FIRE ALARM WITH TEST SWITCH
F XXCD
COMBINATION AUDIBLE/VISUAL NOTIFICATION DEVICE CHIME/FLASHING "FIRE" LIGHT
CD = CANDELA RATING
F XXCD
COMBINATION AUDIBLE/VISUAL
NOTIFICATION DEVICE CD = CANDELA RATING
C = CEILING-MOUNTED
F
FIRE ALARM SPEAKER WITH STROBE
CD = CANDELA RATING
B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE.
C. BOX OPENING SHALL NOT EXCEED 16 SQUARE INCHES.
D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE COMPLETELY FILLED WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL).
E. PROVIDE A WALL AROUND OUTLETS LARGER THAN 16 SQUARE INCHES. THE INTEGRITY OF THE WALL RATING SHALL BE MAINTAINED.
F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 100 SQUARE INCHES PER 100 SQUARE FEET.
G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE RESISTIVE ASSEMBLIES SHALL BE SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES.
Pinellas County
Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings
114400 North 49th Street Clearwater, FL.
E
S MP
MANUAL MOTOR STARTER WITH OVERLOAD HEATERS AND PILOT LIGHT
SD
DIMMER SWITCH
(1500 WATTS UNLESS OTHERWISE INDICATED)
BRANCH CIRCUIT CONDUIT CONCEALED ABOVE CEILING OR IN WALL. CONDUIT SHALL INCLUDE PHASE, NEUTRAL AND GROUND CONDUCTORS AS REQUIRED FOR CIRCUITS (UNLESS OTHERWISE NOTED).
F
VISUAL SIGNALING UNIT, WALL MOUNTED
(NO AUDIO DEVICE)
P
FIREMAN'S PHONE JACK
H. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS.
I. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 1/8 INCH BETWEEN THE EDGES OF THE OUTLET BOX AND THE EDGES OF THE OPENING.
DUPLEX RECEPTACLE
BRANCH CIRCUIT CONDUIT CONCEALED IN SLAB, UNDERGROUND OR UNDER FLOOR.
TS
SPRINKLER TAMPER
SWITCH CONNECTION
5. ALL DEVICES SHALL BE MOUNTED VERTICAL, UNLESS OTHERWISE NOTED.
TWIST LOCK RECEPTACLE T
SURGE PROTECTION TYPE (TVSS)
SP
DUPLEX RECEPTACLE
PEDESTAL MOUNTED RECEPTACLE
FLOOR OUTLET BOX AND DUPLEX RECEPTACLE WITH APPROPRIATE FLANGE.
FLOOR OUTLET BOX WITH TWO DUPLEX RECEPTACLES AND ONE COMBINATION W/ VOICE/DATA OUTLET
DUPLEX RECEPTACLE WITH EACH HALF ON SEPARATE CIRCUIT (BREAKER SHALL BE TWO POLE WITH COMMON TRIP)
C L EQ
UP DN
BRANCH CIRCUIT CONDUIT EXPOSED GROUND OR GROUND ROD AS NOTED CRITICAL BRANCH CONDUIT LIFE SAFETY BRANCH CONDUIT EQUIPMENT BRANCH CONDUIT CONDUIT TURNING UP CONDUIT TURNING DOWN CONDUIT STUB
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER
CONDUIT CONTINUED
DUPLEX SAFETY RECEPTACLE MOUNT COVERPLATES WITH SPANNER HEAD SCREWS
DUPLEX RECEPTACLE WITH TOP HALF SWITCHED
D
SIMPLEX RECEPTACLE (EWC DENOTES
ELECTRIC WATER COOLER. COORDINATE WITH EWC
EWC
INSTALLER FOR MOUNTING HEIGHT)
GFI RECEPTACLE. WP DENOTES WEATHERPROOF COVER. WP
GFI RECEPTACLE MOUNTED ABOVE COUNTER
FLEXIBLE CONDUIT EXISTING TO BE REMOVED EXISTING TO REMAIN EXISTING AFFECTED BY THIS PROJECT FUTURE NEW
TWO DUPLEX RECEPTACLES WITH COMMON COVER
TWO DUPLEX RECEPTACLES WITH COMMON COVER MOUNTED ABOVE COUNTER
ISOLATED GROUND DUPLEX RECEPTACLE,
IG
(ORANGE DEVICE)
LIGHTING
FLUORESCENT STRIP FIXTURE
A
FIXTURE DESIGNATION
FLUORESCENT FIXTURE
FS
H H H FACP FATC
SPRINKLER WATERFLOW SWITCH CONNECTION
ELECTROMAGNETIC DOOR HOLD OPEN DEVICE ELECTROMAGNETIC DOOR HOLD OPEN DEVICE CONNECTION TO CLOSURE/ HOLDER ELECTROMAGNETIC DOOR HOLD OPEN DEVICE CONNECTION TO CLOSURE/ HOLDER INCLUDES DETECTOR CEILING HEAT DETECTOR 135? UNLESS OTHERWISE INDICATED.
