EGSA - Electrical Generating Systems Association

The voltage regulation shall be plus/minus 2% from no load to full load with plus/minus 5% speed change and a 15 C. rise in ambient room temperature as measured by the light beam oscillograph or equivalent. The generator voltage dip from no load to full load shall not exceed 22% as measured by the light beam oscillograph or equivalent. ................
................