14HUG32AF

Non-reversing motor starter NEMA controller size 3 3-Phase, 3-Pole Maximum voltage rating 600VAC Max Hp 60Hz: 25@200V; 30@230V; 50@460V; 50@575V Solid-state overload relay(s) with 25?100A range Control voltage 110VAC 50Hz / 120VAC 60Hz Open device (no enclosure)

Image is representative and may not depict the actual product. General technical data: Weight Height x Width x Depth Finger-safe (main circuit / control circuit) Maximum altitude Ambient storage temperature Ambient operating temperature Humidity (% non-condensing) Rated impulse voltage resistance Rated insulation voltage Country of origin Contactor: Number of NO main contacts Amp rating Mechanical operating cycles Internal/standard auxiliary contact: Number of NC / NO auxiliary contacts Rating Optional auxiliary contact: Max number of NC / NO auxiliary contacts Rating Coil: Voltage Sealed watts Inrush / sealed power Normal coil operating limits (% of rated voltage) Typical drop-out volts (% of rated voltage) Pick-up time / Drop-out time Overload Relay: Current range Trip Class Trip detection Phase failure sensitivity Repeat accuracy Reset options External reset Test function Conformal coating on printed circuit board Number of NC / NO auxiliary contacts Rating of auxiliary contacts Single contact isolation

Siemens Industry, Inc. 3333 Old Milton Parkway, Alpharetta, GA 30005 Subject to change without prior notice.

7.5 lb 9.78 x 6.75 x 5.19 in. No / No 6560 ft (-30 to 65)?C / (-22 to 149)?F (-20 to 40)?C / (-4 to 104)?F (no data) (no data) (no data) Mexico

3 90A 5,000,000

0NC / 1NO 10A@600VAC (A600), 5A@600VDC (P600)

7 total 10A@600VAC (A600), 5A@600VDC (P600)

110VAC 50Hz / 120VAC 60Hz Coil 14W 310 / 26 VA 85% - 110% 50% 26-41 / 14-19 msec

25?100A Class 5 / 10 / 20 (factory set) / 30 Overload, phase failure, phase unbalance, ground fault Trip time after phase-loss: < 3 sec Within 1% Manual, automatic and remote No Electronics & manual actuation Yes 1NC / 1NO 5A@600VAC (B600), 1A@250VDC (R300) 600V

9/28/2015 14HUG32AF

Page 1 of 4

Dual contact isolation Enclosure: Type Rating

Mounting/wiring: Mounting orientation Mounting type Line side connection type / torque Line side solid & stranded conductors

Load side connection type / torque Load side solid & stranded conductors Coil connection type / torque Coil solid & stranded conductors Main auxiliary contact connection type / torque Main auxiliary contact solid & stranded conductors OLR auxiliary contact connection type / torque OLR auxiliary contact solid & stranded conductors Short circuit current rating: Fuses Thermal Magnetic Circuit Breaker Certificates/approvals:

Additional information:

300V differing polarity / 600V common polarity

Open device (no enclosure) NA

Vertical Surface Box lug / 120 lb-in.

1x(14 - 2/0 AWG) 75?C AL or CU Box lug / 120 lb-in. 1x(14 - 2/0 AWG) 75?C AL or CU Screw / 5 lb in. - 12 lb in. 2 x (16 - 12 AWG) CU 60/75?C (no data) (no data) Screw / 7 lb in. - 10 lb in. 2 x (20 - 14 AWG) CU 60/75?C

10kA@600V (Class H or K); 100kA@600V (Class R or J) 14kA@240V; 10kA@600V

UL (file no. E14900) cUL (file no. E14900 for Canada) CSA (file no. LR 6535) ISO 9001 certification

Brochure OLR instruction sheet & trip curves

Siemens Industry, Inc. 3333 Old Milton Parkway, Alpharetta, GA 30005 Subject to change without prior notice.

9/28/2015 14HUG32AF

Page 2 of 4

Siemens Industry, Inc. 3333 Old Milton Parkway, Alpharetta, GA 30005 Subject to change without prior notice.

9/28/2015 14HUG32AF

Page 3 of 4

Siemens Industry, Inc. 3333 Old Milton Parkway, Alpharetta, GA 30005 Subject to change without prior notice.

9/28/2015 14HUG32AF

Page 4 of 4

................
................

In order to avoid copyright disputes, this page is only a partial summary.

Google Online Preview   Download