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL CABINET
FAAP
FIRE ALARM ANNUNCIATOR PANEL - FLUSH MOUNTED
F
FIRE ALARM SYSTEM CONDUIT AND WIRING
E
FIREMAN'S ELEVATOR WARNING LIGHT
LIGHTNING PROTECTION SYSTEM
CI
CLASS I MAIN CONDUCTOR CABLE
6. ALL RECEPTACLES SHALL BE MOUNTED SUCH THAT THE GROUND PIN IS MOUNTED UP. 7. THE NUMBER OF ARROWHEADS ON THE HOMERUNS DENOTES THE NUMBER OF CIRCUITS. 8. ALL PANELS IN THIS PROJECT SHALL BE PROVIDED WITH A TYPE WRITTEN DIRECTORY.
LIGHTING FIXTURE SCHEDULE
TYPE
A1 A1E A2E B1 B1E B2E CE
D1E D3 D3E F FE G
DESCRIPTION
2x4 LED LAY-IN SECURTIY LIGHTING FIXTURE 2x4 LED LAY-IN SECURTIY LIGHTING FIXTURE WITH EMERGENCY BATTERY BACK-UP DRIVER 2x4 LED LAY-IN LIGHTING FIXTURE WITH EMERGENCY BATTERY BACK-UP DRIVER 2x2 LED LAY-IN SECURTIY LIGHTING FIXTURE 2x2 LED LAY-IN SECURTIY LIGHTING FIXTURE WITH EMERGENCY BATTERY BACK-UP DRIVER 2x2 LED LAY-IN LIGHTING FIXTURE WITH EMERGENCY BATTERY BACK-UP DRIVER 4' LONG LED UP/DOWN WALL MOUNTED SECURITY LIGHTING FIXTURE WITH EMERGENCY BATTERY BACK-UP DRIVER
4' LONG LED WALL MOUNTED VAPORTITE LIGHTING FIXTURE WITH EMERGENCY BATTERY BACK-UP DRIVER 4' LONG LED CHAIN HUNG VAPORTITE LIGHTING FIXTURE
4' LONG LED CHAIN HUNG VAPORTITE LIGHTING FIXTURE WITH EMERGENCY BATTERY BACK-UP DRIVER 1x4 LED SURFACE MOUNTED SECURITY FIXTURE 1x4 LED SURFACE MOUNTED SECURITY FIXTURE WITH EMERGENCY BATTERY BACK-UP DRIVER LED WET LOCATION HIGH BAY FIXTURE
MANUFACTURER
FAIL-SAFE FAIL-SAFE METALUX FAIL-SAFE FAIL-SAFE METALUX FAIL-SAFE
METALUX METALUX METALUX FAIL-SAFE FAIL-SAFE FAIL-SAFE
MODEL
FSR-SC-X-24-4-LD3-3-STD-40-UNV-80/97-ED1C FSR-SC-X-24-4-LD3-3-STD-40-UNV-80/97-ED1C-EBP
VOLTAGE
277 V 277 V
24EN-LD1-6700-UNV-EL14-L840-CD-1
277 V
FSR-SC-X-24-2-LD3-3-STD-40-UNV-80/97-ED1C FSR-SC-X-24-2-LD3-3-STD-40-UNV-80/97-ED1C-EBP
277 V 277 V
22EN-LD1-34-UNV-EL14-L840-CD-1
277 V
FMB-X-4-5000/2500-7-40-UNV-80/97-ED-EBP
277 V
VT-LD2-55-DR-W-EL400-UNV-L840-CD2-WL-VT2
VT-LD2-55-DR-W-UNV-L840-CD2-WL-VT2-CHAIN/SETU
VT-LD2-55-DR-W-EL400-UNV-L840-CD2-WL-VT2-CHAI N/SET-U
FMSLP-X-12-4-7500-7-40-UNV-80/97-ED FMSLP-X-12-4-7500-7-40-UNV-80/97-ED-EBP
FHL-7L-50-3A-UNV-TL
277 V 277 V 277 V 277 V 277 V 277 V
GE LED WET LOCATION HIGH BAY FIXTURE WITH EMERGENCY BATTERY BACK-UP DRIVER
FAIL-SAFE
FHL-7L-50-3A-UNV-TL-EBP
277 V
REQUIRED LAMPS
TYPE
LAMP QUANTITY
7900 LUMEN LED 7900 LUMEN LED
WITH UNIT WITH UNIT
6700 LUMEN LED
WITH UNIT
5000 LUMEN LED 5000 LUMEN LED
WITH UNIT WITH UNIT
3400 LUMEN LED
WITH UNIT
5000 LUMEN DOWN/2500 LUMEN UP
WITH UNIT
5500 LUMEN LED
WITH UNIT
5500 LUMEN LED
WITH UNIT
5500 LUMEN LED
WITH UNIT
7500 LUMEN LED 7500 LUMEN LED
WITH UNIT WITH UNIT
7400 LUMEN LED
WITH UNIT
7400 LUMEN LED
WITH UNIT
LOAD
122 VA 122 VA
70 VA
77 VA 77 VA
35 VA
105 VA
COMMENTS
WALL MOUNT @+8'-0" A.F.F.
