Contactors for NEMA Design E motors shall have a horsepower rating not less than 1.4 times the rating of a motor rated 3 kW through 75 kW, have a rating not less than 1.3 times the rating of the motor rated over 75 kW, or be marked for use with a Design E motor (see NEC Article 430-83, Exception No. 1). ................
................