NEMA Contactor and Starter Specifications - Technical Data

Technical Data

Original Instructions

NEMA Contactor and Starter Specifications

Bulletins 500, 502, 503, 505, 506, 506X, 507, 507X, 509, 512, 513, 522E/F/G, 523E/F/G

Topic

Page

Summary of Changes

2

Specifications

3

Electrical Ratings

3

Mechanical Ratings

4

Construction

4

Environmental

5

Short Circuit Rating

5

AC Coil Data

6

Auxiliary Contacts (NEMA A600 and P300) -- Bulletin 595, 596

6

Load-life Curves

6

Approximate Dimensions

8

Type 1 General Purpose Lift-Off Enclosure

8

Type 1 Hinged Enclosure -- with or without Control Transformer

9

Type 1 General Purpose Painted Enclosure

10

Type 3R/12 Rainproof, Dusttight, 4/4X Watertight, Non-metallic Enclosure -- with or without Control Transformer

11

Type 3R/4/12 Rainproof, Dusttight -- Industrial Use Enclosures

12

Unilock Enclosures -- Type 3R, 7 & 9, Class I Groups C & D, Class II, Groups E, F & G -- Divisions 1 & 2

13

Bolted Enclosures -- Type 3R, 7 & 9, Class I, Groups C & D, Class II, Groups E, F & G -- Divisions 1 & 2

14...18

Additional Resources

19

NEMA Contactor and Starter Specifications Technical Data

Summary of Changes

This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes.

Topic Updated specifications , type 1 hinged enclosure figures and size tables

Page throughout

2

Rockwell Automation Publication 500-TD014D-EN-P - March 2023

NEMA Contactor and Starter Specifications

Specifications

Electrical Ratings

NEMA Size

Load Voltage

Continuous Current Rating

Service Limit Current Rating (1)

Maximum Hp Rating (Non-plugging and non-jogging duty)

Maximum Hp Rating (Plugging and jogging duty) (2)

[V]

[A]

115

200

00

230 380

9

460

575

115

200

0

230 380

18

460

575

115

200

1

230 380

27

460

575

1P

115 230

36

115

200

2

230 380

45

460

575

115

200

3

230 380

90

460

575

115

200

4

230 380

135

460

575

115

200

5

230 380

270

460

575

[A]

1?

3?

1?

3?

1/3

--

1/4

--

--

1-1/2

--

1

11

1

1-1/2

1/2

--

1-1/2

--

1 1

--

2

--

1-1/2

--

2

--

1-1/2

1

--

1/2

--

--

3

--

1-1/2

21

2 --

3 5

1

1-1/2

--

1-1/2

--

5

--

2

--

5

--

2

2

--

1

--

--

7-1/2

--

3

32

3

7-1/2

2

--

10

--

3 5

--

10

--

5

--

10

--

5

42

3 5

--

1-1/2

--

--

3

--

3

--

--

10

52

7-1/2 --

15 25

--

25

--

25

2

--

--

7-1/2

5

10

--

15

--

15

--

15

7-1/2

--

7-1/2

--

--

25

--

15

104

15 --

30 50

15 --

20 30

--

50

--

30

--

50

--

30

--

--

--

--

--

40

--

25

156

-- --

50 75

-- --

30 50

--

100

--

60

--

100

--

60

--

--

--

--

--

75

--

60

311

-- --

100 150

-- --

75 125

--

200

--

150

--

200

--

150

Transformer Primary

Switching kVa Rating

(Inrush Current 20 times Continuous Current)

1?

3?

--

--

--

--

--

--

--

--

--

--

--

--

0.6

--

--

1.8

1.2

2.1

--

--

2.4

4.2

3

5.2

1.2

--

--

3.6

2.4

4.3

--

--

4.9

8.5

6.2

11

--

--

--

--

2.1

--

--

6.3

4.1

7.2

--

--

8.3

14

10

18

4.1

--

--

12

8.1

14

--

--

16

28

20

35

6.8

--

--

20

14

23

--

--

27

47

34

59

14

--

--

41

27

47

--

--

54

94

68

117

Transformer Primary

Switching kVa Rating

(Inrush Current = 20 to 40 times

Continuous Current)

1?