81 VA 81 VA 81 VA 105 VA 105 VA 36 VA 94 VA
WALL MOUNT IN ELEVATOR PIT
MOUNT FIXTURE @ +8'-0" A.F.F.
MOUNT FIXTURE @ +8'-0" A.F.F. IN NON SECURE AREAS, MOUNT FIXTURE @ +12'-0" A.F.F. IN SECURE AREAS
MOUNT FIXTURE @ +18'-0" A.F.F. OR FLUSH WITH BOTTOM OF BEAM, WHICH EVER IS LOWER MOUNT FIXTURE @ +18'-0" A.F.F. OR FLUSH WITH BOTTOM OF BEAM, WHICH EVER IS LOWER
DUPLEX RECEPTACLE
NOTE: TICK MARKS SHOWN ON ANY DEVICE REPRESENTS RECEPTACLE CONNECTED TO THE EMERGENCY CIRCUIT
2
a
LOWER CASE LETTER INDICATES CONTROL CIRCUIT SWITCH LEG
CIRCUIT NUMBER
CII
CLASS II MAIN CONDUCTOR CABLE
TEE SPLICE
S1
BUILIDING MOUNTED LED WALLPACK FIXTURE WITH WIRE
GUARD
X
INSTITUTIONAL GRADE LED EXIT SIGN, CEILING
MOUNTED, RED LETTERS, WHITE BACKGROUND AND
SINGLE OR DOUBLE FACE
LUMARK FAIL-SAFE
XTORA9A-WG-XTORMX EXL-7-*-RW-*-*
277 V 277 V
7200 LUMEN LED LED
WITH UNIT
PROVIDED WITH FIXTURE
86 VA
VERIFY FINISH WITH ARCHITECT, MOUNT FIXTURE AT 20'-0" TO TOP OF FIXTURE
VERIFY COLOR/FINISH WITH ARCHITECT. SINGLE FACE, DOUBLE FACE, AND DIRECTIONAL INDICATOR OPTIONS SHALL BE IN ACCORDANCE WITH FLOOR PLANS.
SEAL
(RED DEVICE) TYPICAL FOR ANY DEVICE IN LEGEND
C
CLOCK RECEPTACLE
FLUORESCENT FIXTURE DIAGONAL SHADING DENOTES TO LIGHT FIXTURE CONNECTED TO CRITICAL BRANCH.
BONDING PLATE PIPE CLAMP FOR PLUMBING VENT THRU ROOF.
LIGHTING FIXTURE SCHEDULE NOTES: 1. SHADED FIXTURES IN PLAN VIEW ARE EMERGENCY LIGHTING FIXTURES PROVIDED WITH AN EMERGENCY BATTERY BACK-UP SOURCE.
PRELIMINARY DOCUMENTS
NOT FOR CONSTRUCTION
SPECIAL PURPOSE RECEPTACLE, RATING AS NOTED
FLUORESCENT FIXTURE DIAGONAL SHADING DENOTES HALF OF LAMPS
AIR TERMINATION DEVICE
2. VERIFY COLOR/FINISH OF ALL FIXTURES WITH THE ARCHITECT. 3. SINGLE FIXTURE LISTED IN SCHEDULE. ALL EQUIVALENT FIXTURES SHALL MEET OR EXCEED THE PERFORMANCE OF FIXTURES LISTED IN LIGHTING FIXTURE SCHEDULE.
LIGHTING CONTROL TIME CLOCK
CONNECTED TO CRITICAL BRANCH, OTHER HALF
GROUND TERMINAL
TO NORMAL BRANCH. (3 LAMP FIXTURES SHALL
C
PHOTOCELL, MOUNTED ON ROOF FACING NORTH
HAVE 2 LAMPS CONNECTED TO CRITICAL, 1 LAMP CONNECTED TO NORMAL).
BONDING CONDUCTOR
KEY PLAN
GND
GROUND BAR
FLUORESCENT FIXTURE
DN DOWN CONDUCTOR
PLUG-IN STRIP WITH RECEPTACLES, 18" O.C. UNLESS OTHERWISE INDICATED
COMPLETELY SHADED DENOTES LIGHT FIXTURE CONNECTED TO LIFE SAFETY BRANCH
G
COUNTERPOISE CONDUCTOR
CABLE TRAY
CIRCUIT.
PARAPET MOUNTED AIR TERMINAL P
J
JUNCTION BOX
FLUORESCENT FIXTURE HALF SHADING DENOTES HALF OF LAMPS CONNECTED
FLAT ROOF MOUNTED OR MECHANICAL F
CONDUIT SEAL-OFF FITTINGS
TO LIFE SAFETY BRANCH, OTHER HALF TO NORMAL BRANCH. (3 LAMP FIXTURES SHALL HAVE 2 LAMPS CONNECTED TO LIFE SAFETY, 1 LAMP
THRU-ROOF CONDUCTOR DN
SS C3
SURGE SUPRESSOR C3 = SERVICE ENTRANCE DEVICE
CONNECTED TO NORMAL).
