SECTION 13921 - Government of New York

A. Motor (Nameplate) Voltage: 1. 120/208 V and 277/480 V, Three Phase, 4W Premises Wiring Systems: a. Motors Less Than 1/2 HP: NEMA standard motor voltage 115 V, single phase, 60 Hz. b. Motors 1/2 HP and Larger: 1) 208 Volt Circuit: NEMA standard motor voltage 200 V, three phase, 60 Hz. 208 V, 208-230 V, 220 V, or 230 V motors are not acceptable. ................
................