3?

--

--

--

--

--

--

--

--

--

--

--

--

0.3

--

--

0.9

0.6

1

--

--

1.2

2.1

1.5

2.6

0.6

--

--

1.8

1.2

2.1

--

--

2.5

4.3

3.1

5.3

--

--

--

--

1

--

--

3.1

2.1

3.6

--

--

4.2

7.2

5.2

8.9

2

--

--

6.1

4.1

7.0

--

--

8.1

14

10

18

3.4

--

--

10

6.8

12

--

--

14

23

17

29

6.8

--

--

20

14

24

--

--

27

47

34

59

Capacitor Switching kVAR (3)

3? -- -- -- -- -- -- -- -- -- -- -- -- -- -- 6 -- 13.5 17 -- -- -- -- 12 -- 25 31 -- -- 27 -- 53 67 -- -- 40 -- 80 100 -- -- 80 -- 160 200

Maximum Circuit Closing Inrush

Current [A] Peak

Including Offset 3? 87

140

288 -- -- 483

947

1581

3163

Rockwell Automation Publication 500-TD014D-EN-P - March 2023

3

NEMA Contactor and Starter Specifications Specifications

NEMA Size

Load Voltage

Continuous Current Rating

Service Limit Current Rating (1)

Maximum Hp Rating (Non-plugging and non-jogging duty)

Maximum Hp Rating (Plugging and jogging duty) (2)

Transformer Primary

Switching kVa Rating

(Inrush Current 20 times Continuous Current)

Transformer Primary

Switching kVa Rating

(Inrush Current = 20 to 40 times

Continuous Current)

Capacitor Switching kVAR (3)

Maximum Circuit Closing Inrush

Current [A] Peak

Including Offset

[V]

[A]

[A]

1?

3?

1?

3?

1?

3?

1?

3?

3?

3?

115

--

--

--

--

27

--

14

--

--

200

--

150

--

125

--

81

--

41

--

6

230 380

540

621

--

200

--

--

300

--

150

54

250

--

94 --

27 --

47 --

160 --

6326

460

--

400

--

300

108

188

54

94

320

575

--

400

--

300

135

234

68

117

400

230

--

300

--

--

--

--

--

--

240

7

460

810

932

--

600

--

--

--

--

--

--

480

9470

575

--

600

--

--

--

--

--

--

600

230

--

450

--

--

--

--

--

--

360

8

460

1215

1400

--

900

--

--

--

--

--

--

720

14205

575

--

900

--

--

--

--

--

--

900

(1) Service-Limit Current Ratings -- The service-limit current ratings that are shown represent the maximum rms current, in amperes, which the controller shall be permitted to carry for protracted periods in normal service. At service-limit current ratings, temperature rises shall be permitted to exceed those obtained by testing the controller at its continuous current rating. The current rating of overload relays or the trip current of other motor protective devices that are used shall not exceed the service-limit current rating of the controller.

(2) Plugging or Jogging Service -- The listed horsepower ratings are recommended for those applications requiring repeated interruption of stalled motor current that is encountered in rapid motor reversal in excess of five openings or closings per minute and shall not be more than ten in a ten minute period.

(3) If maximum available current (at capacitor terminals) is greater than 3000 A, contact your local Rockwell Automation sales office, Allen-Bradley distributor, or NEMA ICS-2 Standard.