SCALE
B3 = DISTRIBUTION BOARD DEVICE
FLUORESCENT WALL MOUNTED FIXTURE WITH
A3 = PANELBOARD DEVICE
WALL OUTLET BOX
ST
SHUNT-TRIP BUTTON - FLUSH MOUNTED UNLESS
OTHERWISE NOTED NEMA 3R FOR EXTERIOR LOCATIONS
HID, FLUORESCENT, OR INCANDESCENT FIXTURE
NOT TO SCALE
C
POWER CONNECTION TO EQUIPMENT
FLUORESCENT, OR INCANDESCENT WALL WASHER.
EXIT LIGHT FIXTURE
MAGNETIC MOTOR STARTER OR CONTACTOR
DIRECTION ARROWS AS SHOWN
SIZE AS NOTED
(SHADED QUADRANT INDICATES FACE(S) OF FIXTURE)
EDH-X
ELECTRIC DUCT HEATER
WALL MOUNTED EXIT LIGHT FIXTURE
5
MOTOR CONNECTION, NUMBER DENOTES HORSEPOWER
B
VFD
VARIABLE FREQUENCY DRIVE
DDC
DIRECT DIGITAL CONTROL PANEL
EXTERIOR LIGHT FIXTURE WITH ARMS AS SHOWN ON DRAWINGS
TRACK WITH TRACK LIGHT FIXTURE (TRIANGLES INDICATE QUANTITY OF LIGHT FIXTURES)
BATTERY PACK WITH TWIN HEADS
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.
No.
Description
Date
REVISIONS
DRAWN BY APPROVED BY CHECKED BY DATE
JMB GAC GAC 03/19/2014
TITLE
ELECTRICAL SYMBOL LEGEND
A
PROJECT NO.
50057109
E-000
SHEET NO.
6 F
E
5
4
PROPOSED NEW DUKE ENERGY PRIMARY SERVICE
3
2
1
ELECTRICAL KEY NOTES
#
KEYNOTE TEXT
1 PROPOSED LOCATION FOR DUKE ENERGY PRIMARY SERVICE CONDUCTORS
2 NEW PRIMARY SERVICE TO REFEED EXISTING DUKE ENERGY TRANSFORMERS SERVING "A", "B", AND "C" BARRACKS
3 EXISTING DUKE ENERGY PAD-MOUNTED SWITCHGEAR TO REMAIN.
4 EXISTING DUKE ENERGY TRANSFORMER TO REMAIN.
5 DEMOLISH EXISTING "FSG" SECONDARY SERVICE BACK TO EXISTING TRANSFORMER.
6 DEMOLISH ALL ELECTRICAL ASSOCIATED WITH VISITOR CENTER, FOOD SERVICE, AND LAUNDRY FACILITY. EXISTING EMERGENCY GENERATOR SERVES "A" AND "B" BARRACKS.
7 REFEED EXISTING "A" AND "B" BARRACKS' EMERGENCY FEEDS FROM NEW INFRASTRUCTURE BUILDING. VERIFY ALL EXISTING REQUIREMENTS.
8 DEMOLISH EXISTING DUKE ENERGY PRIMARY FEEDER, ASSOCIATED TRANSFORMERS BACK TO SOURCE.
Dewberry Architects Inc.
401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax
SAFE HARBOR
GENERAL NOTES:
1. TRANSFORMER, SWITCHGEAR, AND PULL BOX LOCATIONS ARE BASED UPON CIVIL DRAWINGS, ELECTRICAL UTILITY DRAWINGS, AND SATELLITE IMAGERY. FIELD VERIFY EXACT LOCATIONS.
2. UNDERGROUND FEEDER ROUTING IS DIAGRAMMATIC AND BASED UPON CIVIL DRAWINGS AND ELECTRICAL UTILITY DRAWINGS. REFER TO CIVIL AND ELECTRICAL UTILITY DRAWINGS FOR FURTHER INFORMATION.
3. TRANSFORMER DATA IS BASED UPON ELECTRICAL UTILITY DRAWINGS AND AN EXISTING FACILITY ELECTRICAL ASSESSMENT REPORT DATED JULY 19, 2006.
4. ALL WORK REQUIRED BY THE UTILITY COMPANY SHALL BE PERFORMED BY THE UTILITY COMPANY AND ALL ASSOCIATED COSTS SHALL BE INCLUDED BY THE DESIGN BUILDER.
5. DESIGN BUILDER TO SEQUENCE ALL DEMOLITION WITH OWNER TO MINIMIZE SHUTDOWNS TO ALL EXISTING OPERATIONS TO REMAIN.
6. PROVIDE EMERGENCY POWER TO ALL NEW SECURITY WORK IN EXISTING BUILDINGS. COORDINATEREQUIREMENTS WITH SECURITY DRAWINGS.
CROSS BAYOU MH
2' V ALLEY GU TTER
49TH ST N Pinellas County Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings 114400 North 49th Street Clearwater, FL.
