1063 RFP Section 4_FINAL_11272013

Main breakers shall be individually mounted and have ground fault protection. Feeder circuit breakers shall be molded case and group mounted. There are two HVL switches, one for the building load and one for the fire and jockey pumps per NEC 695.5 or as required by the authority having jurisdiction. ................
................