Smart Series Commercial Performance Data - Triangle Tube

2006-21 Smart-Performance Data Revised date: 1/12/07

Smart Series Commercial Performance Data

Performance Data Charts

Use Of These Charts Will Determine:

- Model Of The Indirect-Fired Water Heater - MBH Net Boiler Output Required For Hot Water Generation - Boiler Water Temperature Required

To Use The Performance Charts, These Conditions Must Be Known:

- Domestic Water Temperature Rise - Continuous Draw GPH or First Hour Rating GPH

? For the purpose of this manual, First Hour Rating GPH = Continuous Draw GPH + Usable Storage*

? For hot water requirements greater than those listed, multiple water tanks must be used.

? Smart Series indirect-fired water heaters will absorb less than 200,000 BTU per hour with boiler supply temperature of 240? F and domestic water outlet temperature of 210? F.

? The installing contractor assumes responsibility for compliance with state or local codes.

Model

Smart-60 Smart-80 Smart-100 Smart-120

Usable Storage [gal]

50 gal 60 gal 80 gal 100 gal

* Approximately 85% of storage capacity

Min. Circulator Flow Rate [gpm]

20 gpm 22 gpm 24 gpm

28 gpm

Boiler Head loss at Min. Flow 4.0 Ft 3.5 Ft 4.5 Ft

4.0 Ft

1

200? F Boiler Water Temperature

30? F Domestic Rise

Boiler Output (MBH) 50 75 100 150 200 250 300 350 400 450 500 550

600 or More

Boiler Output (MBH) 50 75 100 150 200 250 300 350 400 450 500 550

600 or More

Smart-60 200 300 400 600 800 1000 1200 1400 1580 1580 1580 1580 1580

Smart-60 150 225 300 450 600 750 900 1050 1130 1130 1130 1130 1130

Continuous Draw GPH

Smart-80 200 300 400 600 800 1000 1200 1400 1600 1730 1730 1730 1730

Smart-100 200 300 400 600 800 1000 1200 1400 1600 1800 2000 2000 2000

Smart-120 200 300 400 600 800 1000 1200 1400 1600 1800 2000 2200 2345

Continuous Draw GPH

Smart-80 150 225 300 450 600 750 900 1050 1200 1240 1240 1240 1240

Smart-100 150 225 300 450 600 750 900 1050 1200 1350 1440 1440 1440

Smart-120 150 225 300 450 600 750 900 1050 1200 1350 1500 1650 1685

40? F Domestic Rise

2

200? F Boiler Water Temperature

50?F Domestic Rise

60? F Domestic Rise

Boiler Output (MBH) 50 75 100 150 200 250 300 350 400 450 500

550 or more

Boiler Output (MBH) 50 75 100 150 200 250 300 350 400

450 or more

Boiler Output (MBH) 50 75 100 150 200 250 300 350 400

450 or more

Smart-60 120 180 240 360 480 600 720 840 860 860 860 860

Continuous Draw GPH

Smart-80 120 180 240 360 480 600 720 840 940 940 940 940

Smart-100 120 180 240 360 480 600 720 840 960 1080 1090 1090

Smart-120 120 180 240 360 480 600 720 840 960 1080 1200 1280

Smart-60 100 150 200 300 400 500 600 690 690 690

Continuous Draw GPH

Smart-80 100 150 200 300 400 500 600 700 740 740

Smart-100 100 150 200 300 400 500 600 700 800 812

Smart-120 100 150 200 300 400 500 600 700 800 900

Smart-60 90 130 170 260 345 430 515 550 550 550

Continuous Draw GPH

Smart-80 90 130 170 260 345 430 515 600 600 600

Smart-100 90 130 170 260 345 430 515 600 666 666

Smart-120 90 130 170 260 345 430 515 600 685 740

70? F Domestic Rise

3

200? F Boiler Water Temperature

80? F Domestic Rise

90? F Domestic Rise

Boiler Output (MBH) 50 75 100 150 200 250 300 350 400

450 or more

Boiler Output (MBH) 50 75 100 150 200 250 300 350 400

450 or more

Boiler Output (MBH) 50 75 100 150 200 250 300 350

400 or More

Smart-60 75 115 150 225 300 375 450 450 450 450

Smart-60 70 100 135 200 270 335 360 360 360 360

Smart-60 60 90 120 180 240 280 280 280 280

Continuous Draw GPH

Smart-80 75 115 150 225 300 375 450 500 500 500

Smart-100 75 115 150 225 300 375 450 525 560 560

Smart-120 75 115 150 225 300 375 450 525 600 640

Continuous Draw GPH

Smart-80 70 100 135 200 270 335 400 450 450 450

Smart-100 70 100 135 200 270 335 400 470 500 500

Smart-120 70 100 135 200 270 335 400 470 535 560

Continuous Draw GPH

Smart-80 60 90 120 180 240 300 360 360 360

Smart-100 60 90 120 180 240 300 360 400 400

Smart-120 60 90 120 180 240 300 360 420 450