EXISTING 208/120V, 3 PHASE, 4W, 75KVA, PAD-MOUNTED ELECTRICAL UTILITY TRANSFORMER (UNLABELED BLDG. ADJACENT TO HEALTH)
EXISTING 480/277V, 3 PHASE, 4W,
VT
150KVA, PAD-MOUNTED ELECTRICAL
UTILITY TRANSFORMER (MINI 1)
D
PROPOSED NEW DUKE ENERGY PRIMARY SERVICE
MH
2
VT
2
VT
T T
4
7
"B" PB
("A" AND "B")
7
T
"A"
4
(HEALTH)
HEALTTH CARE FACILITY
"M1"
2
T
8
SHERIFF ADMIN.
VT
MH
145TH AVE N
4
PB
("C" AND "FSC")
"C"
2
8
"M2"
SEAL
5
6
T
T
VT
1
6
PRELIMINARY DOCUMENTS
NOT FOR CONSTRUCTION
T
VT
EXISTING 480/277V, 3 PHASE, 4W,
T
150KVA, PAD-MOUNTED ELECTRICAL
1
T
UTILITY TRANSFORMER (MINI 2)
VT
C
1
PB
KEY PLAN
3
142ND AVE N
4
T
OCPD OCPD OCPD
(CENTRAL)
CENTRAL DIVISION
3
POND
PB PB PB
PB
POND
T TT
EXISTING PRIMARY-SIDE, MEDIUM VOLTAGE, UNDERGROUND FEEDERS. TYPICAL.
SCALE
T
4 SOUTH DIVISION
("A" SOUTH)
PINELLAS COUNTY
4 CRIMINAL COURT
(CJC)
COMPLEX
1" = 100'-0"
"G"
4
POND
POND
VT
(SA)
B
"F"
"E"
"D"
"C"
T
MAINTENANCE
A
1
ELECTRICAL SITE PLAN
Scale: 1" = 100'-0"
T
4
("F" SOUTH)
VT
JURISDICT IONAL WET LAND LINE
OHE
SIR LB021 (FI R 1/2" LB1344 0.30' S., 0.50' W.)
OHE
OHE
VT
VT
No.
Description
Date
REVISIONS
DRAWN BY APPROVED BY CHECKED BY DATE
JMB GAC GAC 03/19/2014
TITLE
ELECTRICAL SITE PLAN
PROJECT NO.
50057109
E-001
SHEET NO.
JJ J
H
Pinellas County
Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings
114400 North 49th Street Clearwater, FL.
6
5
F
A A.1
J
7 4
1 1.1
E
B
D
C
4
7 WP
J
10
SECURITY ELECTRONICS
101
6 6
6
6
10
5
DOCK FAN COILSUTONRITAGE
102
STAIR A
SA1
WP
WP
SALLYPORT SERVICE DRIVE
103
D
C
4 7 WP
PARKING AREA
E.9 F
B
1 1.1
1
FIRST FLOOR POWER PLAN
Scale: 1/8" = 1'-0"
4
3
2
3
5
6.9 7
WP
WP
WP
9
LOADING
DOCK
105
WP
9
5
BULK DRY
STORAGE
108
TV
WALK-IN REF. FAN COIL
5
UNIT
PROGRAM MEETING ROOM
110
COILING DOOR #2
5
3
4
TV DOCK STAGING 107
5
5 VAV BOX 5
JANITOR 142
BULK REFIG 2 STORAGE
109
J
STORAGE 112
PROGRAM MEETING ROOM
111
VAV BOX
5
JANITOR 114
INMATE TOILET
113
VAV BOX
OFFICE 115
PROGRAM MEETING ROOM
116
TV
INMATE TOILET
121
66
AV CLOSET 117
VAV BOX
STAFF
5
118
INMATE TOILET
119
STORAGE VAV BOX
5
WORKER
STAGING 122
WP
SEARCH 123
8
COILING DOOR #1
4
ELEVATOR A EA
1
WP
WP
6
TRASH COMPACTOR 5
WP
GARBAGE/ RECYCLE DOCK
106
WP
UTILITY WASH 136
OFFICE/ CONTROL
137 VAV BOX 5
FEC
C
5 CORRIDOR
141
CART WASH 139 4
4
J
L104
ELECTRICAL 140
ELEVBAT1OR
1
EEB-141
5
WP 5
5 WP
ELEVATOR
1
6
C EC
WP WP
6 L101
5 L109B
L109A L108B L108A
FEC
WATER HEATER
124
STAIR B
WP
SB1
STAFF
TOILET
5
1L21156
AIR COMPRESSOR
126 4
FAN COIL UNIT
L115
TRASH COMPACTOR WP
CLEAN LAUNDRY STORAGE 135
WATER TANK STORAGE 104
BEDDING STORAGE
134
MAINTENANCE SUPPLY 133
RISER ROOM 132
WP
UNIFORM STORAGE
131
VAV BOX 5
VAV BOX 5 BREAK ROOM 130
C
CENTRAL LAUNDRY
138
INMATE TOILET
129
CHEMICAL STORAGE
128
2448
2448
L114A 4
4 4
4
4 DRYERS 127
4
4
4
4 4
DRYER BOOSTER FAN L114B
4 4
L111A L111B L111C L111D L111E L111F L111G L111H
3
5
6.9 7
A
A A.1
B
1
ELECTRICAL KEY NOTES
#
KEYNOTE TEXT
