SECTION 235500 - FUEL-FIRED HEATERS

After the water heater has been installed, the Subcontractor shall boil out the water heater and the entire piping system at low pressure for a period of not less than 8 hours by recirculating a solution consisting of 4 lb trisodium phosphate for each 1000 lb of water contained in the system. ................
................