Horiba Valve Sequencer Math Logic



DAQStation Rate of Change Math Logic

Example is for a 1 hour Rate of Change

Inputs

Channel 001 is type ~TC – Type E – SPAN – 0. 0 to 100.0 ~ Degree F

Math channels

101 = 001*K01

This channel has the rolling average performed on it so we multiple the value from channel 001 times the total number of samples. This removes the Average function from the Rolling Average. It is now just a rolling buffer.

102 = [103.LT.K01?K02:(101-PRE(101))]

If> Then>Else statement. It will display ZERO until the counter has reached the buffer full number. Then once the buffer is full it will display the rate of change.

103 = [103.EQ.K01?103:103+K03]

Counter. Used to skip until the buffer is full

Rolling Average

101 = ON

Interval = 5s

Number of Samples = 720

102 = ON

Interval = 5s

Number of Samples = 1

103 = ON

Interval = 5s

Number of Samples = 1

Constants

K01 = 720 K02 = 0 K03 = 1

Note: The maximum Number of Samples for the Rolling Average is 1500. You need to adjust between the Interval Time and Number of Samples to reach the time needed for the rate of change. The channels 102 and 103 MUST HAVE THE SAME INTERVAL TIME as the Interval used in channel 101 but the Number of Samples for 102 and 103 will always be 1. We are syncing the sample rate with 101.

Other examples are:

24 hour rate of change = Interval 1 minute and Number of Samples is 1440

15 minute rate of change = Interval 1 second and Number of Samples is 900

................
................