Mechanical Ratings

NEMA

Mechanical Life

Size

(Millions of Operations)

00

10

0

10

1

10

2

10

3

5

4

5

5

5

6

5

7

--

8

--

Maximum Number of Auxiliary Contacts

5 8 8 8 8 8 8 4 8 8

Operating Time [ms]

Pick-up (Average)

Drop-out (Average)

20

16

21

16

22

14

27

13

37

20

27

20

25

18

25...79

10...22

88

40

88

45

Construction

Required Torque on

NEMA

Wire Size for Power Terminal Wire Type of Power

Size

Power Terminals Clamps and Pressure

Terminal

Connectors or Lugs

00

#16...10 AWG

9 lb?in

Pressure terminals

0 1

#14...10 AWG #14...8 AWG

20 lb?in 20 lb?in

Saddle or wire clamps

2

#14...4 AWG

45 lb?in

3 4

#8...1/0 AWG #6...4/0 AWG

150 lb?in 275 lb?in

Pressure terminals

5

#4 AWG...500 MCM

375 lb?in

6

7

Lugs sold separately(1)

8

(1) Contact your local Allen-Bradley distributor or Rockwell Automation sales office.

Contact Material Power Contacts Auxiliary Contacts

Requirements for Sizing of Wire

Silver alloy

All wire rated 167 ?F

Silver

(75 ?C) or higher must be sized per the local

Electrical Code for

167 ?F (75 ?C) wire.

4

Rockwell Automation Publication 500-TD014D-EN-P - March 2023

Environmental

NEMA Size

00

0 1 2 3 4 5 6 7 8

Operating Position Horizontal

Vertical

Horizontal Vertical

NEMA Contactor and Starter Specifications Specifications

Operating Temperature Range

Altitude

Starters with eutectic alloy Overload relay

?13...+149 ?F (?25...+65 ?C) Starters with SMPTM Overload relay

?13...+131 ?F (?25...+55 ?C) (provided condensation is

prevented)

10 000 feet before derating

CorrosionResistance All metal parts are treated for corrosion-resistance

Short Circuit Rating

Combination contactors and starters with disconnect switch: Bulletin 502, 506, 512, 522E, 522F, and 522G

Combination Contactors and Starters with Disconnect Switch: Bulletin 502, 506, 512, 522E, 522F, and 522G

NEMA Size

Fuse

Available Short Circuit Amperes

Maximum Voltage

Type

RMS Symmetrical [A]

[V]

0...3

H, K

5000

4...5

H, K

10 000

0...5

J, R

100 000

600

6

L

18 000

7

L

18 000

Combination Lighting Contactors with Disconnect Switch: Bulletin 502L

Lighting Contactor Rating [A]

Fuse

Available Short Circuit Amperes

Maximum Voltage

Type

RMS Symmetrical [A]

[V]

20...100

H, K

5000

200...300

H, K

10 000

600

20...300

J, R

100 000

Combination Contactors and Starters with Circuit Breaker: Bulletin 503, 507, 513, 523E, 523F, and 523G

Enclosure Type

NEMA

Available Short Circuit Amperes

Maximum Voltage

Size

RMS Symmetrical [A]

[V]

1, 3R, 3R/4/12, 4/4X (stainless)

Unilock 3R, 7, & 9

0...5

65 000

480

Bolted 3R, 7, & 9

3R, 3R/4/12, 4/4X (stainless)

1, 3R, 3R/4/12, 4/4X (stainless)

0...5

25 000

Unilock 3R, 7, & 9 Bolted 3R, 7, & 9

3R, 3R/4/12, 4/4X (stainless)

Enclosure Type

1, 3R, 3R/4/12, 4/4X (stainless) Unilock 3R, 7, & 9 Bolted 3R, 7, & 9

1, 3R, 3R/4/12, 4/4X (stainless) Unilock 3R, 7, & 9 Unilock 3R, 7, & 9 Bolted 3R, 7, & 9

0...5

10 000

6

18 000

7

25 000

Combination Lighting Contactors with Circuit Breaker: Bulletin 503L

Lighting Contactor Rating [A]

Available Short Circuit Amperes RMS Symmetrical [A]

20...300

65 000

20...300

65 000

20...300

65 000

20...300

25 000

20...100

20...300

10 000

20...300

600

Maximum Voltage [V] 480 600

Rockwell Automation Publication 500-TD014D-EN-P - March 2023

5

................
................