1 DEDICATED RECEPTACLE FOR SUMP PUMP
2 J-BOX FOR WALK-IN REFRIGERATOR LIGHTING, DOOR HEATER (IF PROVIDED), AND CONTROLS. COORDINATE LOCATION, MOUNTING HEIGHT, AND REQUIREMENTS WITH FOOD SERVICE CONSULTANT AND SHOP DRAWINGS PRIOR TO ROUGH-IN. SEAL ALL CONDUIT PENETRATIONS AND MAKE CONNECTIONS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
3 COORDINATE LOCATION, MOUNTING HEIGHT, AND REQUIREMENTS WITH FOOD SERVICE CONSULTANT AND SHOP DRAWINGS PRIOR TO ROUGH-IN. SEAL ALL CONDUIT PENETRATIONS AND MAKE CONNECTIONS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
4 PROVIDE DEDICATED BRANCH CIRCUIT IN 208/120V PANELBOARD. COORDINATE VOLTAGE, CIRCUIT BREAKER/CONDUCTOR AMPERE RATING, PHASE, AND CONNECTION REQUIREMENTS WITH EQUIPMENT SELECTIONS. ADJUST CONDUCTOR AND CONDUIT SIZES FOR VOLTAGE DROP (AS REQUIRED).
5 PROVIDE DEDICATED BRANCH CIRCUIT IN 480/277V PANELBOARD. COORDINATE VOLTAGE, CIRCUIT BREAKER/CONDUCTOR AMPERE RATING, PHASE, AND CONNECTION REQUIREMENTS WITH EQUIPMENT SELECTIONS. ADJUST CONDUCTOR AND CONDUIT SIZES FOR VOLTAGE DROP (AS REQUIRED).
6 PROVIDE DEDICATED BRANCH CIRCUIT IN 208/120V PANELBOARD. ADJUST CONDUCTOR AND CONDUIT SIZES FOR VOLTAGE DROP (AS REQUIRED).
7 J-BOX FOR SECURITY GATE OPERATOR. COORDINATE LOCATION, MOUNTING HEIGHT, AND REQUIREMENTS WITH ARCHITECT AND SECURITY GATE SHOP DRAWINGS PRIOR TO INSTALLATION.
8 DISCONNECT SWITCH FOR DOCK LIFT. COORDINATE LOCATION, MOUNTING HEIGHT, AND REQUIREMENTS WITH ARCHITECT AND SECURITY GATE SHOP DRAWINGS PRIOR TO INSTALLATION.
9 DISCONNECT SWITCH FOR DOCK LEVELER. COORDINATE LOCATION, MOUNTING HEIGHT, AND REQUIREMENTS WITH ARCHITECT AND SECURITY GATE SHOP DRAWINGS PRIOR TO INSTALLATION.
10 J-BOX FOR SECURITY ELECTRONICS. COORDINATE LOCATION, MOUNTING HEIGHT, AND REQUIREMENTS WITH OWNER AND SECURITY CONTRACTOR PRIOR TO INSTALLATION.
GENERAL NOTES:
1. PROVIDE ELECTRICAL CONNECTIONS FOR ALL EQUIPMENT INDICATED ON ARCHITECTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION, OR OTHER EQUIPMENT PLANS AS REQUIRED. CONNECTION INFORMATION TO BE COORDINATED WITH FINAL CONSTRUCTION DOCUMENTS.
2. COORDINATE ALL LAUNDRY EQUIPMENT WITH LAUNDRY SERVICE DRAWINGS.
3. ALL FINAL LAUNDRY EQUIPMENT CONNECTIONS WILL BE PROVIDED AS REQUIRED BY FINAL LAUNDRY CONSTRUCTION DOCUMENTS INCLUDING ALL ELECTRICAL STUB-UP LOCATIONS, OVERCURRENT PROTECTION, CONDUIT AND WIRE REQUIREMENTS.
4. REFER TO TECHNOLOGY DRAWINGS FOR ALL SECURITY AND DATA INFRASTRUCTURE CONNECTION REQUIREMENTS. ALL EQUIPMENT COORDINATION SHALL BE IN ACCORDANCE WITH FINAL TECHNOLOGY CONSTRUCTION DOCUMENTS.
Dewberry Architects Inc.
401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax
C
SEAL
PRELIMINARY DOCUMENTS
NOT FOR CONSTRUCTION
D
KEY PLAN
SCALE
1/8" = 1'-0"
E.9 F
No.
Description
Date
REVISIONS
DRAWN BY APPROVED BY CHECKED BY DATE
JMB GAC GAC 03/19/2014
TITLE
FIRST FLOOR POWER PLAN
PROJECT NO.
50057109
E-110
SHEET NO.
