900VPR-2-280/600V Voltage Protection Relay

PRDELAITMAISNHAEREYT

900VPR-2-280/600V

DIN 35mm

Voltage Protection Relay

Features

! 1? - 2 Wire, 3? - 3 Wire, 3? - 4 Wire input ! Monitors Under voltage, Over voltage, Under frequency,

Over frequency, Phase asymmetry, Phase failure, Phase sequence and Neutral loss in 3? - 4 Wire system ! True RMS measurement ! Power ON delay, Trip time delay and Recovery time delay ! Adjustable switching hysteresis ! Two Alarm relays with NO or NC operation selectable

Display specifications

Type Display No. of LED No. of push button

Digital Liquid Crystal Display 3 3

LED indication chart

Condition No fault Trip (Relay1) Trip (Relay2) Trip (If Programming for both relay)

POWER LED ON

ON

ON

ON

'R1' LED OFF ON OFF ON

'R2' LED OFF OFF ON ON

Input specifications Functions Measurements

Time setting Alarm indications Latching Reset Measuring range

Trip settings Under voltage

Over voltage

Under frequency Over frequency Phase asymmetry Hysteresis Voltage Frequency Asymmetry

Under voltage, Over voltage, Under frequency, Over frequency, Phase asymmetry, Phase failure, Phase sequence and Neutral loss Note: Neutral fault is disable below 100V for R phase Power on delay, Trip time delay and Recovery time delay, Response time Trip Selectable Auto / Manual 3? - 3 wire (L-L) : 280 to 600V AC 3? - 4 wire (L-N) : 160 to 300V AC 1? - 2 wire (L1-N1) : 160 to 300V AC

280 to 600V AC (L-L) [for 3? - 3 wire] 160 to 300V AC (L-N) [for 3? - 4 wire] 160 to 300V AC (L1-N1) [for 1? - 2 wire] 280 to 600V AC (L-L) [for 3? - 3 wire] 160 to 300V AC (L-N) [for 3? - 4 wire] 160 to 300V AC (L1-N1) [for 1? - 2 wire] 45 - 65Hz 45 - 65Hz 5 - 99%

1.0V -99.9V 0.2 - 2.0Hz 2.0 - 20%

Input specifications Resolution Voltage Frequency Accuracy Voltage Frequency Time

Output specifications Relay output Relay rating

Environmental specifications Operating temperature Storage temperature Humidity (Non condensing) Degree of protection

Mechanical specifications Dimension (in mm) Weight (unpacked) Mounting Terminal torque & capacity Enclosure

Dimensions (All are in mm) 35

90 90 67.50

1V 0.1Hz ?1% of full range ?0.3Hz ?5% of setting, ?250ms

2 Relays each SPDT (1 C/O) NO (5A @ 250V AC) , NC (3A @ 250V AC)

0 to 55?C -20 to 70?C Up to 95% RH IP20

35 x 90 x 70.5 (W x H x D) 135 gms Din Rail 0.5 NM LEXAN N923(PC)

45

70.50



1

900VPR-2-280/600V

Terminal connection

RELAY 1

15 18 16

COM1

NO1

NC1

RELAY 2

26 28 25

NC2

NO2 COM2

L2

L3

N L1

Compliance Applicable EMC standards Product standard - IEC 60947-2 Category Electrostatic discharge Electrical fast transient / Burst Electromagnetic field Surge Conducted RF Rated power frequency Voltage dip / Short interruptions Conducted emissions Radiated emissions Emission & Immunity

Reference standards IEC 61000-4-2 IEC 61000-4-4 IEC 61000-4-3 IEC 61000-4-5 IEC 61000-4-6 IEC 61000-4-8 IEC 61000-4-11 CISPR-11 CISPR-22 IEC 61326-1

Environmental Product standard : IEC 60947-2 Safety test standard : IEC 61010-1

1. Cold condition 2. Dry heat 3. Rapid change of temperature 4. Damp heat 5. Adhesion of coating 6. Humidity conditioning 7. Insulation resistance of conductors

Voltage Protection Relay

Ordering information

Product code 900VPR-2-280/600V-CE-RoHS

Operating range 280 to 600V AC

Certication ? ? ?



2

................
................

In order to avoid copyright disputes, this page is only a partial summary.