6
5
4
3
2
F
A A.1
E
B
D
C
1 1.1
S1 GE
S1
G GE
GE
GE
G
S1
G
GE
GE
X S1
GE
D3E
FE
SECURITY ELECTRONICS
S1
101
DOCK STORAGE
102
STCAEIR
G
A
SA1
CE GE
S1
X
CE
G
S1 GE
GE
G
G
GE
GE
G
G
GE
SALLYPORT SERVICE DRIVE
103
GE
G
G
GE
GE
G
G
GE
D
C
G S1
GE
G
GE
G
G
GE
PARKING AREA
GE
G
E.9 F
B
GE S1
G
GE
X S1
1 1.1
1
FIRST FLOOR LIGHTING PLAN
Scale: 1/8" = 1'-0"
3
5
6.9 7
S1
GE
G
X
G
GE
GE
G
G
GE
GE
G
G
GE
GE
G
G
GE
TRASH COMPACTOR
GE
G
G
GE
GE
WATER TANK
G
STORAGE
104
G
GE
FE
F
F
FE
S1
S1
G
G
GE
BULK DRY
STORAGE
108
X
A1
A1E
X
A1E
A1
A1E
A1
A1E
A1
A1E
PROGRAM MEETING ROOM
110
PROGRAM MEETING ROOM
116
A1
A1E
A1
A1E
A1
A1
A1E
A1
A1E
A1E
WORKER X
S1
STAGING
12A12
GE
G
G
LOADING DOCK 105
FE
F
F
FE
FE
F
G DOCK STAGING 107 GE
G
GE
G
A1
G
G
A1E
G FE
GE
BULK REFIG STORAGE 109
FE
STORAGE 112 F
A1E 111
A1
A1E A1
A1 A1E
FE
JANITOR 114B1
A2E
FE
115
A2E B1E
A1
A1E
A1
INMFAETE
121
A1E
A1
A1E
STOFREAGE
A1E
B1
AV CFLEOSET
FE
FE
INMATE TOILET
A1
B1E
STAFF TOILET
1F19
118
A1E B1
SEARCH
B1 123
A1
A1
A1E
A1E
A1
X
A1E
A1
A1E
X
A1E
A1
ELEVATOR
D1E
A
D1E
EA
A1
A2E
A2E
OFFICE/ CONTROL A2E 137 A2E
X
X
A1E
A1
A1E
A1
A1E
CORRIDOR 141
FEC
A1E
C
A1E
D3E
F
FE
CART
ELEVATOR
ELEVATOR
WASH
ELECTRICAL D1E
B
D1E
D1E
C D1E
139
1D430E
EB
X
EC B1
A1
FEC HWEAAFTETEERR
X A1E
X X
CE
STAIR
B
SB1
X
S1
X
F
A1E
A1
A1E
X
GE
G
GE
G
GE
G
GE
GE
CE
X
STAFF
TOILET
125
X
F
FE X
FE
AIR
CE
COMPRESSOR
GARBAGE/ RECYCLE DOCK
F
F
G
GE
G
GE
G
GE
126
G
GE
106
F
UTILITY
WASH
FE
136
F
D3E
FE
F
CF LEAN LAUNDFREY
GE
G
GE
G
GE
G
GE
STORAGE
135
CENTRAL
D3
LAUNDRY
138
S1
FE
F
F
FE
G
GE
G
GE
G
GE
G
D3E
BEDDING STORAGE
134
DRYERS 127
D3
FE
F
F
FE
MAINTENANCE
GE
G
GE
G
GE
G
GE
SUPPLY
133
D3
D3E RISER ROOM 132 D3E
a
S1
FE
F
F
FE
UNIFORM
STORAGE
131
F
FE
F
BREAK ROOM 130
S1
ITNOMFIELAETTE
F CHEMICAL FE STORAGE
G
128
2448
2448
C
G S1
G
D3E
3
5
6.9 7
A
H
Pinellas County
Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings
114400 North 49th Street Clearwater, FL.
1
GENERAL NOTES: 1. REFER TO REFLECTED CEILING PLANS FOR EXACT LOCATIONS
OF FIXTURES. 2. ALL LIGHTING FIXTURES SHALL BE CONTROLLED VIA RELAY
CONTROL PANELS FROM THE MAIN BUILDING CONTROL/SECURITY ROOM. 3. PROVIDE UNSWITCHED CONDUCTORS TO ALL EMERGENCY LIGHTING POWER SUPPLIES IN DESIGNATED FIXTURES. 4. REFER TO SHEET E-000 FOR FIXTURE SCHEDULE.
A A.1
Dewberry Architects Inc.
401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax
B
C
SEAL
PRELIMINARY DOCUMENTS
NOT FOR CONSTRUCTION
D
KEY PLAN
SCALE
1/8" = 1'-0"
E.9 F
No.
Description
Date
REVISIONS
DRAWN BY APPROVED BY CHECKED BY DATE
JMB GAC GAC 03/19/2014
TITLE
FIRST FLOOR LIGHTING PLAN
PROJECT NO.
50057109
E-111
SHEET NO.
6
5
4
3
2
F
A A.1
E
B
D
C
D
C
E.9 F
B
1 1.1
3
5
6.9 7
F
F F
C
F F
F
F F
WP F
SECURITY ELECTRONICS
101
DOCK STORAGE
WP
102
1
FS TS
STAIR A
SA1
WP 5
F
WP
WP
SALLYPORT SERVICE DRIVE
103
PARKING AREA WP
F F F
BULK DRY STORAGE
108
PROGRAM MEETING ROOM
110
PROGRAM MEETING ROOM
116
WORKER STAGING
122
LOADING DOCK 105 WP/110cd
F
14 TS
WP H 3
ELEVATOR A EA
DOCK STAGING
107
WP F
PROGRAM MEETING ROOM
111
JANITOR 142
BULK REFIG STORAGE 109
F STORAGE
112
INMATE TOILET
113
JANITOR 114
OFFICE 115
INMATE TOILET
121
STORAGE 120
F AV CLOSET
117
STAFF TOILET
118
INMATE TOILET
119
SEARCH 123
F F
F
F
OFFICE/ CONTROL
137
FEC
C
CORRIDOR 141
14 TS
CART
ELEVATOR
WASH 139
WP
ELECTRICAL H 140
B EB
2
14 E
TS
ELEVATOR
H
C
EC
2
FEC
WATER HEATER
124
STAIR B SB1
F F
F
TRASH COMPACTOR
WP F
F
GARBAGE/ RECYCLE DOCK
106
UTILITY WASH 136
F WP
CLEAN LAUNDRY STORAGE 135
E STAFF TOILET 125
AIR COMPRESSOR
126
110cd
110cd
CENTRAL LAUNDRY
138
BEDDING STORAGE
134
DRYERS 127
WATER TANK STORAGE 104
MAINTENANCE SUPPLY 133
F
H
RISER ROOM 132
1
FS
TS
UNIFORM STORAGE
131
BREAK ROOM 130
INMATE TOILET
129
CHEMICAL STORAGE
128
2448
2448
F
1 1.1
3
5
1
FIRST FLOOR FIRE ALARM & MISC. SYSTEMS PLAN
Scale: 1/8" = 1'-0"
6.9 7
A
F F
A A.1
1
ELECTRICAL KEY NOTES
#
KEYNOTE TEXT
1 COORDINATE LOCATION WITH DIVISION 21 CONTRACTOR PRIOR TO INSTALLATION. PROVIDE ADDRESSABLE INPUT MONITORING MODULE(S) LOCATED WITHIN A CONDITIONED, ACCESSIBLE SPACE OR IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
2 MOUNT HEAT DETECTOR TO ELEVATOR PIT WALL AS INDICATED. LOCATE WITHIN 2'-0" OF SIDEWALL FIRE SPRINKLER PENDENT. COORDINATE LOCATION AND REQUIREMENTS WITH DIVISION 21 CONTRACTOR AND A.H.J. PRIOR TO INSTALLATION.
3 MOUNT SMOKE DETECTOR ABOVE ELEVATOR DOOR AS INDICATED.
4 TAMPER SWITCH FOR CONTROL VALVE SERVING ELEVATOR PIT SIDEWALL FIRE SPRINKLER PENDENT
5 COORDINATE LOCATION WITH A.H.J. PRIOR TO INSTALLATION.
GENERAL NOTES:
1. ALL NOTIFICATION DEVICES SHALL HAVE A LUMINOUS INTENSITY OF 75 CANDELA UNLESS OTHERWISE NOTED.
Dewberry Architects Inc.
401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax
B
Pinellas County
Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings
114400 North 49th Street Clearwater, FL.
C
SEAL
PRELIMINARY DOCUMENTS
NOT FOR CONSTRUCTION
D
KEY PLAN
SCALE
1/8" = 1'-0"
E.9 F
No.
Description
Date
REVISIONS
DRAWN BY APPROVED BY CHECKED BY DATE
JMB GAC GAC 03/19/2014
TITLE
FIRST FLOOR FIRE ALARM & MISC. SYSTEMS
PLAN
PROJECT NO.
50057109
E-112
SHEET NO.
................
................
In order to avoid copyright disputes, this page is only a partial summary.
To fulfill the demand for quickly locating and searching documents.
It is intelligent file search solution for home and business.
Related download
- english literature and composition practice exam
- apa quick reference handbook preface
- easy step by step free sprinkler system design
- random loot tables sly flourish
- code builder for minecraft education edition api
- items 1 14 must be filled out before generator signs item 15
- electrical symbol legend general notes
- adobe illustrator cc 17 1 amtlib dll crack
- the ultimate player s guide to minecraft
- http files 59 robux hack
Related searches
- john legend songland song
- songland john legend pick
- we need love john legend lyrics
- john legend we need love youtube
- songwriter john legend love love
- we need love john legend song
- john legend songland
- john legend song from songland
- electrical symbol chart pdf
- electrical drawing symbol key
- general science notes pdf
- matplotlib legend font colors